Professional Documents
Culture Documents
IGEM-G-5 Edition 2 - INSTALLATION PIPEWORK, GAS APPLIANCES AND
IGEM-G-5 Edition 2 - INSTALLATION PIPEWORK, GAS APPLIANCES AND
IGEM-G-5 Edition 2 - INSTALLATION PIPEWORK, GAS APPLIANCES AND
9.1.1 Installation pipework shall be designed and installed in accordance with BS 6891
or IGEM/UP/2, as appropriate, and must be installed and maintained in
accordance with GS(I&U)R.
The maximum pressure drop from the outlet of the gas meter installation to any
appliance inlet connection shall not exceed 1 mbar under maximum flow
conditions.
9.1.3 Where the meter installation is remote from the dwelling, the designer and/or
the installer of the installation pipework shall determine the pipe diameter and
installation volume.
Where the pipe diameter exceeds 35 mm, the installation shall be designed and
installed in accordance with IGEM/UP/2 and a notice should be placed near or
adjacent to the meter outlet point indicating that the pipework diameter exceeds
35 mm.
Where the installation volume exceeds 0.035 m3, the installation shall be tested
and commissioned in accordance with either IGE/UP/1 or IGE/UP/1A; and a
notice shall be placed near or adjacent to the meter outlet point indicating that
the installation volume exceeds 0.035 m3.
where pipework passes through a dwelling other than the one it supplies, it
shall be enclosed in a purpose-provided duct
pipework passing through a wall or floor shall be sleeved and take the
shortest practical route
Note: The coating on pliable corrugated tubing/copper does not fulfil such a purpose and a
purpose designed sleeve has to be applied i.e. the sleeve needs to be corrosion
resistant, impermeable to gas and protecting the enclosed pipe against failure by
movement of the structure.
67
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk
IGEM/G/5 Edition 2 Licensed for use by National Grid plc only
any duct or other void such as a ceiling void containing installation pipework
shall be ventilated in accordance with BS 8313
Note: Where a duct is continuous, ventilation can, normally, be achieved by providing openings
at top and bottom, direct to outside air, in accordance with BS 8313. Where a duct takes
the form of an enclosure at each storey level, ventilation in accordance with BS 8313 is,
normally, required at each storey level.
Similarly as for pipelines, the provision of ventilation air via purpose-provided ducts is not
a preferred arrangement. Where such an arrangement is made, the ventilation provided
has to be sufficient as to achieve the required ventilation levels for the pipework itself.
Note: For proprietary systems (e.g. external PE riser systems), see the manufacturer’s
instructions.
68
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk
IGEM/G/5 Edition 2 Licensed for use by National Grid plc only
9.2.1 Selection
Any new appliance shall be CE marked and be suitable for use in the particular
circumstances that apply in multi-occupancy buildings with regard to flueing and
ventilation.
Note 2: A device that only attempts automatically to re-light gas does not satisfy this clause.
where the appliance is to be installed in a timber framed building, the
appliance manufacturer’s instructions have to advise that the appliance is
suitable for installing in such a building.
9.2.2 Installation
69
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk
IGEM/G/5 Edition 2 Licensed for use by National Grid plc only
9.3.1 Any person carrying out maintenance of a gas appliance must be competent to
carry out the work.
70
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website: www.igem.org.uk