Professional Documents
Culture Documents
Acoustic Measuring of Partial Discharge in Power Transformers
Acoustic Measuring of Partial Discharge in Power Transformers
net/publication/231023331
CITATIONS READS
25 2,318
2 authors:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by José Ramírez-Niño on 18 September 2014.
This article has been downloaded from IOPscience. Please scroll down to see the full text article.
(http://iopscience.iop.org/0957-0233/20/11/115108)
Download details:
IP Address: 200.4.4.86
The article was downloaded on 12/10/2009 at 16:14
Abstract
Power transformers’ reliability can be seriously affected by partial discharges. For this reason,
it is necessary to implement technical methods to identify endangered equipment before
catastrophic failures occur. A well-known method that can be applied either in the laboratory
or in the field is the detection and localization of partial discharges, by means of the analysis of
the acoustic signals they produced. An innovative partial discharge detector was developed
based on the analysis of an acoustic or electrical PD signal envelope. This paper describes the
architecture of the developed acoustic detector, which is composed of a set of ultrasonic
sensors, signal conditioning and control modules, a graphical interface and the required
software for the location of the affected area within the transformer. The conditioning and
control modules perform analog to digital conversion, arrival time measurement,
communication and control operations. Finally, some power transformer diagnostic testing is
presented and discussed.
reference obtained from the power supply, allowing the user innovative characteristic regarding the analysis of the signals
to obtain a diagram called NQØ (number, charge and phase). coming from the sensors, which have a resonance frequency
The acoustic method is a very attractive alternative for in the range of 150 kHz. The response to an acoustic transient
on-line partial discharge detection in power transformers. The impulse is shown in figure 1. As depicted in this figure, the
transformer tank is grounded; therefore, the sensors can be acoustic partial discharge signal reaches a maximum value and
placed, in a safe way, over any point of any wall of the decreases exponentially with time. The signals oscillate at the
transformer’s tank in order to detect the acoustic emission resonant frequency mainly associated with frequency response
of partial discharges. Partial discharge signals travel through of the sensors.
the insulating oil of the transformer, and they are practically Two important parameters are extracted from the wave
immune to interference caused by corona and other external shape. The first one is maximum amplitude, which provides
sources. By correlating the detected acoustic signals with the information regarding the strength of the phenomenon. The
phase voltage, it is possible to screen discharge pulses from magnitude can also be related to the proximity between the
other noise patterns. acoustic source and the sensor position. The second parameter
It is clear that the acoustic method can easily detect partial is the time at which the transient begins. As several sensors
discharges when sources are located in the insulating oil, but are used, the arrival time to the first sensor is defined as the
when they are located in the solid insulation system, their initial time, and the signals from other sensors are correlated
detection is very problematic. Acoustic signals are attenuated with this one. This parameter is used for the localization of the
and the signals that reach the acoustic sensors do not have acoustic activity, measuring the arrival times of the acoustic
enough magnitude to be detected. In many cases only the signal to each sensor. In order to adequately digitalize these
electrical method can detect the partial discharges activity. signals, sample speeds of around 1 M samples s−1 are required.
Partial discharges, water ingress and high temperature The characteristic distinctive of the acoustic meter
generate decomposition gases that are dissolved in the proposed is to take advantage of the envelope waveform taken
insulating oil. Consequently, acoustic partial discharges from acoustic sensor signals instead of original signals. The
measurements and dissolved gas analysis are key factors for a envelope waveform is obtained by taking the absolute value
good field diagnostic for power transformer evaluation. of the original PD signals (figure 1) by a full wave rectifier,
The described partial discharge detector is based on the and subsequently, it is band limited by applying a low-pass
fact that PD acoustic emission can be registered by means of filter that reduces the high-frequency components, producing
piezoelectric sensors. Some publications [1, 2] and patents the waveform shown in figure 2.
[3] have analyzed the issue of acoustic partial discharge The envelope signal preserves the information from
detection and localization through their acoustic emission and
the original signal in terms of maximum amplitude and in
its propagation [4]. Signal processing tools are also used to
the beginning of the partial discharges transients. This
identify different sources and type of discharges [5–7] and
information is all that we need to locate the source of
their location within the power transformer [8]. Currently,
discharges.
a working group is drafting a guide for the detection and
The envelope is a slow mode signal that can be sampled
localization of partial discharges inside power transformers
at a frequency at least ten times lower than the original signal.
and reactors [9], evidencing that this technique is considered
This reduces the cost of the electronics requirements and
both useful and accurate for on-service evaluation of this
simplifies the analysis of the signals. The user does not
important equipment.
require any information related to the frequency response of
Mexican Electrical Utilities (CFE, Comisión Federal de
the sensors, but only needs the useful information.
