IM 01E20C02-01E
12th Edition
Yokogawa Electric Corporation
CONTENTS
Contents
i IM 01E20C02-01E
CONTENTS
ii IM 01E20C02-01E
CONTENTS
REVISION RECORD
iii IM 01E20C02-01E
1. INTRODUCTION
1. INTRODUCTION
This instrument has been adjusted at the factory before • All rights are reserved. No part of this manual may
shipment. be reproduced in any form without Yokogawa's
written permission.
To ensure correct use of the instrument, please read
• Yokogawa makes no warranty of any kind with
this manual thoroughly and fully understand how to
regard to this material, including, but not limited to,
operate the instrument before operating it.
implied warranties of merchantability and suitability
for a particular purpose.
NOTE • All reasonable effort has been made to ensure the
This manual describes the hardware and soft- accuracy of the contents of this manual. However,
ware configurations of the AXFA14 converter if any errors or omissions are found, please inform
and the software configuration of the AXF Yokogawa.
integral flowmeter. • Yokogawa assumes no responsibilities for this
product except as stated in the warranty.
The contents of “basic operating procedures”, • Please note that this user's manual may not be
“parameter description”, “operation via BRAIN revised for any specification changes, construction
terminal (BT200)”, “operation via HART commu- changes or operating part changes that are not
nicator”, and “actual operation” for the AXF considered to affect function or performance.
integral flowmeter are the same as the AXFA14, • If the customer or any third party is harmed by the
see Chapter 5 to 9 in this manual. use of this product, Yokogawa assumes no responsi-
For the hardware configuration of the AXF bility for any such harm owing to any defects in the
integral flowmeter, see the user’s manual of the product which were not predictable, or for any
AXF Integral Flowmeter/Remote Flowtube indirect damages.
[Hardware Edition] (IM 01E20D01-01E).
For FOUNDATION Fieldbus protocol (Output Signal Safety and Modification Precautions
and Communication suffix code; -F), please refer • The following general safety precautions must be
to IM 01E20F02-01E. observed during all phases of operation, service, and
For PROFIBUS PA protocol (Output Signal and repair of this instrument. Failure to comply with
Communication suffix code; -G), please refer to these precautions or with specific WARNINGS
IM01E20F12-01E. given elsewhere in this manual violates safety
standards of design, manufacture, and intended use
of the instrument. Yokogawa assumes no liability for
NOTE
the customer's failure to comply with these require-
Please refer to manual IM 01E20D01-01E for ments. If this instrument is used in a manner not
information of the AXF Remote Flowtube. specified in this manual, the protection provided by
this instrument may be impaired.
• Yokogawa will not be liable for malfunctions or
NOTE damage resulting from any modification made to this
instrument by the customer.
When describing the model name like
• The following safety symbol marks are used in this
AXFC in this manual, "" means any of
user's manual and instrument.
the following.
002, 005, 010, 015, 025, 032, 040, 050, 065,
080, 100, 125, 150, 200, 250, 300, 350, 400 WARNING
1-1 IM 01E20C02-01E
1. INTRODUCTION
(2) Wiring
NOTE WARNING
A NOTE sign denotes information necessary for • The wiring of the magnetic flowmeter must be
essential understanding of operation and fea- performed by expert engineer or skilled person-
tures. nel. No operator shall be permitted to perform
procedures relating to wiring.
• When connecting the wiring, check that the
Protective grounding terminal supply voltage is within the range of the voltage
Functional grounding terminal specified for this instrument before connecting
(This terminal should not be used as a protective the power cable. In addition, check that no
grounding terminal.) voltage is applied to the power cable before
connecting the wiring.
Alternating current • The protective grounding must be connected
Direct current securely at the terminal with the mark to
avoid danger to personnel.
1-2 IM 01E20C02-01E
1. INTRODUCTION
Its probability rises in such cases as sticking For ATEX or IECEx explosion proof type, be
rain water by storm or other similar situation sure to read IM 01E20A01-11EN.
and washing up work near flowmeter installa- For TIIS explosion proof type, be sure to read
tion place. “INSTALLATION AND OPERATING PRECAU-
Either to illuminate or stop illuminating the infra- TIONS FOR TIIS FLAMEPROOF EQUIPMENT”
red switches by the flashlight may cause the at the end of this manual.
mis-reaction. • Only trained persons use this instrument in the
Refer to Chapter 6 “Menu P: Parameter Protec- industrial location.
tion Items” and section “10.2.2” how to use the • The protective grounding must be connected
write protect function in detail. to a suitable IS grounding system.
• Take care not to generate mechanical spark
when access to the instrument and peripheral
(4) Maintenance
devices in hazardous locations.
WARNING
WARNING
1-3 IM 01E20C02-01E
1. INTRODUCTION
1-4 IM 01E20C02-01E
2. HANDLING PRECAUTIONS
2. HANDLING PRECAUTIONS
This instrument has been inspected carefully at the
factory before shipment. When the instrument is
2.2 Accessories
delivered, visually check that no damage has occurred Check that the parts shown below are included in the
during transportation. package:
Read this section carefully as it contains important Mounting hardware: 1 set
information on handling this instrument. Refer to the Hexagonal wrench: 1 piece (nominal size 3 mm)
relevant sections for information not contained in this
section. If you have any problems or questions, please
contact Yokogawa sales office. 2.3 Storage Precautions
If the instrument is to be stored for a long period of
2.1 Checking Model and time after delivery, observe the following points.
Specifications The instrument should be stored in its original
packing condition in the storage location.
The model code and specifications are found on the
Select a storage location that fulfils the following
name plate located on the outside of the case. Check
conditions:
that the model code and specifications match what you
• A place where it will not be exposed to rain or
have ordered.
water
Be sure you have your model number and serial • A place subject to minimal vibrations or shocks
number available when contacting Yokogawa. • Temperature and humidity levels should be as
follows:
Temperature: -30 to 70°C
Humidity: 5 to 80% RH (no condensation)
The preferred ambient temperature and
humidity levels are 25°C and approximately
65% RH.
If the AXFA14 converter is transferred to the
installation site and stored without being installed,
its performance may be impaired due to the infiltra-
tion of rainwater and so forth. Be sure to install and
wire the AXFA14 as soon as possible after transfer-
ring it to the installation location.
F0201.EPS
2-1 IM 01E20C02-01E
2. HANDLING PRECAUTIONS
2-2 IM 01E20C02-01E
3. INSTALLATION
3. INSTALLATION
1. Fix the instrument on the mounting fixture using
WARNING
four screws.
Installation of the magnetic flowmeter must be 2. Fix the mounting fixture with the instrument
performed by expert engineer or skilled person- installed on a 2-inch pipe using a U-bolt.
nel. No operator shall be permitted to perform
procedures relating to installation.
Horizontal Mounting
IMPORTANT
Mounting fixture
Nut
3-1 IM 01E20C02-01E
4. WIRING
4. WIRING
This chapter describes the wiring on the converter side • Ground the remote flowtube and the converter
only. For information relating to wiring on the separately.
flowtube side, refer to the user’s manual of the AXF • Cover each shield of the signal cable with vinyl
Remote Flowtube (IM 01E20D01-01E). tube or vinyl tape to avoid contact between two
shields or between a shield and a case.
WARNING • When waterproof glands or union equipped
waterproof glands are used, avoid tightening
The wiring of the magnetic flowmeter must be the glands with an excessive torque.
performed by expert engineer or skilled person- • When the power supply voltage is 24V, it
nel. No operator shall be permitted to perform comes with a blanking plug. Use this plug to
procedures relating to wiring. cover the unused wiring port when wiring the
instrument with only one, four-core cable.
• Be sure to turn power off before opening the
CAUTION cover.
• Before turning the power on, tighten the cover
Once all wiring is complete, check the connec- securely.
tions before applying power to the instrument. • The terminal box cover is locked by the special
Improper arrangements or wiring may cause a screw. In case of opening the terminal box
unit malfunction or damage. cover, use the hexagonal wrench attached. For
handling the locking screw, refer to Figure
4.4.1.
• Be sure to lock the cover by the special screw
4.1 Wiring Precautions using the hexagonal wrench attached after
installing the cover. For handling the locking
Be sure to observe the following precautions when
screw, refer to Figure 4.4.12.
wiring:
• Explosion protected types must be wired in
accordance with specific requirement (and, in
CAUTION certain countries, legal regulations) in order to
preserve the effectiveness of their explosion
• In cases where the ambient temperature
protected features.
exceeds 50°C (122°F), use external heat-
resistant wiring with a maximum allowable
temperature of 70°C (158°F) or above.
IMPORTANT
• Do not connect cables outdoors in wet weather
in order to prevent damage from condensation Prepare the signal cable and the excitation cable
and to protect the insulation. almost the same length. It is recommended to
• Do not splice the cable between the flowtube lay them together closely.
terminal and the converter if it is too short.
Replace the short cable with a cable that is the
appropriate length.
• All the cable ends must be provided with round
crimp-on terminals and be securely wired.
• The signal cables must be routed in separate
steel conduit tubes 16 (JIS C 8305) or flexible
conduit tubes 15 (JIS C 8309).
• Always route the power and output signal
cables in separate steel conduit tubes, except
when the power supply voltage is 24 V and
four-core cables are used for wiring. Keep
conduits or flexible tubes watertight using
sealing tape.
4-1 IM 01E20C02-01E
4. WIRING
(1) Dedicated Signal Cable (AXFC) • As crimp terminals A, B, SA, SB and C have
Conductors (A and B)
their own electrical potentials, securely insulate
Shields (SA and SB) them so as not to come in contact with one
Tape another.
• To prevent a shield from coming in contact with
Outer jacket 10.5 (0.413") another shield or the case, cover each shield
with a vinyl tube or wrap it in vinyl tape.
Shield (C)
Insulation
Insulation
F0401.EPS
NOTE
Figure 4.2.1 Dedicated Signal Cable AXFC
Conductors A and B carry the signal from the
The flow signal is transmitted via this dedicated cable. electrodes, and C is at the potential of the liquid
The cable is constructed with double shielding over the (signal common). Shields SA and SB are kept
two conductors, and heat-resistant vinyl is used for the at the same potentials as the individual elec-
outer jacket material. trodes (these are actively driven shields.) This is
Finished diameter: 10.5 mm (0.413") done to reduce the effect of the distributed
Maximum length: 100 m (330 ft) capacitance of the cable at long cable length.
Maximum temperature: 80°C (176°F) Note that, since the signals from the individual
electrodes are impedance converted inside the
IMPORTANT converter, errors will result if they come in
contact with any other component. Great care
If the cable is longer than required, cut off any must be taken in the cable end treatment.
extra length rather than coiling it up, and termi-
nate the conductors as shown in Figure 4.2.2.
(2) Excitation Cable/Power Cable/Output
Avoid using junction terminal boards to extend Cable
the cable length, as this will interrupt the shield-
JIS C3401 control cable equivalent
ing.
JIS C3312 power cable equivalent
14 AWG Belden 8720 equivalent
B
A
SB
90 (3.54)
90 (3.54)
C
150±5
(5.9)
(5.9)
On the On the
converter flowtube
side side In case of power cable, Green/Yellow covered conduc-
tor shall be used only for connection to PROTECTIVE
10.5 (0.4)
L (Specified Dimensions)
CONDUCTOR TERMINALS. Conform to IEC227,
20 (0.8)
IEC245 or equivalent national authorization.
AXFC
F0402.EPS
4-2 IM 01E20C02-01E
4. WIRING
Unit : mm
(approx. inch) 4.3 Wiring Ports
Crimp Terminal
This instrument is of watertight construction as
stipulated in JIS C0920. It is shipped with a wiring
bracket (waterproof gland or waterproof gland with
EX1
EX2
EX2
EX1
F0403.EPS
(1) When waterproof property is unnecessary
Figure 4.2.3 End Treatment of Excitation Cable (When there are no particular optional
specifications)
The wiring port is sealed with a cap (not water-proof)
NOTE
that must be removed before wiring. At this time,
• For excitation and power cables, always use a handle the wiring port in accordance with the JIS
crimp terminal with an insulation cover. C0920 mentioned above. Do not remove the cap from
• Use crimp tools from the manufacturer of the the unused wiring port.
crimp terminal you want to use to connect the
crimp terminal and cable.
(2) When waterproof property is necessary
• Use crimp tools that are appropriate for the (Wiring using waterproof glands)
diameter of the cable to be connected.
IMPORTANT
4-3 IM 01E20C02-01E
4. WIRING
For working on the electric wire tubes or the flexible (3) Conduit Wiring
tubes (G1/2), remove the waterproof gland and attach When wiring the conduits, pass the conduit through the
them directly to the wiring port. wiring connection port, and utilize the waterproof
gland to prevent water from flowing in. Place the
conduit pipe on an angle as shown in Figure 4.3.4.
Install a drain valve at the low end of the vertical pipe,
and open the valve regularly.
Washer
Gasket
Waterproof gland
Cable
F0404.EPS
F0407.EPS
Gasket
G1/2
4.4 Wiring Connections
Washer
Tightening gland
4.4.1 Removing Cover
Cable Loosen cover locking screw 2 clockwise using a
hexagonal wrench (nominal size 3 mm) to unlock the
When working on conduit pipes or
flexible pipes (G1/2 only) cover. (Upon shipment from the manufacturing plant,
F0405.EPS
the cover is unlocked.) Hold the flowmeter with your
Figure 4.3.2 Waterproof Gland with Union Joint hand and remove the cover by turning it in the direc-
(Optional code EU)
tion of the arrow as shown below.