Electricidad and LFC, Compañı́a de Luz y Fuerza del Centro)
operate the Mexican National Grid at three voltage levels, 115,
230 and 400 kV. A large number of transformers and reactors 3. Partial discharge acoustic detector
involved in this network have an operative life that exceeds
30 years. Therefore, there is a need for the implementation of The architecture of the partial discharge acoustic detector is
diagnostic tools that can be used in an extensive way, without shown in figure 3. The partial discharge acoustic detector
the disadvantage of scheduled outages or a large investment consists of a set of piezoelectric ultrasonic sensors with a
in test equipment. The main contribution of the proposed resonant frequency around 150 kHz. Those sensors have an
instrument is the use of the acoustic signal envelope for amplifier that couples the impedance to be transmitted through
further analysis contrary to commercial equipment that uses double-shielded coaxial cables to the measuring equipment.
acoustic signals, received by sensors without being processed. The measuring equipment has a signal conditioning module
Our approach offers important competitive advantages in for each sensor. A microcontroller carries out several
signal processing and in the type of electronics used in the functions such as controlling the input signal gain; the
measurement module. analog/digital conversion of each signal; measuring of arrival
times; generation of a common analog signal to fix the
2. Operation philosophy detection threshold for all channels and communication with
a PC, LAN or UAN network via Ethernet. Finally, a power
The proposed partial discharge acoustic detector differs from supply energizes the circuits and provides a phase reference
existing commercial equipment, in the fact that it has an extracted from the system voltage.
2
Meas. Sci. Technol. 20 (2009) 115108 J Ramı́rez-Niño and A Pascacio
µ µ µ µ µ µ µ µ µ µ µ µ µ µ µ µ
Figure 1. Electric signal produced by partial discharge at the acoustic sensor output.
Each signal conditioning module, as shown in figure 4, capturing wave shapes, counting events, measuring arrival
is made up of a band-pass filter centered around 150 kHz, a time and localizing the partial discharges source.
programmable gain amplifier controlled by a microcontroller, (i) Capturing wave shape mode. When the shape wave
an envelope detector and a comparator. The analog output of the acoustic signal exceeds a pre-established trigger
(AO) signal is then digitized by the microcontroller. A threshold, then the analog/digital conversion in all
comparator provides a digital output (DO) as it compares the channels starts. The acquired signal information is
analog signal with a threshold level (TI) established through displayed in a graphical way, as a function of time.
commands interpreted by the microcontroller. (ii) Counting events mode. In this mode, the equipment
The TI, which is common to four input channels, is counts the acoustic events that exceed a given trigger
compared with the signal envelope provided by the sensors, threshold for a specified period of time and restart the
and these signals’ start time counters for each acoustic channel. count in order to obtain the event trends.
The advantage provided by the envelope waveform is that there These allow the user to know whether the acoustic events
are only positive signals at the comparators inputs. are sporadic or periodic. If the repetition rate matches
120 Hz, there is a high probability that the acoustic event
4. Operation characteristics corresponds to partial discharge events. If there is a
periodicity of 60 Hz or it is sporadic, it could mean that
The partial discharge acoustic detector is operated with a the detected activity may be related to corona or other
computer and can be operated either locally or remotely with interference sources.
an Ethernet network port. The equipment can be used to assess (iii) Arrival time measurement mode. The equipment provides
transformers dielectric integrity on site or remotely supervised the arrival time of acoustic signals to each of the sensors
for on-line monitoring. in microseconds. The initial time is defined as the
The acoustic detector has four operating modes, which arrival time to the nearest sensor from a given acoustic
provide different types of information. It can be used for source. Therefore, it is possible to determine which
3
Meas. Sci. Technol. 20 (2009) 115108 J Ramı́rez-Niño and A Pascacio
µ µ µ µ µ µ µ µ µ µ µ µ µ µ µ µ
sensor receives the acoustic signal first. This mode is (iv) Partial discharge source location mode. With previously
indispensable for locating partial discharge sources by measured arrival times, the test equipment determines the
triangulation of the acoustic signals obtained from the coordinates in three dimensions from the origin of the
four sensors. acoustic activity in the equipment under evaluation.
4
Meas. Sci. Technol. 20 (2009) 115108 J Ramı́rez-Niño and A Pascacio
Signal condtioning
Ao
DO
S1 BP-Filter Gain Envelop detector Comparatpr
TI
GI
By taking the example shown in figure 6, the acoustic signal (x − xs4 )2 + (y − ys4 )2 + (z − zs4 )2 − (A + VS ∗ Tas4 )2 = 0
arrives first at sensor S3. At this time, the measurement of (4)
5
Meas. Sci. Technol. 20 (2009) 115108 J Ramı́rez-Niño and A Pascacio
6
Meas. Sci. Technol. 20 (2009) 115108 J Ramı́rez-Niño and A Pascacio
µ
Figure 11. Graphical display of the arrival times for each sensor,
Figure 9. Display of the waveform of the envelope of acoustic showing that the acoustic transient arrives first at sensor 1.
signals produced by partial discharges.
acoustic signals that are confused with partial discharge.
Figure 10 displays a screen of the software display, Therefore, this factor must be considered when the acoustic
showing two graphs. At the upper-left corner, the count of activity is measured for a long time and the equipment is
acoustic events that exceed a certain trigger level and that unattended and operating in monitoring mode.
occur in a 5 s period is shown for each sensor. The trends of Additional and useful information that the test equipment
acoustic events for a long time period (a day or a week) are also can provide is the measurement of arrival times, as shown in
shown at the lower part of the screen. With this information it figure 11. This information is mainly used to locate the partial
is possible to determine the periodicity of the acoustic activity, discharge source. In all cases, the sensor that does not show a
as well as other activity related to external events such as load time bar (arrival time equal to zero) indicates that this sensor is
tap changer operation or switching. the nearest to the disturbance source, assuming that the sound
The environment noise can produce false alarms. is propagated in a uniform medium with constant speed. This
Sometimes, sand moved by the wind or rain may produce is a close approximation of what occurs in real transformers.
Figure 10. Display of the number of acoustic events and the trend of the acoustic activity.
7
Meas. Sci. Technol. 20 (2009) 115108 J Ramı́rez-Niño and A Pascacio
Figure 12. Visual display of the triangulation process, where the localization in three dimensions of the partial discharge source and the four
acoustic sensors is shown.
The sensor with zero arrival time should be kept in the • A commercial tool kit is used to solve the equation system.
same position and the user has to move the other sensors around If there are any scaling and ill-conditioning problems
to reduce the volume of the electric equipment being explored when solving the equation system, the application
and facilitate the partial discharge source location. A good software indicates the problem and it can be easily
knowledge of the construction of the transformers is always corrected by relocating one or more sensors.
recommended to identify the affected component. Figure 12 • The acoustic signals of the four sensors must exceed the
shows the localization of the partial discharge source in three level of the pre-established threshold. This assures a
dimensions, after applying the triangulation mathematical correct value of the arrival times.
model. The arrival time values and the location coordinates of • The average speed of the sound used in the calculations
the acoustic sensors were used in this determination. must be close to the real average value, in order to assure
Valid results are obtained with the triangulation that the solutions are inside the test volume. Otherwise,
mathematical model only when the following conditions are the mathematical triangulation process may not converge
accomplished. or gives solutions outside the test volume.
• Special care should be taken when multiple partial
• A careful localization of the sensors is necessary in order discharge sources are presented because an error in
to obtain a real solution of the equation system. It was measuring arrival times can occur. Under this condition,
found that the best results are obtained when the separation the equation system is incompatible and it is not possible
between sensors is greater than 1 m, and a symmetrical to obtain a valid solution.
distribution is avoided. When the sensors are located
symmetrically, for example, all aligned in one plane, The value used for the speed of the sound is 1510 m s−1 and was
the nonlinear equation system (1)–(4) is not compatible obtained in an experimental way under controlled conditions
and causes the solution of equation (7) not to converge, at an ambient temperature of 20 ◦ C; however, variations under
because there are redundant equations. 10% of this value can be acceptable.
8
Meas. Sci. Technol. 20 (2009) 115108 J Ramı́rez-Niño and A Pascacio
Acknowledgment