Gasket
Plastic gland
F0406.EPS
F0408.EPS
4-4 IM 01E20C02-01E
4. WIRING
WARNING
4-5 IM 01E20C02-01E
4. WIRING
wires.
796 (2610)
600 (1970)
446 (1460)
200 ( 660)
0
20.4 22 24 26 28.8
Usable range E (V)
Cable cross section area: 1.25 mm2
Cable cross section area: 2 mm2
F0411.EPS
Set the local Commercial power frequency in Figure 4.4.4 Protective Grounding Terminal Location
4-6 IM 01E20C02-01E
4. WIRING
B EX2 SB Taping*
(1) Connection with the Remote Flowtube C C
EX1 EX1
(General-Purpose Use, Submersible Type, EX2 EX2
EX1
Sanitary Type) C * Individually tape and insulate the
Remote flowtube shields corresponding to SA and
Connect wiring as shown in the figure below. SB on the remote flowtube side.
F0414.EPS
In case of the explosion proof type, the protective Resistive Load Max. 750 Ω.
Communication Resistive load
grounding of remote flowtube must be connected to BRAIN 250 to 450 Ω
HART 250 to 600 Ω
a suitable IS grounding system. In that case,
F0415.EPS
(functional grounding terminal) need not be connected. Figure 4.4.7 4 to 20 mA DC Output Connection
4-7 IM 01E20C02-01E
4. WIRING
Pulse Output
AXFA14 Protective diode
DO+
Mechanical Counter
IMPORTANT PULSE OUT DO-
NOTE
NOTE
For pulse output from the DO terminals, param-
eters must be set. Refer to “Chapter 6: Param- For status input to the DIO terminals, parameters
eter Description” in this manual. must be set. Refer to “Chapter 6: Parameter
Description” in this manual.
Protective diode
AXFA14 DO+
Mechanical Counter
Status Output / Alarm Output
PULSE OUT
DO-
AXFA14 IMPORTANT
DO+
PULSE OUT Load Electronic Counter Since this is an isolated transistor output, be
DO-
careful of voltage and polarity when wiring. Do
30V DC, 0.2A. max
not apply a voltage larger than 30V DC or a
F0416.EPS
current larger than 0.2A in order to prevent
Figure 4.4.8 Pulse Output Connection damage to the instrument.
4-8 IM 01E20C02-01E
4. WIRING
Load
DO- (or DIO-)
F0419.EPS
NOTE
Cover locking
screws
F0420.EPS
4-9 IM 01E20C02-01E
5. BASIC OPERATING PROCEDURES
WARNING
Be sure to set parameters as “Protect” on the write protect function after finish of
parameter setting work.
Under extremely rare case, the infra-red switches may respond unexpectedly in
such conditions as sticking ball of water or extraneous substances on the surface
of display panel glass according to the principle of infra-red switch operation.
Its probability rises in such cases as sticking rain water by storm or other similar
situation and washing up work near flowmeter installation place.
Either to illuminate or stop illuminating the infra-red switches by the flashlight may
cause the mis-reaction.
Refer to Chapter 6 “Menu P: Parameter Protection Items” and section “10.2.2”
how to use the write protect function in detail.
IMPORTANT
Operate the display unit under the condition where direct sunlight, etc... do not
shine to the setting switches directly when the parameter setting operation is
carried out.
NOTE
(1) Always use the setting switches with the cover of the AXFA14 or the AXF
integral flowmeter closed.
(2) Use these switches with them covered by the glass window.
(3) If dirt, dust or other substances surfaces on the display panel glass, wipe
them clean with a soft dry cloth.
(4) The operation with dirty gloves may cause a switch response error.
5-1 IM 01E20C02-01E
5. BASIC OPERATING PROCEDURES
Instantaneous flow rate: % FR Displays the instantaneous flow rate for the span as a percentage.
Actual instantaneous flow rate FR Displays the actual reading for instantaneous flow rate.
Instantaneous flow rate: mA FR Displays the instantaneous flow rate for the span as a current output value.
Bar graph indicating None Displays the instantaneous flow rate for the span as a percentage
instantaneous flow rate using bar graph.
Totalized forward-direction flow rate FTL Displays the totalized value for flow rate in the forward direction.
Totalized reverse-direction flow rate RTL Displays the totalized value for flow rate in the reverse direction.
Totalized differential flow rate DTL Displays the differential totalized value for flow rate between
forward totalization and reverse totalization.
Tag number TAG Display the tag number (using up to 16 characters).
Diagnosis of electrode adhesion ADH Displays the adhesion condition in the form of a bar graph.
(See the description for parameters K10 through K15 from
Chapter 6: Parameter Description for more details.)
Communication type COM Displays the communication type.
T0501.EPS
(4)
5-2 IM 01E20C02-01E
5. BASIC OPERATING PROCEDURES
Before changing any settings, be sure to check the corresponding setting details
in Chapter 6: Parameter Description.
+ +
Select “No”
Setting modes
* The term "mode" is used to refer to a situation
where display and setting are possible.
+
Press the SET switch while holding down the SHIFT switch. F0502.EPS
Sample Display: Procedure for moving from Display Mode to Setting Mode
1st line: Actual instantaneous flow rate [FR]
Start:
Display Mode 2nd line: Bar graph indicating instantaneous flow
FR rate
100.000 m3/h
0 100 3rd line: Totalized forward flow rate [FTL]
3274m3 FTL
Setting switches
Hold the switch for 2 seconds.
(*1)
Entry Mode NOTE
Touch SHIFT + key When other operations are carried out, the
system will automatically return to the Display
Mode.
When no operations in this display are carried
out for 20 seconds, the system will automati-
cally return to the Display Mode.
(*1)
NOTE
F0503-1.EPS The Major Item Parameter which is set just
before will be shown when entrying the Setting
Mode again within 1 minute after returning
from Setting Mode to Display Mode.
5-3 IM 01E20C02-01E
5. BASIC OPERATING PROCEDURES
No NOTE
Yes
When the operations except and
switches are carried out, the system will
automatically return to the Display Mode.
When no operations in this display are carried
out for 20 seconds, the system will automati-
cally return to the Display Mode.
NOTE
F0503-2.EPS
5-4 IM 01E20C02-01E
5. BASIC OPERATING PROCEDURES
NOTE
If no operations are carried out for a period of 10 minutes in Setting Mode, the
system will automatically return to the Display Mode.
(i) Selection-type B21:Base Flow Unit The desired data item is selected from a predefined list.
m3
m3
kl(Kiloliter)
(ii) Numeric-type B23:Flow Span Data is set using the values in each digit and using
100 l/min the decimal point.
000100 l/min
Rng:0.00001 32000
Regarding the alphanumeric-type format (iii), the following alphanumerics are displayed in the following sequence:
NOTE
5-5 IM 01E20C02-01E
5. BASIC OPERATING PROCEDURES
Major item B:Easy Setup The cursor has been moved to B21: Base Flow
20:Flow Damping Unit in this screen. (Sub-item selection screen (A))
Sub-item 21:Base Flow Unit
selection (A) 22:Base Time Unit
Sub-item B21:Base Flow Unit In this screen, Parameter Replacement Mode has
Parameter Current unit setting m3
Replacement Mode m3 been called up using the switch.
Available selections kl(Kiloliter)
Sub-item B21:Base Flow Unit Touch the switch to move the cursor to the
Current unit setting m3
l(Liter)
Available selections cm3
unit item for selection. In this example, the
switch is touched twice to select l (Liter)
X2
NOTE
Sub-item Major item B:Easy Setup The system automatically returns to sub-item
Parameter 20:Flow Damping
Sub-item selection screen (A).
21:Base Flow Unit
Search Mode selection (A) 22:Base Time Unit
F0504-2.EPS
5-6 IM 01E20C02-01E
5. BASIC OPERATING PROCEDURES
Sub-item Major item B:Easy Setup Sub-Item Parameter Search Mode has been accessed
50:Auto Zero Exe
Parameter Sub-item 10:Language in this screen.
Search Mode parameter 20:Flow Damping
X4
Touch the switch to move the cursor to
B23: Flow Span.
Major item B:Easy Setup The cursor has been moved to B23: Flow Span in
22:Base Time Unit this screen. (Sub-item selection screen (B))
Sub-item 23:Flow Span
selection (B) 24:Flow Decimal Pnt
NOTE
NOTE
Sub-item Major item B:Easy Setup The system automatically returns to sub-item
Parameter 22:Base Time Unit
Sub-item 23:Flow Span
selection screen (B).
Search Mode selection (B) 24:Flow Decimal Pnt
NOTE
B23:Flow Span
100 l/min If the input value is outside the valid selection
Incorrect setting: 1200000 l/min
Rng:0.00001 32000 range, the message “Out of range. Touch any
Out of range.
key.” will be displayed. In such a case, touch
Touch any key. any switch to return to Parameter Replacement
Mode and redo the setting.
5-8 IM 01E20C02-01E
5. BASIC OPERATING PROCEDURES
C10:Tag No The cursor will flash on and off on the left of the tag
Parameter Current setting value Fl-1101
Replacement Mode Modified value
number. As “FI-1201” is to be setup in this example,
l-1101
touch the switch to move the cursor to the
X4 position for multiples of 100.
NOTE
Sub-item Major item C:Basic Setup The system automatically returns to sub-item
Parameter 49:Flow User Span selection screen (C).
Sub-item 10:Tag No
Search Mode selection (C) 11:Flow Damping
5-9 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6. PARAMETER DESCRIPTION
6.1 Parameters NOTE
With the exception of parameters that were specified In order to ensure that correct flow rate data can
by the customer upon ordering, all of the internal be acquired, it is crucial that the nominal size,
parameters will initially be set to default values. flow rate span, and meter factor of the combined
Actions such as the modification of display details can remote flowtube are set. In cases where a
then be carried out whenever necessary. remote flowtube is ordered at the same time as
the AXFA14, or where the AXF integral flowme-
For FOUNDATION Fieldbus protocol, please refer to IM
ter is ordered, the nominal size and meter factor
01E20F02-01E.
will be set upon shipment from the manufactur-
For PROFIBUS PA protocol, please refer to IM ing plant, and these will not require additional
01E20F12-01E. setting. If the AXFA14 is ordered separately, the
default value will be set for the meter factor;
accordingly, it will be necessary to change this
IMPORTANT setting to the meter factor indicated on your
remote flowtube name plate.
Make sure to keep the instrument’s power on at
If a flow rate span was specified upon ordering,
least for 30 seconds after you set the param-
this will be set before shipment. If this is not the
eters. If you turn the power off immediately after
case, however, it will be necessary for the
the parameters are set, the settings will be
appropriate value to be set by the user.
canceled.
R: Read only
W: Writable
Parameter number.
T0601.EPS
6-1 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-2 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-3 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-4 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-5 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-6 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-7 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-8 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-9 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-10 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-11 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6.4 Parameter Description [B22: Base Time Unit] Selection of time units for
the flow rate span
(1) Menu B: Easy Setup items → This setting is linked with that of parameter C41.
This parameter selects the time units for the flow rate
Those parameters with a high frequency of use have
span; however, if “m” has been selected for the flow
been grouped together in Easy Setup. All basic
rate units, “/s” is automatically set for this parameter.
functions can be controlled using only the parameters
from this block. Parameters from Menu B share
identical names with those from other menus; however, [B23: Flow Span] Setting of the flow rate span
modification of one such parameter will result in the → This setting is linked with that of parameter C42.
other being automatically modified. The span can be set for the forward flow rate in the
range 0 to 32,000 (although this does not include 0). The
units set using B21/C40: Base Flow Unit and B22/
[B10: Language] Selection of language used for the C41: Base Time Unit will be displayed at this time.
display unit
→ This setting is linked with that of parameter H30. NOTE
One of the following languages can be selected for the
If the flow rate units, time units, and flow rate
display unit.
span are specified upon ordering, these param-
eters will be setup before shipment; however, if
Data Range
this is not the case, it will be necessary for the
Setting item Description appropriate values to be set up by the user.
English All parameters, alarm messages, etc. displayed in
English.
Japanese All parameters, alarm messages, etc. displayed in NOTE
Japanese katakana.
French All parameters, alarm messages, etc. displayed in Flow rate span is the value for instantaneous
French. flow rate that corresponds to a current output of
German All parameters, alarm messages, etc. displayed in 20 mA. The following factors should be taken
German.
into consideration when deciding on the flow rate
Italian All parameters, alarm messages, etc. displayed in
Italian. span.
Spanish All parameters, alarm messages, etc. displayed in • In the case of applications with large variations
Spanish. in flow rate, the maximum flow rate should be
T0614.EPS
set. If a flow rate in excess of the flow rate
span was to occur, output would be possible
[B20: Flow Damping] Setting of the damping time up to an upper limit of 108%, and beyond this,
constant error would occur. Note that the same applies
→ This setting is linked with that of parameter C11. to pulse output and totalization.
The damping time constant should be modified to • In the case of applications that have a rela-
suppress an output fluctuation or to change the re- tively stable flow rate, a flow rate span of 1.5 to
sponse time. This time constant has an effect on analog 2.0 times larger than the normal flow rate may
output and on the flow rate display (i.e., actual instan- be considered suitable.
taneous flow rate, %, current value), and in addition, it • The flow rate to be adopted should - upon
also affects pulse output and totalization. However, conversion to flow velocity - correspond to a
when “No Damping” has been set for J24: T/P Damp value within the range of 0.1 to 10 m/s. The
Select, there will be no effect on pulse output or flow velocity can be confirmed using sizing data
totalization. or with parameter C44: Velocity Check, and in
* Time constant: The time required for the output to the latter case, the value obtained when span is
reach 63.2% from 0%. converted to flow velocity will be displayed.
• Regardless of the position of the decimal point,
the largest value that can be set on the display
[B21: Base Flow Unit] Selection of flow units for the
unit is 32,000. Furthermore, it is not possible to
flow rate span
set a number of 4 or greater for the highest-
→ This setting is linked with that of parameter C40.
order digit. Similarly, if 3 is set for this highest-
This parameter selects the flow units for the flow rate
order digit, it will not be possible to set a
span. (In case of mass flow, the setting of density is
also required. Refer to C46: Mass Flow Density
for more details.)
6-12 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-13 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
B33/E11.
[B33: Pulse Scale] Setting of pulse scale
→ This setting is linked with that of parameter E11.
[B40: Display Select1] Setting of the first line for
Pulse output is performed in individual counts in
display unit
accordance with this parameter’s setting. If 0 is
→ This setting is linked with that of parameter H10.
selected, it indicates that the pulse output function is
This parameter selects the display content of the first
not to be used.
line for display unit. The size of the characters which
are displayed will depend on the selections made for
6-14 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
B41/H11: Display Select2 and B42/H12: Display remote flowtube is ordered at the same time as
Select3 as described below. (For more details, refer to the AXFA14, or where the AXF integral flowme-
Chapter 5: Basic Operating Procedures.) ter is ordered, the nominal size and meter factor
will be set upon shipment from the manufactur-
ing plant, and these will not require additional
CAUTION
setting. If the AXFA14 is ordered separately, the
It is not possible to set Display Select1 to “Off”. default value will be set for the meter factor;
accordingly, it will be necessary to set the meter
factor indicated on your remote flowtube name
[B41: Display Select2] Setting of the second line plate.
for display unit If a flow rate span was specified upon ordering,
→ This setting is linked with that of parameter H11. this will be set before shipment. If this is not the
This parameter selects the display content of the case, however, it will be necessary for the
second line for display unit. When “Off” is selected, appropriate value to be set by the user.
one-line display will be adopted regardless of the
setting made for B42/H12: Display Select 3.
[C10: Tag No] Setting of the tag number
[B42: Display Select3] Setting of the third line for → The setting for this parameter corresponds to one of
display unit the ordered items.
→ This setting is linked with that of parameter H12. Up to a maximum of 16 characters can be entered for
This parameter selects the display content of the third the display unit. For more details regarding the actual
line for display unit. When “Off” is selected for this characters that can be used, refer to Section 5.2.2:
parameter, two-line display is adopted. Setting Mode.
6-15 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
(1) Confirm that the serial number indicated by [C42: Flow Span] Setting of the flow rate span
COMB. NO. on the AXFA14 converter’s → Refer to the description of parameter B23.
name plate corresponds with the AXF remote
flowtube’s serial number. [C43: Flow Decimal Pnt] Setting of the decimal
(2) Set the values that are marked in the point position for the instantaneous flow rate
METER FACTOR fields on the name plate → Refer to the description of parameter B24.
for the Remote Flowtube.
(3) The meter factors are crucial in ensuring that
the electromotive force is correctly in propor- [C44: Velocity Check] Display of the flow rate span
tion to the flow velocity and are determined velocity
at the manufacturing plant by actual-flow This parameter displays the flow rate span for the
calibration. maximum range in m/s units.
6-16 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
[C45: Density Unit] Setting of the density units for (3) Menu D: Total Setting items
mass flow rate Menu D contains parameters that are relevant to
This parameter selects the units for density as required totalization function settings.
when making settings using C46: Mass Density.
[C46: Mass Density] Setting of the density for mass [D10: Total Unit] Setting of units for totalization
flow rate scale
This parameter is necessary in situations where t, kg, g, → Refer to the description of parameter B30.
klb or lb has been selected as the mass unit in B21/
C40: Base Flow Unit. If a mass unit is selected in [D11: Total Scale] Setting of the totalization scale
B21/C40: Base Flow Unit and a value of 0 is set for → Refer to the description of parameter B31.
this parameter, the setting alarm “57: Dens Set Err”
will be displayed. In such a case, ensure that the
density is set correctly. [D12: Total Decimal Pnt] Setting of the decimal
point position for the totalization display
[C47: User Span Select] Selection of the use of This parameter sets the position of the decimal point
special flow rate units for totalization display in terms of the number of digits.
This parameter selects whether or not special units are Except in cases where 0 is selected, the totalized units
used for instantaneous flow rate. Actual setting of these are not displayed.
units is carried out using C48: Flow User Unit and
C49: Flow User Span. Example: When totalized value is 12345678 m3
[C48: Flow User Unit] Setting of the special flow Item Totalization display
rate units 0 12345678 m3
This parameter is used to select the special units (up to 1 1234567.8
maximum 8 characters in length). These units are 2 123456.78
displayed when instantaneous flow rate is selected in 3 12345.678
the Display Mode, and they are displayed for A20: 4 1234.5678
FLOW RATE when BRAIN communication is being
5 123.45678
carried out.
6 12.345678
7 1.2345678
[C49: Flow User Span] Setting of the special flow
T0619.EPS
rate span
This parameter sets the special span to be displayed for
100% output in the maximum range. [D13: Total Low Cut] Setting of the totalization stop
range
This parameter allows the settings to be made that
NOTE
prevent totalization when the flow rate is at or below
Example : To set the special flow rate span to the low-cut setting value. In cases where there are
100 dl/s multiple ranges or forward/reverse ranges, low cut is
Since 100 dl (deci-liter)=10 l (liter), carried out at the setting value for the smallest span
“l (Liter)” is set for B21/C40: Base (i.e., an integer between 0 and 10%).
Flow Unit, Example: When the first range = 10 m3/h, the second
“/s” is set for B22/C41: Base Time range = 100 m3/h, and the Total Low Cut =
Unit, 3%, no totalization is carried out at flow
“10” is set for B23/C42: Flow rates of 0.3 m3/h or lower.
Span,
“Yes” is set for C47: User Span
Select,
“dl/s” is set for C48: Flow User
Unit,
“100” is set for C49: Flow User
Span.
“100 dl/s” is indicated for 100%
output in the Display Mode.
6-17 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
function for the forward totalized value and the reverse F0602.EPS
totalized value.
*: The preset function is to set a preset value to [D23: Ttl Switch Lower] Setting of the totalization
totalization and is used to start the count for totaliza- switch value (lower 6 digits)
tion from the set value. The totalization switch function operates to set the
The preset value is determined using D21: Ttl Set status output terminal (i.e., DO or DIO) to “Closed
Val Lower and D22: Ttl Set Val Upper. Setting of (On)” when the forward internal totalized value reaches
zero as the preset value allows the zero-reset function or exceeds the totalization switch value. (For details
to be implemented. After presetting, this parameter regarding the setting method for the status output, refer
goes back to its previous status (“Start” or “Stop”). In to the descriptions of parameters F20 and F21.)
case that “Start” has been selected, the count for
totalization starts from the preset value. If this function is set up, the totalization count will stop
at 99999999.
Item Description D23 sets the lower 6 digits of the 8-digit totalization
Start (initial value) Starts totalization switch value.
Stop Stop totalization
Preset Total Sets the preset value for totalization display that [D24: Ttl Switch Upper] Setting of the totalization
has been specified as the forward totalized value. switch value (upper 2 digits)
This parameter sets the upper 2 digits of the 8-digit
Preset Rev Total Sets the preset value for totalization display that
totalization switch value.
has been specified as the reverse totalized value.
T0620.EPS
[D30: Ttl User Select] Selection of the use of
special totalization unit
NOTE
This parameter specifies whether or not special units
Totalization presets can also be set up by using are used for totalization unit. Actual setting of these
status input. For details regarding the setting units is carried out using D31: Ttl User Unit.
method, refer to the descriptions of F21.
[D31: Ttl User Unit] Setting of special totalization
units
IMPORTANT Units of up to maximum 8 characters in length can be
specified using this parameter. The units set with this
When performing the preset function for the parameter are displayed whenever totalization (i.e.,
forward totalized value or the reverse totalized FTL, RTL, DTL) is selected in the Display Mode, and
value, release the “0% Signal Lock” and return they are displayed for A30: TOTAL, A31: REV
to “Normal” in Test Mode. For “0% Signal Lock”, TOTAL, and A32: DIF TOTAL when BRAIN
refer to F21: DIO Function. For “Test Mode”, communication is being carried out.
refer to H10: Test Mode.
6-18 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
Data Range
NOTE
Pulse Rate (pps)
Example: To count in 1 dl (deci-liter) steps Setting
Maximum Value Minimum Value
with flow rate span=10 l/s. (0) 50% Duty 11000 0.0001
Since 1 dl (deci-liter) = 0.1 l (liter),
(1) 0.05ms 10000 (pps: pulses per second)
“l (Liter)” is set for B21/C40: Base
(2) 0.1ms 5000
Flow Unit,
(3) 0.5ms 1000
“/s” is set for B22/C41: Base Time
(4) 1ms 500
Unit,
“10” is set for B23/C42: Flow Span, (5) 20ms 25
“Unit/P” is set for B30/D10: Total (6) 33ms 15
Unit, (7) 50ms 10
“0.1” is set for B31/D11: Total (8) 100ms 5
Scale, T0621.EPS
Closed (On)
(4) Menu E: Pulse Setting items Open (Off)
Menu E contains items relevant to pulse output.
Pulse width F0603.EPS
6-19 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
[F20: DO Function] Setting of the function for the DO status output terminal
This parameter sets the function for the DO (status output) terminal.
Setting Function Description
No Function Stops output (i.e., inactive condition) As no function is set, there is no output.
Pulse Output Pulse output Pulse output is carried out.
Alarm Output Output upon alarm
Refer to Alarms (Section 6.5).
Warning Output Output upon warning
Status output is carried out when the forward internal
totalized value reaches or exceeds the totalization switch value.
Total Switch(O) Totalization switch output
The totalization switch value is determined using D23: Ttl
Switch Lower and D24: Ttl Switch Upper.
Status output is carried out when the instantaneous flow rate
equals or falls below the low flow rate limit (L), or when it equals
H/L Alarm(O) H/L alarm output
or exceeds the high flow rate limit (H). These limit values are
determined using G10: Low Alarm and G11: High Alarm.
Status output is carried out when the instantaneous flow rate equals
or falls below the low-low flow rate limit (LL), or when it equals or
exceeds the high-high flow rate limit (HH). These limit values are
HH/LL Alarm(O) HH/LL alarm output
determined using G12: Low Low Alarm and G13: High High
Alarm.To output “HH/LL Alarm” as an alarm, set G33: Alm-
HH/LL to “Yes.”
When flow is in the reverse direction, switching to the reverse
Fwd/Rev Rngs(O) Forward/reverse flow rate measurement range is carried out automatically, measurement is performed,
and status output is carried out.
Auto 2 Rngs(O) Automatic 2 ranges switching This function ensures that when the instantaneous flow
rate exceeds 100% of the range, transition to the next
Auto 3 Rngs(O) Automatic 3 ranges switching (Note 1)
range is carried out automatically. Status output is carried
Auto 4 Rngs(O) Automatic 4 ranges switching (Note 1) out upon range switching.
When range switching is carried out in response to external
Answerback: 2 ranges switching via
Ext 2 Answer(O) status input, status output is performed in the form of an
external status input
answerback to indicate the range currently being used.
Note 1: When these functions are selected, two terminals become necessary for status output, the DO and DIO
terminals which cannot be used for other functions. Accordingly, the setting for F20: DO Function is
automatically adopted as the setting for F21: DIO Function. (Setting of these two functions is not possible
using F21: DIO Function.)
T0622.EPS
6-20 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
[F21: DIO Function] Setting of the function for the DIO status input/output terminal
This parameter sets the function for the DIO (status input/output) terminal.
Ext Ttl Set(I) Forward totalization preset via The totalization display value is preset or reset to zero in
external status input accordance with the external status input. The preset value is
determined using D21: Ttl Set Val Lower and D22: Ttl Set
Val Upper.
Reverse totalization preset via In case that “Start” is selected for D20: Total Execution, the
Ext R Ttl Set(I)
external status input count for totalization starts from the preset value.
Ext 2 Ranges(I) 2 ranges switching via external status This function allows the switching of 2 ranges in response
input to status input for a single direction only.
Note 1: When these functions are selected, two terminals become necessary for status output, the DO and DIO
terminals which cannot be used for other functions.
T0623.EPS
6-21 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
[F22: DO Active Mode] Setting of the active mode Example 1: When the “Pulse Output” function is
for DO terminal selected for the DO terminal and the E12:
Pulse Width is “1 ms”, the following
Operations are performed in accordance with the
signals are output from the terminal.
following table when the active mode has been set to
“Closed (On) Act” using this parameter. Operating Closed (On)
patterns are reversed when the active mode has been
Open (Off)
set to “Open (Off) Act.”
1 ms 1 ms
Condition of DO terminal
Selected function Closed (On) Active Open (Off) Active
Open (Off) Closed (On)
F0604-1.EPS
Pulse Output Open (Off) when Closed (On) when
(see Example 1) pulses are output. pulses are output.
Example 2: When the “Alarm Output” function is
Alarm Output
Good (normal) Alarm status selected for the DO or DIO (O) terminal,
(see Example 2)
Warning Output Good (normal) Warning status the following signals are output from the
Total Switch(O)
Below setting value
Equal or above terminal.
(see Example 3) setting value
H/L Alarm(O) Normal H/L alarm status Closed (On)
HH/LL Alarm(O) Normal HH/LL alarm status Open (Off)
Fwd/Rev Rngs(O) Forward direction Reverse direction
Note: For “Auto 2 Rngs(O),” “Auto 3 Rngs(O)”, “Auto 4 Rngs(O)”, and “Ext Alarm occurs Alarm occurs
2 Answer(O)”, see the Multiple ranges setting section.
T0624.EPS
Closed (On) Active Open (Off) Active
F0604-2.EPS
[F23: DIO Active Mode] Setting of the active mode Example 3: When the “Total Switch (O)” function is
for DIO terminal selected for the DO or DIO (O) terminal,
the following signals are output from the
Operations are performed in accordance with the
terminal.
following table when the active mode has been set to
“Closed/Short Act” using this parameter. Operating Closed (On)
patterns are reversed when the active mode has been Open (Off)
set to “Open/Open Act.”
Equal or above setting value Equal or above setting value
Condition of DIO (O) terminal
Selected function Closed (On) Active Open (Off) Active
Open (Off) Closed (On) F0604-3.EPS
Alarm Output
Good (normal) Alarm status
(see Example 2) Example 4: When the “0% Signal Lock (I)” function is
Warning Output Good (normal) Warning status selected for the DIO (I) terminal, the
Total Switch(O) Equal or above following signals are input to the terminal.
(see Example 3) Below setting value
setting value
H/L Alarm(O) Normal H/L alarm status Short
HH/LL Alarm(O) Normal HH/LL alarm status
Open
Fwd/Rev Rngs(O) Forward direction Reverse direction
Note: For “Auto 2 Rngs(O),” “Auto 3 Rngs(O)”, “Auto 4 Rngs(O)”, and “Ext Signal lock status Signal lock status
2 Answer(O)”, see the Multiple ranges setting section.
T0625.EPS Short Active Open Active
F0604-4.EPS
Condition of DIO (I) terminal
Selected function
Open Short
0% Signal Lock (I)
Normal Signal locked status
(see Example 4)
Ext Auto Zero (I) Normal Start of automatic zero adjustment
Ext Ttl Set (I) Normal Forward totalization preset
Ext R Ttl Set (I) Normal Reverse totalization preset
Note: For “Ext 2 Ranges(I),” see the Multiple ranges setting section.
*: “DIO (O)” indicates DIO function is used for output. “DIO (I)”
indicates DIO function is used for input. T0626.EPS
6-22 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
The multiple ranges use the following parameters: Table 6.4.1 Status Output for Automatic Multiple Ranges
[B23: Flow Span] Setting of the flow rate span Switching
(Setting of the forward No.1 range) Status output
[F30: Forward Span 2] Setting of the forward No.2 Parameter setting
Function DIO
DO
range F20 F21 DIO (O) DIO (I)
No No Forward single
[F31: Forward Span 3] Setting of the forward No.3 Function
– – –
Function range
range
Fwd/Rev No Forward Open – –
[F32: Forward Span 4] Setting of the forward No.4 Rngs (O) Function Auto forward/ Reverse Closed – –
range No Fwd/Rev reverse 1 range Forward – Open –
Function Rngs (O) Reverse – Closed –
[F33: Reverse Span 1] Setting of the reverse No.1
Auto 2 No Forward 1 range Open – –
range Rngs (O) Function Forward 2 range Closed – –
Auto forward
[F34: Reverse Span 2] Setting of the reverse No.2 No Auto 2 2 ranges Forward 1 range – Open –
range Function Rngs (O) Forward 2 range – Closed –
[F40: Auto Range Hys] Setting of the automatic Auto 3 Auto 3 Auto forward
Forward 1 range Open Open –
Forward 2 range Closed Open –
multiple ranges hysteresis width. Rngs (O) Rngs (O) 3 ranges
Forward 3 range Open Closed –
[F41: Bi Direction Hys] Setting of the forward/ Forward 1 range Open Open –
reverse flow measurement hysteresis width Auto 4 Auto 4 Auto forward Forward 2 range Closed Open –
Rngs (O) Rngs (O) 4 ranges Forward 3 range Open Closed –
Forward 4 range Closed Closed –
Forward 1 range Open Open –
Multiple Ranges Setting 1: Fwd/Rev Auto 2 Forward 2 range Open Closed –
Automatic multiple ranges switching Rngs (O) Rngs (O) Reverse 1 range Closed Open –
Auto forward/ Reverse 2 range Closed Closed –
When the instantaneous flow rate exceeds 100% of
reverse 2 ranges Forward 1 range Open Open –
the range, transition to the next range (up to four Auto 2 Forward 2 range Closed Open –
Fwd/Rev
ranges) is carried out automatically. Furthermore, Rngs (O) Rngs (O) Reverse 1 range Open Closed –
when the flow is in reverse, the reverse range is Reverse 2 range Closed Closed –
automatically selected. *: “No Function” is the default value. Only DO or DIO terminals are
used for single or dual ranges; accordingly, the unused terminal
Range switching can be confirmed according to the remains at the default value (i.e., No Function) and can therefore
status of the DO and DIO status output terminals. be used for other functions.
Refer to Table 6.4.1: Status Output for Automatic *: “DIO (O)” indicates DIO function is used for output.
T0627.EPS
6-23 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
100%
F20: DO Function F21: DIO Function
Select a function. Select a function.
6-24 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
*: “No Function” is the default value. Only DIO terminal is used for
dual ranges; accordingly, the unused DO terminal remains at the
default value (i.e., No Function) and can therefore be used for
other functions. [F40: Auto Range Hys] Setting of automatic range-
*: “DIO (I)” indicates DIO function is used for input. T0628.EPS switching hysteresis width
Automatic switching takes place for multiple range
switching when 100% of the range is exceeded, and
this parameter allows a hysteresis width to be set for
this switching.
Refer to Figure 6.4.1: Multiple Ranges and Hysteresis
Widths.
6-25 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
mum span. 30
A setting value of -110% indicates that the alarm is 20
disabled.
Low Low Alarm
0 Time (t)
[G13: High High Alarm] High-high alarm setting
H L
This parameter sets the high-high limit (HH) alarm DO
value, and this is done using a % value of the maxi-
HH LL
mum span. DIO
A setting value of 110% indicates that the alarm is
Select “H/L Alarm(O)” for F20: DO Function
disabled. Select “HH/LL Alarm(O)” for F21: DIO Function
Select “Closed (On) Act” for F22: DO Active Mode
NOTE Select “Closed/Short Act” for F23: DIO Active Mode
F0608.EPS
Setting of -110% or 110% results in the corre-
sponding function being disabled; accordingly,
settings can be combined to implement only high
alarms or low alarms, etc.
6-26 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
[%] [%]
100 100 High High Alarm
90
80 80
High Alarm High Alarm
20
Low Low Alarm
0 Time (t) 0 Time (t)
H H
DO DO
L Alarm set to L Alarm set to
-110% indicates -110% indicates
that the alarm is that the alarm is
LL disabled. HH disabled.
DIO DIO
HH Alarm set to 110% indicates
LL Alarm set to -110% indicates
that the alarm is disabled.
that the alarm is disabled.
NOTE
6-27 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
[G14: H/L Alarm Hys] Setting of upper/lower alarm [G22: 4-20mA Burn Out] Display of the current
value hysteresis width output during a CPU failure
This parameter sets the hysteresis width for upper and This parameter displays the current output direction for
lower alarm value, using a % value of the maximum a CPU failure (i.e., burnout). Note that communication
span. will not be possible if such a failure occurs.
With the standard specification, this is set to High and
Output Example 25mA is output when a failure occurs. Low is setup for
optional code C1, and in such a case, 0mA is output
The hysteresis width is set to 5%.
when a failure occurs.
Settings are:
G10: Low Alarm = 30%
NOTE
G11: High Alarm = 80%
G12: Low Low Alarm = 20% The current output direction for a CPU failure
(i.e., burnout) can be changed. Refer to selection
G13: High High Alarm = 90%
10.2.1: Setting of Burnout Switch.
G14: H/L Alarm Hys = 5%
6-28 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
alarm.
NOTE
Setting Function
No Not recognized as an alarm Records for “30: Sig Overflow” are kept only
when G31 specifies that this condition is to be
Yes Recognized as an alarm
T0634.EPS
recognized as an alarm (i.e., “Yes” is selected).
Records for “31: Empty Pipe” are kept only when
NOTE G32 specifies that this condition is to be recog-
The AXFA14 or the AXF integral flowmeter has nized as an alarm (i.e., “Yes” is selected).
three different type of alarm (i.e., system alarms, Records for “33: Adhesion Alm” are kept only
process alarms, and setting alarms). For setting when G34 specifies that this condition is to be
alarms and process alarms, settings are made recognized as an alarm (i.e., “Yes” is selected).
with G30, G31, G32, G33 and G34 to specify
[G42: Alm Record Time1] Display the operation
whether these will be recognized as an alarm.
time of alarm record1
Refer to Section 6.5: Alarm Functions for more
This parameter is used to display the operation time at
details regarding the content of each alarm and which the alarm indicated by G41: Alm Record1
the effect of alarm recognition on output. was occurred. For example, “1D23:45” indicates that
an alarm was occured at the operation time of 1 day,
[G40: Operation Time] Display of operation time 23 hours, and 45 minutes.
This parameter is used to display the operation time.
The operation time is the total time that is counted IMPORTANT
while the device works actually.
Use these values as a reference because the
When the power supply is off, the operation time is not
time of alarm records (1 to 4) have an error.
counted.
For example, “1D23:45” indicates an operation time of
[G43: Alm Record2] Alarm record2
1 day, 23 hours, and 45 minutes.
This parameter is used to display the second most-
IMPORTANT recent alarm, and the alarms that can be displayed are
the same as those for G41: Alm Record1.
Use this value as a rough guideline because the
[G44: Alm Record Time2] Display the operation
operation time has an error.
time of alarm record2
This parameter is used to display the operation time at
[G41: Alm Record1] Alarm record1 which the alarm indicated by G43: Alm Record2
This parameter is used to display the most-recent was occurred. For example, “1D23:45” indicates that
alarm, and the alarms that can be displayed are as an alarm was occured at the operation time of 1 day,
follows. 23 hours, and 45 minutes.
6-29 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
[G45: Alm Record3] Alarm record3 [H30: Language] Selection of language used for the
This parameter is used to display the third most-recent display unit
alarm, and the alarms that can be displayed are the → Refer to the description for parameter B10
same as those for G41: Alm Record1. This parameter can be used to select the language for
the display unit.
[G46: Alm Record Time3] Display the operation
time of alarm record3
This parameter is used to display the operation time at (8) Menu J: Auxiliary Function Setting items
which the alarm indicated by G45: Alm Record3 Menu J contains setting items such as the flow direc-
was occurred. For example, “1D23:45” indicates that tion, rate limits, and current output limits.
an alarm was occured at the operation time of 1 day,
23 hours, and 45 minutes. [J10: 4-20mA Low Cut] Setting of the low-cut range
for current output
[G47: Alm Record4] Alarm record4 This parameter is used to force current output to 0%
This parameter is used to display the fourth most- (i.e., 4mA) in the vicinity of 0% output, and setting for
recent alarm, and the alarms that can be displayed are the current (4 to 20 mA) output low cut is made using
the same as those for G41: Alm Record1. a percentage of the smallest flow rate span. However,
the low cut function will be terminated if this param-
[G48: Alm Record Time4] Display the operation eter is set to 0%.
time of alarm record4 The indications of the instantaneous flow rates (%,
This parameter is used to display the operation time at Actual instantaneous flow rate, mA, Bar graph) on the
which the alarm indicated by G47: Alm Record4 display unit are the same action.
was occurred. For example, “1D23:45” indicates that
an alarm was occured at the operation time of 1 day, Example: Situation where low cut is set to 10%
23 hours, and 45 minutes.
Output Setting value
5.6mA(10%)
(7) Menu H: Display Setting items
Menu H contains setting items relevant to the display
unit. 4mA
0.5% 0.5%
Input
[J20: Flow Direction] Setting of the flow direction Signal processing method:
Upon shipment from the manufacturing plant, the A fixed upper and lower limit value is setup with
system is setup such that flow in the same direction, as respect to the primary delay response value for the
shown by the direction of the arrow mark on the flow rate value obtained during the previous sam-
flowtube, will be measured as forward flow; however, pling, and if the currently sampled flow rate is
this parameter can be used to set “Reverse” so that outside these limits, then the corresponding limit is
flow in the opposite direction to the arrow mark will be adopted as the current flow rate value. In addition, if
treated as forward. signals which breach the limits in the same direction
occur over multiple samples (i.e., within the dead
time), it is concluded that the corresponding signal is
a flow rate signal.
6-31 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
Example 1: Step input [J24: T/P Damp Select] Setting of damping opera-
Input: 0 to 10% tion
Damping time constant: 3 s This parameter is used to select that the flow rate value
Dead time: 3 s
Rate limit value: 1% obtained through damping calculation for totalization
Step signal and pulse output or the instantaneous flow rate value
10%
(no damping) for totalization and pulse output.
Flow rate value Setting Function
after rate limit 63.2%
processing
Damp Damping
100 225 Number of signal samples [J30: Power Synch] Setting of power synchroniza-
Dead time: 3 s F0614.EPS tion
(1) In comparison with the previous value at (a), it is This parameter sellects whether or not the internal
determined that the signal is in excess of the rate frequency is to be synchronized with that of the power
limit value and the response becomes 1%. How- supply.
ever, the actual output applies damping, and Setting Function
therefore the output turns out to be as indicated by No Not synchronized
the solid line. Yes Synchronized
T0639.EPS
(2) Subsequent flow values within the dead time zone
correspond to signals of post-damping flow value [J31: Power Frequency] Setting of power fre-
+ rate limit value (1%). quency
When “Yes” (i.e., in synchrony) has been selected for
(3) Since input signals do not return to within the rate
J30: Power Synch, this parameter is used to display
limit value during the dead time, it is determined at
the power supply frequency. If “No” (i.e., not synchro-
(c) that this signal is a flow rate signal.
nized) has been selected, the power supply frequency is
(4) The output signal becomes a damped curve and to be specified.
compliance with the step signal begins.
Three seconds after determination of a flow rate IMPORTANT
signal in the above figure, a level of 63.2% is
reached. In situations where a DC power supply is used
for converters, set the local commercial power
Example 2: Slurry noise
frequency in area where the converter is in-
Input: 0 to 10% stalled.
Slurry noise Damping time constant: 1 s Set “No” for J30: Power Synch and the local
Dead time: 1 s commercial power frequency for J31: Power
Flow rate value
after rate limit Rate limit value: 1%
+1% processing Frequency.
In the figure on the left, it is
-1% determined that the slurries
Flow rate value after damping
noise signal is not a flow rate Following settings are necessary by power supply and
signal.
Time
by flow tube size.
Dead time: 1 s F0615.EPS
Power Supply Code 1
(100 to 240 V AC or 100 to 120 V DC)
[J23: Pulsing Flow] Selection of pulsing flow Size 2.5 mm (0.1 in.)
support to 400 mm (16 in.)
In a situation where pulsating flow causes error in the AC J30 Power synchronous (Yes)
power supply J31 No setting
average flow value, due to the application of a plunger DC J30 Power asynchronous (No)
pump, this parameter provides functionality whereby power supply J31 Local commercial power frequency
calculation is controlled and variations in flow rate are T0642-1.EPS
Power Supply Code 2 (24 V AC/DC)
followed.
Size 2.5 mm (0.1 in.) to 400 mm (16 in.)
Setting Function
AC J30 Power asynchronous (No)
No Normal power supply J31 Local commercial power frequency
Yes Support for pulsing flow DC J30 Power asynchronous (No)
T0637.EPS power supply J31 Local commercial power frequency
T0642-2.EPS
6-32 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
[J40: Memo 1] Setting of memo 1 [K11: Adhesion Level1] Setting the resistance value
for adhesion diagnostic level1
[J41: Memo 2] Setting of memo 2
This parameter sets the resistance value (in M ohm) for
[J42: Memo 3] Setting of memo 3 judgment of Level 1.
These parameters are used with the memo function, [K12: Adhesion Level2] Setting the resistance value
and up to 16 characters can be set for each. for adhesion diagnostic level2
This parameter sets the resistance value (in M ohm) for
[J50: Software Rev No] Display of software judgment of Level 2.
revision
This parameter is used to display the software’s [K13: Adhesion Level3] Setting the resistance value
revision number. for adhesion diagnostic level3
This parameter sets the resistance value (in M ohm) for
(9) Menu K: Diagnostic Function Setting items judgment of Level 3.
Menu K contains items that are relevant to the diagno- *: The warning 80: Adhesion Wng is displayed
sis of insulation adhesion to the electrode. when the adhension level reaches Level 3.
*: If “Warning Output” has been selected for F20: DO
[K10: Adhesion Check] Setting of adhesion Function or F21: DIO Function, then status
diagnostic function output will be performed when the adhesion level
This parameter selects whether or not the adhesion reaches Level 3.
diagnostic function will be carried out. [K14: Adhesion Level4] Setting the resistance value
Setting Function for adhesion diagnostic level4
No Halt the adhesion diagnostic function This parameter sets the resistance value (in M ohm) for
Yes Carry out the adhesion diagnostic function judgment of Level 4.
T0640.EPS *: The process alarm 33: Adhesion Alm is displayed
when the adhension level reaches Level 4.
NOTE *: Alarm output will be preformed if “Alarm Output”
has been selected for F20: DO Function or F21:
Adhesion Diagnostic Function DIO Function, and “Yes” for G34: Alm-Adhe-
This function diagnose adhesion using elec- sion.
trode resistance values.
When “Adhesion check” has been set for B41/ [K15: Adh Measure Value] Displays the resistance
H11: Display Select 2 or B42/H12: Display value for adhesion diagnose
This parameter displays the value measured using the
Select 3, the diagnose adhesion is indicated
on the display unit using four different levels. adhesion diagnostic function (in M ohm).
If the judgment value for Level 3 is exceeded, When “No” is selected for K10: Adhesion Check,
this parameter displays the indetermination value.
a warning is displayed; and if the value for
Level 4 is exceeded, an alarm is displayed.
(10) Menu M: Automatic Zero Adjustment
Available conductivity for this function is Function Setting items
limited to:
Menu M contains items that are relevant to automatic
Nominal size 10 mm or smaller: 30 S/cm
adjustment of the zero point.
Nominal size 15 mm or larger: 10 S/cm
Make sure to use the adhesion diagnostic [M10: Auto Zero Exe] Execution of automatic zero
function with the greater conductivity than the adjustment function
above mentioned value. → Refer to the description of parameter B50.
[M11: Magflow Zero] Results of automatic zero
Alarm adjustment
Warning
This parameter is used to display the results obtained
from B50/M10: Auto Zero Exe. Specifically, the
correction value displayed, and it is also possible to
Level: 1 Level: 2 Level: 3 Level: 4
F0616.EPS
directly enter correction value.
6-33 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
(11) Menu N: Loop Test Setting items [N31: Test DIO (O)] Setting for the DIO terminal
Menu N contains items that are relevant to loop testing. condition during testing
This parameter sets the condition of the DIO terminal
[N10: Test Mode] Setting for loop test execution during loop testing. Setting is possible when “Test”
Setting Function has been selected for N10: Test Mode.
Normal No execution of loop testing.
Setting Function
Test Loop testing is started
Input mode Must be set when N32: Test DIO (I) is used
T0641.EPS
to display the condition of the DIO terminal.
Open (Off) DIO terminal in Open (Off) condition
IMPORTANT Closed (On) DIO terminal in Closed (On) condition
T0643.EPS
[N11: Test Output Value] Setting for test output [P10: Key Code] Parameter of the display restriction
values This parameter restricts access to the Service Mode.
During loop testing, current output (4 to 20mA),
totalization, and pulse will be output in accordance
NOTE
with this parameter’s setting, and values can be set
when “Test” has been selected for N10: Test Mode. Write Protect function
With multiple ranges or when performing forward/
The parameters P20 through P23 are set
reverse flow measurements, setting should be done
when using the write protect function. Specifi-
using a percentage of the maximum range.
cally, this function responds to a hardware
switch or the setting of a software password,
[N30: Test DO] Setting for DO terminal condition
and it protects parameters from being over-
during testing
written.
This parameter sets the condition of the DO terminal
If the hardware switch is set to “Protect”, it will
during loop testing. Setting is possible when “Test”
not be possible to overwrite parameters;
has been selected for N10: Test Mode.
furthermore, this condition will be maintained
Setting Function until the switch is set to “Enable”.
Open (Off) DO terminal in Open (Off) condition For more details regarding hardware switch
Closed (On) DO terminal in Closed (On) condition
settings, refer to Section 10.2.2: Setting of
Write Protect Switch.
Pulse Outputs pulses as were specified with Menu E.*
T0642.EPS
6-34 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
Default setting (Enable) [P23: Software Seal] Display the software seal
P20:Write Protect When the joker password has been used to release
No write protection, this parameter displays “Break”, and
when protection is cancelled using the password set
F0617.EPS using P22: New Password, it returns to “Keep”.
Write protection (Protect) NOTE
P20:Write Protect
If you should forget your password, the joker
Yes
password can be used to temporarily release write
protection function. To obtain the joker password,
F0618.EPS
please contact your nearest YOKOGAWA sales
[P21: Enable Wrt Passwd] Setting of password to office.
release the write protection function
When the correct password is input, write protection
will be released for a period of 10 minutes; further-
more, this period will be extended by a further 10
6.5 Alarm Functions
minutes each time a parameter is overwritten.
6.5.1 Alarm Levels
P21:Enable Wrt Passwd
******** Alarms are classified into the following four different
types based on level.
F0619.EPS
P22:New Password
When an alarm has been occurred, the corresponding
alarm name, description, and suitable countermeasure
F0620.EPS will be displayed on the display unit. The normal
The default setting for this parameter is a string of 8 Display Mode and Alarm Mode may be displayed
spaces (i.e., Enable), and thus, the password field will alternatively. When a warning has been issued, the
be empty. When the cursor is flashing, the password corresponding content will be shown in the third line in
should be input. Press the SET key twice to confirm the Display Mode.
the password. The display will then change to
“********”. Upon occurrence of an alarm
After password setting (example: a System alarm)
Countermeasure
message
F0621.EPS
To change a password, first of all use the password Upon issuance of a warning
originally set with P21: Enable Wrt Passwd to (a description appears in the 3rd line only
when a warning is occurred)
release the write protect function, and then set the new
password. Alternatively, if it is desired to return to the
condition where no password is set, enter a string of 8
spaces. Description of
warning
F0622.EPS
6-35 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
6-36 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
63 PLS > 500p/s Pulse rate is 500 pps or Closed Normal Normal Alarm Mode
more with 1 ms selection. (On) operation operation Stopped (message) No
Pulse rate is 25 pps or
64 PLS > 25p/s more with 20 ms selection.
Pulse rate is 15 pps or
65 PLS > 15p/s more with 33 ms selection.
Pulse rate is 10 pps or
66 PLS > 10p/s more with 50 ms selection.
Pulse rate is 5 pps or
67 PLS > 5p/s more with 100 ms selection.
Pulse rate is 0.00005 pps
70 PLS<0.0001p/s or less.
Measure Mode (C20) is
set to Enhanced DF Alarm Mode
71 Meas Mod Set without selecting an Closed Fixed Stopped Stopped (message) No
optional code (On)
HF1 or HF2.
6-37 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
Process Alarms (Device is normal but process-related errors make correct measurement impossible.)
Display unit/BRAIN Alarm countermeasure
(60) content message on display unit Alarm description Countermeasure
Carry out an investigation as follows:
• Check the signal cable for breakage.
Check signal cable • Check for contact between signal cable,
30:Sig Overflow Input signal error power cable, and excitation cable.
and grounding
• Check for stray currents in the fluid.
• Check the grounding.
Fill flow tube with Flowtube is not filled with
31:Empty Pipe Fill the flowtube with fluid.
fluid fluid
Flow rate alarm for greater
32:HH/LL Alm Check the flow rate and than High-High limit value Check the flow rate and setting value of
setting value or less than Low-Low limit High High limit and Low Low limit.
value.
33:Adhesion Alm Clean electrodes Electrode adhesion alarm Clean the electrodes.
T0650.EPS
6-38 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
Setting Alarms (Device is normal but errors have been made in the setting of parameters.)
Display unit/BRAIN Alarm countermeasure
(60) content message on display unit Alarm description Countermeasure
Check whether parameters
Check parameter C40, C41, Span flow velocity setting is 11 m/s or C40, C41, and C42 are correct.
50:Span > 10m/s
and C42 more In case that multiple range or
forward and reverse flow
Check parameter C40, C41, Span flow velocity setting is 0.05 m/s or measurement functions is used,
51:Span < 0.1m/s less check whether parameters F30
and C42
through F34 are correct.
Check parameter D10 and
52:TTL>10000p/s Totalization rate is 11000 pps or more
D11 Check whether parameters
Check parameter D10 and D10 and D11 are correct.
53:TTL<0.0001p/s Totalization rate is 0.00005 pps or less
D11
54:4-20 Lmt Err Check parameter J11and J12 The condition [4-20 low limit (J11) < Check whether parameters J11
4-20 high limit (J12)] is not satisfied. and J12 are correct.
The condition [No. 1 range < No. 2 Check whether parameters
55:Multi Rng Err Check parameter F30 to F34 range < No. 3 range < No. 4 range] is F30 through F34 are correct.
not satisfied for multiple ranges.
The condition [High Alarm (G11) –
Low Alarm (G10) > H/L Alarm Hys
Check whether parameters
56:H/L HH/LL Set Check parameter G10 to G14 (G14)] or the condition [High High G10 through G14 are correct.
Alarm (G13) – Low Low Alarm (G12)
> H/L Alarm Hys (G14)] is not satisfied.
Mass units have been selected for Base
Check parameter C40, C45, Flow Unit (C40) but density is set to 0. Check whether parameters
57:Dens Set Err C40, C45, and C46 are correct.
and C46
Pulse rate is 11000 pps or more with
Check parameter E10, E11, 50% duty selection.
60:PLS > 10000p/s Pulse rate is 10000 pps or more with
and E12
0.05 ms selection.
Check parameter E10, E11, Pulse rate is 5000 pps or more with
61:PLS > 5000p/s 0.1 ms selection.
and E12
Check parameter E10, E11, Pulse rate is 1000 pps or more with
62:PLS > 1000p/s 0.5 ms selection.
and E12
Check parameter E10, E11, Pulse rate is 500 pps or more with
63:PLS > 500p/s 1 ms selection.
and E12 Check whether parameters
Check parameter E10, E11, Pulse rate is 25 pps or more with E10, E11, and E12 are correct.
64:PLS > 25p/s 20 ms selection.
and E12
Check parameter E10, E11, Pulse rate is 15 pps or more with
65:PLS > 15p/s 33 ms selection.
and E12
Check parameter E10, E11, Pulse rate is 10 pps or more with
66:PLS > 10p/s 50 ms selection.
and E12
Check parameter E10, E11, Pulse rate is 5 pps or more with
67:PLS > 5p/s 100 ms selection.
and E12
Check parameter E10, E11,
70:PLS<0.0001p/s Pulse rate is 0.00005 pps or less.
and E12
Measure Mode (C20) is set to Enhanced
DF without selecting an optional code Check whether parameter C20
71:Meas Mod Set Check parameter C20
HF1 or HF2. is correct.
A value of 3000.1 mm or more is set for Check whether parameter C32
72: Size Set Err Check parameter C32 Nominal Size (C32). is correct.
The condition in Adhesion detection Check whether parameters K11,
73: Adh Set Err Check parameter K11 to K14 level, Level:1<Level:2<Level:3<Level:4 K12, K13 and K14 are correct.
is not satisfied.
T0651.EPS
Setting Alarms (Device and measurements are normal but a warning is issued.)
Display unit/BRAIN Alarm countermeasure
(60) content message on display unit Alarm description Countermeasure
Slight adhesion to Clean and check the electrodes.
80:Adhesion Wng – electrodes. Refer to parameter K13.
Carry out adjustment as follows:
• Check if the flowtube is filled with
Results of automatic zero fluid.
82:Auto Zero Wng – adjustment are higher than • Check if the flow velocity is
the rated values. completely zero.
• Check the condition of grounding.
Confirm whether the flow rate is in
excess of the upper limit (108%) or
83:Fix Cur Wng – The current value is fixed. below the lower limit (-8%), or
whether upon entry to the Test Mode
or not.
84:Disp Over Wng Overflow in the display digits during Check whether parameter C43 is
–
(only for display unit) instantaneous flow rate display. correct.
Investigate whether the display unit
90:Disp SW Wng Display unit switches are not cover is fitted or whether the cover’s
(only for display unit) – operating. glass surface is dirty.
T0652.EPS
6-39 IM 01E20C02-01E
6. PARAMETER DESCRIPTION
NOTE
NOTE
6-40 IM 01E20C02-01E
7. OPERATION VIA BRAIN TERMINAL (BT200)
This chapter describes the AXFA14 converter as (1) Alphanumeric keys and shift keys
an example. The same attention must be paid to You can use the alphanumeric keys in conjunction with
the AXF integral flowmeter. the shift keys to enter letters, digits, and symbols.
tions
7.1.1 Key Layout and Display Shift keys F0703.EPS
0.3
Movement keys 1 –9
• Select items Function keys
T0701.EPS
• Move the cursor Used to execute
• Change pages commands
displayed at the
bottom of the
screen.
b) Entering letters (i.e., A through Z)
Power
ON/OFF key (See Table 7.1.) Press an alphanumeric key following a shift key to
ENT key enter the letter shown on the same side as the shift
• Enters selected key. The shift key must be pressed for each letter
items
• Sets up input data being input.
on the connected
Alphanumeric keys
instrument.
• Enter digits Left-side letter on an Right-side letter on
• Runs BT200
• Enter letters in alphanumeric key an alphanumeric key
functions.
combination with
the shift keys. Shift keys
F0701.EPS F0704.EPS
If BATTERY is displayed on W
the screen, it indicates that the
battery voltage has dropped. IC
F0702.EPS
7-1 IM 01E20C02-01E
7. OPERATION VIA BRAIN TERMINAL (BT200)
Use the function key [F2] CAPS to select between Function Command List
uppercase and lowercase (for letters only). The case Command Function
toggles between uppercase and lowercase each time ADJ Displays the ADJ menu
you press [F2] CAPS. CAPS/caps Selects uppercase or lowercase
CODE Selects symbols
Entering uppercase Entering lowercase CLR Erases input data or deletes all data
7-2 IM 01E20C02-01E
7. OPERATION VIA BRAIN TERMINAL (BT200)
EX
1 N/– POWER Restrictions exist with regard to the distance
EXCITATION 2 L/+ SUPPLY
C +
CURRENT
OUTPUT
I
over which communication is possible. (See
SA –
SIGNAL A +
Chapter 11: Outline.)
DO
B –
SB + DIO
–
4 to 20 mA IMPORTANT
Control room
DC signal
Relaying transmission Terminal Receiving If the power of flowmeter is turned off within 30
I terminals line board instrument
seconds after parameters have been set, these
I settings will be canceled. Accordingly, please
Receiving keep the power on for at least 30 seconds after
resistance: setting parameters.
250 to 450
IMPORTANT
BT200
BT200 BT200 F0705.EPS
Figure 7.2 Connecting the BT200 After approximately 5 minutes of inactivity, the
Auto Power-Off function will operate to turn your
WARNING BT200 off.
Be sure to set parameters as “Protect” on the
write protect function after finish of parameter
setting work. NOTE
Under extremely rare case, the infra-red In case of BT200, the parameters are displayed
switches may respond unexpectedly in such in English only.
conditions as sticking ball of water or extraneous Even if the language with the exception of English
substances on the surface of display panel glass is selected at B10/H30: Language, the param-
according to the principle of infra-red switch eters are displayed in English upon BT200.
operation.
Its probability rises in such cases as sticking rain
water by storm or other similar situation and 7.2.2 The data update and upload/
washing up work near flowmeter installation download function of BT200
place.
Either to illuminate or stop illuminating the infra- (1) The data update of BT200
red switches by the flashlight may cause the When the following parameters are displayed, the
measured data is updated automatically every seven
mis-reaction.
seconds.
Refer to Chapter 6 “Menu P: Parameter Protec-
tion Items” and section “10.2.2” how to use the Item Name (BRAIN) Item Name (BRAIN)
write protect function in detail. A10 FLOW RATE (%) G42 ALM TIME 1
A20 FLOW RATE G43 ALM RECORD2
A21 FLW RATE (mA) G44 ALM TIME 2
IMPORTANT A30 TOTAL G45 ALM RECORD3
A31 REV TOTAL G46 ALM TIME 3
Communication signal is superimposed on
A32 DIF TOTAL G47 ALM RECORD4
analog output signal. It is recommended to set a
C44 VELOCITY CHK G48 ALM TIME 4
low-pass flter (approximately 0.1s) to the re-
ceiver in order to reduce the output effect from G22 4-20 BURNOUT N32 TEST DIO (I)
G40 OPERATE TIME P20 W PROTECT
G41 ALM RECORD1 P23 SOFT SEAL
T0704.EPS
7-3 IM 01E20C02-01E
7. OPERATION VIA BRAIN TERMINAL (BT200)
or
F0706-01.EPS
NOTE
7-4 IM 01E20C02-01E
7. OPERATION VIA BRAIN TERMINAL (BT200)
MENU When the cursor has been SETTING When selected, “l (Liter)”
A:DISPLAY moved to B: EASY SETUP, B21:FLOW UNIT will begin to flash on and
B:EASY SETUP m3
C:BASIC SETUP press the key to l(Liter) off: Press the
D:TOTAL SET access Parameter Screen key once again to confirm
E:PULSE SET PRINTER OFF
(Sub-Item Parameter F2:PRINTER ON your selection.
F:STATUS FUNC
Search Mode). FEED POFF NO
In case of cancel, press the
HOME SET ADJ ESC
( NO ) key.
PARAMETER
B10:LANGUAGE Press the key twice The units for flow rate have
SETTING
English to move the cursor to B21:FLOW UNIT been changed to l (Liter).
B20:FLOW DAMPING B21: FLOW UNIT. l(Liter)
3.0s Press ( OK ) key to
B21:FLOW UNIT
m3 exit Setting Screen
DATA DIAG PRNT ESC (Parameter Replacement
FEED NO OK Mode), and then the display
returns to Parameter
X2 Screen (Sub-Item
Parameter Search Mode) of
Menu B items.
In case of redo of setting,
PARAMETER After moving the cursor to
B10:LANGUAGE B21: FLOW UNIT, press press the ( NO ) key
English to return the Setting Screen
B20:FLOW DAMPING the key to access
3.0s (Parameter Replacement
B21:FLOW UNIT Setting Screen (Parameter Mode).
m3 Replacement Mode).
DATA DIAG PRNT ESC ( OK )
X2
7-5 IM 01E20C02-01E
7. OPERATION VIA BRAIN TERMINAL (BT200)
MENU When the cursor has been SETTING The data will begin to flash
A:DISPLAY moved to B: EASY SETUP. B23:FLOW SPAN on and off: Press the
B:EASY SETUP 100.000l/min
C:BASIC SETUP Press the key to + 120 key once again
D:TOTAL SET
access Parameter Screen to confirm your entry.
E:PULSE SET PRINTER OFF
(Sub-Item Parameter F2:PRINTER ON In case of cancel, press the
F:STATUS FUNC
HOME SET ADJ ESC Search Mode). FEED POFF NO ( NO ) key.
In the parameter list, the The value for flow span has
PARAMETER SETTING
B10:LANGUAGE parameter for setting of flow B23:FLOW SPAN been changed to
English rate span is B23: FLOW 120.000l/min “120.000 l/min.”
B20:FLOW DAMPING
3.0s SPAN. Press the Press ( OK ) key to
B21:FLOW UNIT exit Setting Screen
l(Liter)
key four times to move the
cousor to B23. (Parameter Replacement
DATA DIAG PRNT ESC FEED NO OK
(Note that the key Mode), and then the display
returns to Parameter
can be used to move the
Screen (Sub-Item
cursor to the top of the next
Parameter Search Mode) of
screen.
Menu B items.
In case of redo of setting,
press the ( NO ) key
or
to return the Setting Screen
(Parameter Replacement
Mode).
PARAMETER After moving the cursor to
B22:TIME UNIT B23: FLOW SPAN, press
/min ( OK )
B23:FLOW SPAN the key to access
100.000l/min
B24:FLOW DECIMAL Setting Screen (Parameter
l Replacement Mode). PARAMETER The changed setting for
DATA DIAG PRNT ESC B22:TIME UNIT flow rate span can now be
/min confirmed.
B23:FLOW SPAN
120.000l/min
B24:FLOW DECIMAL Press the ( ESC ) key
l
to return to Menu Screen
DATA DIAG PRNT ESC (Major Item Parameter
SETTING Search Mode).
In this mode, new values can
B23:FLOW SPAN
100.000l/min be entered into the
F0708.EPS
+ 0 highlighted field using the
alphanumeric keys.
7-6 IM 01E20C02-01E
7. OPERATION VIA BRAIN TERMINAL (BT200)
MENU When the cursor has been The tag number has been
SETTING
A:DISPLAY moved to C: BASIC SETUP, C10:TAG NO changed to “FI-1201”.
B:EASY SETUP
C:BASIC SETUP press the key to FI-1201
Press ( OK ) key to
D:TOTAL SET access Parameter Screen
E:PULSE SET exit Setting Screen
F:STATUS FUNC (Sub-Item Parameter
Search Mode). (Parameter Replacement
HOME SET ADJ ESC
FEED NO OK Mode), and then the display
returns to Parameter
Screen (Sub-Item
Parameter Search Mode) of
Menu C items.
In case of redo of setting,
PARAMETER The cursor will already be press the ( NO ) key
C10:TAG NO aligned with C10: TAG NO.
FI-1101 to return the Setting Screen
C11:FLOW DAMPING Press the key to (Parameter Replacement
3.0s access Setting Screen Mode).
C20:MEASURE MODE
Standard DF (Parameter Replacement
Mode). ( OK )
DATA DIAG PRNT ESC
X4
7-7 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
8-1 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
G Control room
1 N/– POWER
EX
EXCITATION 2 L/+ SUPPLY
CURRENT
4 to 20 mA DC signal line
C + OUTPUT
I
Terminal board
SA –
SIGNAL A +
DO
+
B –
SB + DIO
– – Relaying
terminals
USB
FieldMate
Receiving instrument
I+ I- modem
load resistance:
250 Ω to 600 Ω
USB (including cable
AXFA14 resistance)
PC/FieldMate
F0802.EPS
WARNING IMPORTANT
Be sure to set parameters as “Protect” on the If the power of flowmeter is turned off within 30
write protect function after finish of parameter seconds after parameters have been set, these
setting work. settings will be canceled. Accordingly, please
Under extremely rare case, the infra-red keep the power on for at least 30 seconds after
switches may respond unexpectedly in such setting parameters.
conditions as sticking ball of water or extraneous
substances on the surface of display panel glass
according to the principle of infra-red switch
operation. NOTE
Its probability rises in such cases as sticking rain
water by storm or other similar situation and Before updating any setting, remember to always
washing up work near flowmeter installation check the data content you want to change as
place. described in Chapter 6: Parameter Description.
Either to illuminate or stop illuminating the infra-
red switches by the flashlight may cause the
mis-reaction.
Refer to Chapter 6 “Menu P: Parameter Protec- NOTE
tion Items” and section “10.2.2” how to use the In case of HART Configuration, the parameters
write protect function in detail. This menu in the are displayed in English only.
275 is located at [Hot key] → [2 Wrt Protect Even if the language with the exception of
Menu]. English is selected at “Language” setting display,
the parameters are displayed in English upon
HART Configuration Tool.
8-2 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
8-3 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
8-4 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
Burst Mode
IMPORTANT
AXFA14 continuously sends the data via HART
The D/A trim should be executed only at single communication when the burst mode is set on (any one
range mode. If the D/A trim is executed at Bi of PV, % range/current, or process vars/crnt). The data
direction mode, it is possible that the current is sent intermittently as a digital signal at 3 times a
output becomes 108%. second.
The burst mode is set as follows.
(1) Setting the data to be sent
• Procedure to call up the display
IMPORTANT
DD Device Setup → Detailed setup
When “D/A trim” or “Scaled D/A trim” is carried → HART output → Burst option
out, the warning message “83: Fix Cur Wng” is DTM Configuration → HART → Burst option
T0810.EPS
displayed on the display unit.
Select the type of data to be sent from the following
options:
- Instantaneous flow rate (PV)
- Output in % and current output (% range/current)
CAUTION
- Instantaneous flow rate, totalization value* and
The output adjustment function can match the current output (Process vars/crnt)
4mA and 20mA output to the reference meter * “Totl,” “Reverse Totl” or “Dif Totl”
such as a voltmeter. In the output adjustment, it (2) Setting the burst mode
is necessary to use the calibrated voltmeter and
• Procedure to call up the display
resistance.
DD Device Setup → Detailed setup →
HART output → Burst mode
DTM Configuration → HART → Burst mode
Fixed Current Output
T0811.EPS
This feature can be used to output a fixed current for Then, select “On” at the menu to start the burst
loop checks. mode.
In the case of using DD To release from the burst mode, call up the burst
Call up the test output parameter (Loop test) and select mode display, and set to “Off.”
the output signal. The default setting is “Off.”
8-5 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
NOTE
8-6 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
Parameter
Read/Write of BRAIN Data(*1)
protocol
F0803.EPS
8-7 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
Parameter
Read/Write of BRAIN Data(*1)
protocol
Enhanced DF W C20 –
Low MF (EDF) W C23 –
High MF (EDF) W C24 –
8-8 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
Parameter
Read/Write of BRAIN Data(*1)
protocol
8-9 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
Parameter
Read/Write of BRAIN Data(*1)
protocol
5 Review 1 Review1 R – –
2 Review2 R – –
3 Review3 R – –
R – –
4 Review4
*1 : Data Renewing
P : Periodic Date Renewing
u/d : Discretionary Renewing
– : Other (Method etc...) F0806.EPS
8-10 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
F0807.EPS
8-11 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
Root Menu
Process Variables A
Device Status B
Diag and Service C
Easy Setup D
Configuration E
Calibration F
Write Protect G
Parameter Data
Read/Write of BRAIN Renewing
protocol (*1)
A
Process Variables PV R A20 P
PV % rnge R A10 P
PV AO R A21 P
PV Span R B23 P
PV Damping R C11/B20 P
Totl R A30 P
Reverse Totl R A31 P
Dif Totl R A32 P
B
Device Status Process Variable PV
PV % rnge
Totl
Reverse Totl
Dif Totl
8-12 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
Parameter Data
Read/Write of BRAIN Renewing
protocol (*1)
C
Diag and Service Output Test Loop test – – –
Test Mode W N10 –
Test DO W N30 –
Test DIO (I) R N32 P
Test DIO (O) W N31 –
D
Easy Setup Tag W C10 u/d
Language W B10/H30 u/d
PV Damping W B20/C11 u/d
Base Flow Unit W B21/C40 u/d
Base Time Unit W B22/C41 u/d
PV Span W B23/C42 u/d
Flow Decimal Pnt W B24/C43 u/d
Total Unit W B30/D10 u/d
Total Scale W B31/D11 u/d
Pulse Unit W B32/E10 u/d
Pulse Scale W B33/E11 u/d
Display Select1 W B40/H10 u/d
Display Select2 W B41/H11 u/d
Display Select3 W B42/H12 u/d
Auto Zero Exe – – –
F0809.EPS
8-13 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
Parameter Data
Read/Write of BRAIN Renewing
protocol (*1)
E
Configuration Characterize Meter Nominal Size Unit W C31 u/d
Nominal Size W C32 u/d
Measure Mode R C20 –
Low MF R C21 –
High MF R C22 –
Low MF (EDF) R C23 –
High MF (EDF) R C24 –
MF Set – – –
8-14 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
Parameter Data
Read/Write of BRAIN Renewing
protocol (*1)
8-15 IM 01E20C02-01E
8. OPERATION VIA HART COMMUNICATOR
Parameter Data
Read/Write of BRAIN Renewing
protocol (*1)
F
Calibration Auto Zero Exe – M10/B50 –
Magflow Zero R/W M11 –
D/A trim – – –
Scaled D/A trim – – –
G
Write Protect Write protect R P20 P
Enable Wrt Password W P21 –
New Password W P22 –
Software Seal R P23 –
8-16 IM 01E20C02-01E
9. ACTUAL OPERATION
9. ACTUAL OPERATION
After you have installed the flowtube into the process
piping, wired the input/output terminals, set up the
required parameters, and performed a pre-operation
zero adjustment, the magnetic flowmeter should output
an accurate flow signal from its terminals as soon as
flow of the fluid to be measured begins. This section
describes zero adjustment and the corresponding
procedures.
For FOUNDATION Fieldbus protocol, please refer to IM
01E20F02-01E.
For PROFIBUS PA protocol, please refer to IM
01E20F12-01E.
IMPORTANT
9-1 IM 01E20C02-01E
9. ACTUAL OPERATION
NOTE
9-2 IM 01E20C02-01E
9. ACTUAL OPERATION
Sub-item Major item M:Adjustment When zero adjustment function has been completed,
Parameter Sub-item the system automatically returns to the sub-item
10:Auto Zero Exe
Search Mode selection (D) 11:Magflow Zero
selection screen (D).
F0901.EPS
NOTE
CAUTION
In certain cases where the multiple range function is being used with other status
inputs, it may not be possible to perform settings for automatic zero adjustment.
For more details, refer to the description of multiple ranges from Chapter 6:
Parameter Description.
In order to carry out zero adjustment via external status input, it will be necessary to set
“Ext Auto Zero (I)” using F21: DIO Function. The following describes the setting
procedure:
Major item F:Status Function Touch the switch once to move the cursor to
Sub-item
41:Bi Direction Hys
Parameter Sub-item 20:DO Function
F21: DIO Function.
Search Mode parameter 21:DIO Function
9-3 IM 01E20C02-01E
9. ACTUAL OPERATION
F21:DIO Function
Parameter
No Function
Touch the switch twelve times to move the
Replacement No Function
(execute) Mode Alarm Output
cursor to “Ext Auto Zero (I)”.
X12
F21:DIO Function
No Function
Touch the switch to select “Ext Auto Zero
Ext Auto Zero (I) (Zero adjustment via external status input)”.
Ext Ttl Preset (I)
NOTE
Sub-item Major item F:Status Function The system automatically returns to sub-item
20:DO Function
Parameter Sub-item 21:DIO Function
selection screen (E).
Search Mode selection (E) 22:DO Active Mode
F0902-2.EPS
Zero adjustment will be started if the DIO terminals are shorted (when the active mode has
been set to “Closed/Short Act” using F23: DIO Active Mode).
This process will end after approximately 30 seconds.
F0902-3.EPS
NOTE
When the DIO terminals continue to be shorted, this zero adjustment is automati-
cally repeated.
9-4 IM 01E20C02-01E
10. MAINTENANCE
10. MAINTENANCE
10.1 Maintenance 10.1.1 Fuse Replacement
CAUTION
IMPORTANT
Cover locking
screws
• As a rule, maintenance of this flowmeter should
be implemented in a maintenance service shop
where the necessary tools are provided.
F1002.EPS
• The amplifier assembly contains sensitive parts
Figure 10.1.1 Removing the Display Cover
that may be damaged by static electricity.
Excercise care so as not to directly touch the
electronic parts or circuit patterns on the board,
for example, by preventing static electrification
by using grounded wrist straps when handing
the assembly.
10-1 IM 01E20C02-01E
10. MAINTENANCE
10.1.2.2 Changing the Display Unit Direction 10.1.2.3 Installing the Cover
90 Degrees
(1) Taking care not to entangle the cables, install the
(1) Hold the display unit with your hand and remove cover to the flowmeter by turning it in the direc-
the two mounting screws. tion of the arrow as shown below.
(2) Turn the display unit 90 degrees clockwise and (2) Tighten cover locking screw 1 counterclockwise
confirm the assembling position, taking care of the
using a hexagonal wrench (nominal size 3) to lock
connector and wire of the display unit.
the cover.
At this time, do not remove the connector.
(3) Secure the display unit using its two mounting
screws.
*1
Cover locking
screws
F1005.EPS
Clockwise 90°
F1004.EPS
Figure 10.1.2 Changing the Display Unit Direction 90
Degrees
IMPORTANT
10-2 IM 01E20C02-01E
10. MAINTENANCE
F1007.EPS
10-3 IM 01E20C02-01E
10. MAINTENANCE
10.4 Troubleshooting
Although magnetic flowmeters rarely require maintenance, failures may occur when the
instrument is not operated correctly. This section describes troubleshooting procedures
where the cause of the breakdown is identified through receiver indication.
10.4.1 No Indication
START
Is anything else NO
being displayed?
YES
Does the
NO
arrow on the tube match the
flow direction?
Is the flowtube NO
full of fluid?
YES
Change the piping or the
Check the resistance between mounting condition so that
the flowtube’s A, B, and C the tube fills with the fluid.
terminals using a circuit tester.
Is the NO
resistance 100 M or more
in each case?
YES
Is foreign NO
matter adhering to
the walls?
YES
10-4 IM 01E20C02-01E
10. MAINTENANCE
START
YES
Are valves leaking? Replace the valve(s).
NO
F1009.EPS
10-5 IM 01E20C02-01E
10. MAINTENANCE
START
Are parameters NO
Set the parameters correctly.
set correctly?
YES
Is the NO
Completely ground the converter and
flowmeter completely flowtube (Refer to the section on
grounded? grounding in the relevant user’s manual).
YES
Does the NO
conductivity stay within the Use within the specified conductivity range.
specified range?
Signal terminals A-C and B-C: NO Dry the tube fully to restore insulation
100 M or more? resistance.
Excitation terminals EX1-C:
1 M or more?
YES
10-6 IM 01E20C02-01E
11. OUTLINE
11. OUTLINE
■ STANDARD SPECIFICATIONS HART:
Refer to IM 01E20F02-01E for FOUNDATION fieldbus Load Resistance:
communication type and IM 01E20F12-01E for 250 to 600 Ω (including cable resistance)
PROFIBUS PA communication type marked with “” Note: HART is a registered trademark of the FieldComm
Group.
11-1 IM 01E20C02-01E
11. OUTLINE
0 CAUTION
0 1 2 6 8 10
V[m/s] *1: When performing the Insulation Resistance Test or the
F02.EPS
11-3 IM 01E20C02-01E
11. OUTLINE
CAUTION
This instrument is a Class A product, and it is
designed for use in the industrial environment. Please
use this instrument in the industrial environment only.
11-4 IM 01E20C02-01E
11. OUTLINE
11-5 IM 01E20C02-01E
11. OUTLINE
G
D
D
E
E
AXF***G-F
AXF***C-F
Lightning Protector A lightning protector is built into the power terminals. A
DC Noise Cut The DC Noise Cut Circuit is built in. Available for 15 mm (0.5 in.) and larger sizes, and for
Circuit fluids with the conductivity of 50 µS/cm or higher. Nullifies the empty check and electrode ELC
adhesion diagnostic function.
Burn Out Down The output level is set to 0 mA during a CPU failure and is set 2.4 mA (-10%) or less during
an alarm. Standard products are delivered with a setting 25 mA during a CPU failure and (*2) (*2) C1
21.6 mA (110%) or more during an alarm.
NAMUR NE43 Output signal Failure alarm down-scale: The output level is set to 0 mA during a CPU
(*2) (*2) C2
Compliance limits: 3.8 to failure and is set 2.4 mA (–10%) or less during an alarm.
20.5 mA
Failure alarm up-scale. The output level is set to 25 mA during a CPU failure
(*2) (*2) C3
and is set 21.6 mA (110%) or more during an alarm.
Active Pulse Active pulses are output in order to drive an external electromagnetic or electronic counter
Output directly using the converter’s internal power supply. (Nullfies the standard transistor contact
pulse output.)
Output voltage: 24 V DC ±20% (*2) (*2) EM
Pulse specifications:
• The drive current of 150 mA or less
• Pulse rate: 0.0001 to 2 pps (pulse/second); Pulse width: 20, 33, 50, or 100 ms
Waterproof Glands Waterproof glands are attached to the electrical connections. Available only for JIS G1/2 – EG
female electric connections.
Waterproof Glands Waterproof glands with union joints are attached to the electrical connections. Available only
– EU
with Union Joints for JIS G1/2 female electric connections.
Plastic Glands Plastic glands are attached to the electrical connections. Available only for JIS G1/2 female – EP
electric connections.
Stainless Steel Provided with a JIS SUS304 (AISI 304 SS/EN 1.4301 equivalent) stainless steel mounting
SB
Mounting Bracket bracket in lieu of the standard carbon steel bracket.
Stainless Steel Screwed JIS SUS304 (AISI 304 SS/EN 1.4301 equivalent) stainless steel tag plate. Choose
Tag Plate this option when an SS tag plate is required in addition to the standard nameplate with the tag SCT
number inscribed on it.
Dimension (Height Width): Appr. 12.5 (4.92) 40 (15.7) mm (inch)
Painting Color Coated in black (Munsell N1.5 or its equivalent.) P1
Change
Coated in jade green (Munsell 7.5BG4/1.5 or its equivalent.) P2
Coated in metallic silver. P7
Epoxy Resin Epoxy resin coating which has alkali-resistance instead of standard polyurethane resin X1
Coating coating. The color is same as standard type.
High Anti-corrosion Three-layer coating (polyurethane coating on two-layer epoxy resin coating) in the same
Coating range as that for the standard coating. The color is same as standard type. X2
Salt/alkali/acid/weather-resistance.
Calibration Level 2: The Declaration and the Calibration Equipment List are issued. L2
Certificate
Level 3: The Declaration and the Primary Standard List are issued. L3
Level 4: The Declaration and the Yokogawa Measuring Instruments Control System are issued. L4
ATEX Certification ATEX Explosion proof
– KF21
See “HAZARDOUS AREA CLASSIFICATION”
FM Approval FM Explosion proof – FF1
See “HAZARDOUS AREA CLASSIFICATION”
CSA Certification CSA Explosion proof
– CF1
See “HAZARDOUS AREA CLASSIFICATION”
IECEx Certification IECEx Explosion proof
See “HAZARDOUS AREA CLASSIFICATION” – SF21
11-6 IM 01E20C02-01E
11. OUTLINE
Applicable Model
General- Explosion
Purpose proof Type
use
Item Specification Code
G
D
D
E
E
AXF***G-F
AXF***C-F
Flameproof packing Four flameproof packing adapters
– G14
adapter for TIIS
Flameproof Type
Three flameproof packing adapters and one blind plug.
– (*2) G13
Applicable only when a four-wires cable is used for power input and signal output.
*1: Select optional code G14 or G13 when TIIS Flameproof type with wiring using a flameproof packing adapter. Available only for JIS G1/2 female electric concections.
*2: In the case of fieldbus communication type, optional codes C1, C2, C3, EM and G13 are unable to select.
T06_02.EPS
11-7 IM 01E20C02-01E
11. OUTLINE
■ EXTERNAL DIMENSIONS
● Remote Converter AXFA14G, AXFA14C
Ground Terminal (M4) Unit: mm (approx. inch)
197(7.76)*1
28 103(4.06) 66(2.6)
(1.1) 31(1.22) 180(7.09)
ø128(5.04)
57(2.24) 49(1.92)
243.5(9.59)
139.5(5.49)
ø87(3.43)
55(2.17)
(approx. inch)
A
B
E
A
B
SA
SB
C
F
90(3.54)
90(3.54)
C
(5.91)
1505
1505
FLOW TUBE
CONVERTER
ø10.5(0.41)
L(SPECIFIED LENGTH)
20(0.79)
Model D E F G
AXFC AXFC-4 70(2.76) 25(0.98) 50(1.97) 60(2.36)
F07.EPS
AXFC-0-L
ø10.5(0.41)
CAP
AXFC
11-8 IM 01E20C02-01E
11. OUTLINE
● Flameproof packing adapter for TIIS Flameproof type (optional code G14 or G13)
T1
Unit : mm
Adapter body(M. Screw) (Approx. inch)
O-Ring
Packing case
16.5(0.65)
Hexagon socket set screw
Packing *
18(0.71) Hexagon socket set screw
O-Ring
C
F L O-Ring
G Washer
Union nut
Packing gland
*Packing D
Clamp ring
(Choose from the table below
depend on cable outside diameter) Clamp nut
T2 O-Ring
B.coupling
Cable(user's scope) F09.EPS
G 14: 4 units
● Unless otherwise specified, difference in the dimensions are refer to the following table.
General tolerance in the dimensional outline drawing.
Unit : mm (approx.inch)
Category of basic dimension Category of basic dimension
Tolerance Tolerance
Above Equal or below Above Equal or below
3 (0.12) 0.7 (0.03) 500 (19.69) 630 (24.80) 5.5 (0.22)
3 (0.12) 6 (0.24) 0.9 (0.04) 630 (24.80) 800 (31.50) 6.25 (0.25)
6 (0.24) 10 (0.39) 1.1 (0.04) 800 (31.50) 1000 (39.37) 7.0 (0.28)
10 (0.39) 18 (0.71) 1.35 (0.05) 1000 (39.37) 1250 (49.21) 8.25 (0.32)
18 (0.71) 30 (1.18) 1.65 (0.06) 1250 (49.21) 1600 (62.99) 9.75 (0.38)
30 (1.18) 50 (1.97) 1.95 (0.08) 1600 (62.99) 2000 (78.74) 11.5 (0.45)
50 (1.97) 80 (3.15) 2.3 (0.09) 2000 (78.74) 2500 (98.43) 14.0 (0.55)
80 (3.15) 120 (4.72) 2.7 (0.11) 2500 (98.43) 3150 (124.02) 16.5 (0.65)
120 (4.72) 180 (7.09) 3.15 (0.12)
180 (7.09) 250 (9.84) 3.6 (0.14)
250 (9.84) 315 (12.40) 4.05 (0.16)
315 (12.40) 400 (15.75) 4.45 (0.18)
400 (15.75) 500 (19.69) 4.85 (0.19)
Remarks: The numeric is based on criteria of tolerance class IT18 in JIS B 0401.
11-9 IM 01E20C02-01E
12. EXPLOSION PROTECTED TYPE INSTRUMENT
WARNING NOTE
• Magnetic flowmeters with the model name For ATEX explosion proof type specification,
AXFA14C are products which have been refer to IM 01E20A01-11EN.
certified as explosion proof type instruments.
Strict limitations are applied to the structures,
installation locations, external wiring work, 12.2 FM
maintenance and repairs, etc. of these instru-
(1) Technical Data
ments. Sufficient care must be taken, as any
Applicable Standard:
violation of the limitations may cause danger-
FM3600, FM3615, FM3810, ANSI/NEMA 250
ous situations.
Explosion proof for Class I, Division 1, Groups A,
Be sure to read this chapter before handling
B, C & D.
the instruments.
Dust-ignition proof for Class II/III, Division 1,
For explosion proof type instrument, the de-
Groups E, F & G.
scription in this chapter is prior to other descrip-
“SEAL ALL CONDUITS WITHIN 18 INCHES”
tion in this user's manual.
“WHEN INSTALLED IN DIV. 2, SEALS NOT
For ATEX or IECEx explosion proof type, be
REQUIRED”
sure to read IM 01E20A01-11EN.
For TIIS explosion proof type, be sure to read Maximum power supply voltage: 250 Vac/130 Vdc
“INSTALLATION AND OPERATING PRECAU- Excitation Circuit: 140V max
TIONS FOR TIIS FLAMEPROOF EQUIPMENT” Enclosure: NEMA 4X
at the end of this manual. Temperature Code: T6
Ambient Temp.: –40°C to +60°C (–40°F to +140°F)
(2) Electrical Connection
WARNING The type of electrical connection is stamped near the
electrical connection port accordiing to the following
The terminal box cover and display cover is locked codes.
by special screw. In case of opening the cover, Screw Size Marking
please use the hexagonal wrench attached. ISO M20x1.5 female M
ANSI 1/2NPT female N
The covers of explosion proof type products are
locked. Use the attached hexagonal wrench to
open and close the cover. Before opening the
cover, be sure to check that the power of
flowmeter has been turned off. Once the cover is
closed, be sure to re-lock the product.
F1204.EPS
Be sure to lock the cover with the special screw
using the hexagonal wrench attached after
tightening the cover.
12-1 IM 01E20C02-01E
12. EXPLOSION PROTECTED TYPE INSTRUMENT
(3) Installation
12.3 CSA
WARNING
(1) Technical Data
• All wiring shall comply with National Electrical Applicable Standard:
Code ANSI/NFPA 70 and Local Electrical For CSA C22.2 Series;
Code. C22.2 No 0, C22.2 No 0.4, C22.2 No 0.5,
• In hazardous locations, wiring to be in conduit C22.2 No 25, C22.2 No 30, C22.2 No 94,
as shown in Figure 12.2. C22.2 No.61010-1-12,
• When installed in Division 2, “SEALS NOT C22.2 No.61010-2-030-12
REQUIRED” For CSA E79 Series;
CAN/CSA-E79-0, CAN/CSA-E79-1,
Certificate: 1481213
HAZARDOUS LOCATIONS
Conduit Sealing Fitting For CSA C22.2 Series
Magnetic Flowmeter
Explosion proof for Class I, Division 1, Groups A,
B, C & D.
Dust-ignition proof for Class II/III, Division 1,
Groups E, F & G.
“SEAL ALL CONDUITS WITHIN 50 cm OF THE
18" (457 mm) Max. ENCLOSURE”
F1205.EPS
“WHEN INSTALLED IN DIV. 2, SEALS NOT
Figure 12.2 Conduit Wiring
REQUIRED”
(4) Operation
Maximum power supply voltage: 250 Vac/130 Vdc
Excitation Circuit: 140V max
WARNING
Enclosure: Type 4X
• “OPEN CIRCUIT BEFORE REMOVING COV- Temperature Code: T6
ERS.” Ambient Temp.: –40°C to +60°C (–40°F to +140°F)
• “SEAL ALL CONDUITS WITHIN 18 INCHES”
For CSA E79 Series
in hazardous locations.
• When installed in Division 2, “SEALS NOT Flameproof for Zone 1, Ex d IIC T6
REQUIRED” Maximum power supply voltage: 250 Vac/130 Vdc
• Take care not to generate mechanical spark Excitation Circuit: 140V max
when access to the instrument and peripheral Enclosure: IP66, IP67
devices in hazardous locations. Temperature Code: T6
Ambient Temp.: –40°C to +60°C (–40°F to +140°F)
(5) Maintenance and Repair
(2) Installation
12-2 IM 01E20C02-01E
12. EXPLOSION PROTECTED TYPE INSTRUMENT
12-3 IM 01E20C02-01E
12. EXPLOSION PROTECTED TYPE INSTRUMENT
Apply a non-hardening
(2) Wiring Installation sealant to the threads of these
fittings for waterproofing.
For the external wiring of flameproof types, use a
flameproof packing adapter approved by Yokogawa
(refer to Figure 12.4.2) or cable wiring using a flame- Wiring metal Apply a blanking
conduit plug to the unused
proof metal conduit (refer to Figure 12.4.4 and “IN- wiring port
STALLATION AND OPERATING PRECAUTIONS
FOR TIIS FLAMEPROOF EQUIPMENT” at the end Flameproof
Tee packing adapter
of this manual).
Flexible metal conduit
(2-1) Wiring Cable through Flameproof Pack-
ing Adapter Drain plug
F1211.EPS
12-4 IM 01E20C02-01E
12. EXPLOSION PROTECTED TYPE INSTRUMENT
lock nut.
(e) Insert the cable through the union cover, the union Hazardous
area Apply a blanking
coupling, the clamp nut, the clamp ring, the gland, plug to the unused
the washer, the rubber packing, and the packing Gas sealing wiring port
device
box, in that order. Flameproof flexible
Flameproof
(f) Insert the end of the cable into the terminal box. heavy-gauge metal conduit
(g) Tighten the union cover to grip the cable. When steel conduit
Seal fitting
tightening the union cover, tighten approximately Tee
After wiring, impregnate the
one turn past the point where the cable will no Drain plug fitting with a compound to seal tubing.
F1213.EPS
longer move up and down.
Proper tightening is important. If it is too tight, a Figure 12.4.4 Typical Wiring Using Flameproof Metal
circuit break in the cable may occur; if not tight Conduit
Wrench
Union cover
Lock nut
Packing box
F1212.EPS
12-5 IM 01E20C02-01E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT
To meet flameproof requirements, equipment that can be (4) Path length of joint surface
termed “flameproof” must: On a joint surface, the length of the shortest path through
(1) Be certified by a Japanese public authority in accordance which flame flows from the inside to outside of the flame-
with the Labour Safety and Health Laws of Japan and proof enclosure. This definition cannot be applied to threaded
have a certification label in an appropriate location on its joints.
case, and
(5) Gaps between joint surfaces
(2) Be used in compliance with the specifications marked on
its certification label, equipment nameplate and precau- The physical distance between two mating surfaces, or
tionary information furnished. differences in diameters if the mating surfaces are cylindrical.
2. Electrical Apparatus of Flame- Note: The permissible sizes of gaps between joint surfaces, the path
length of a joint surface and the number of joint threads are
proof Type of Explosion-Pro- determined by such factors as the enclosure’s internal
tected Construction volume, joint and mating surface construction, and the
explosion classification of the specified gases and vapours.
Electrical apparatus which is of flameproof construction is
subjected to a type test and certified by the Japanese Ministry
of Labour aiming at preventing explosion caused by electrical
apparatus in a factory or any location where inflammable
gases or vapours may be present. The flameproof construc-
1 EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT
2 EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT
6. Maintenance of Flameproof that the apparatus must always be restored to its original
Apparatus condition). If you attempt to repair the flameproof
apparatus, company-specified components shall be used.
To maintain the flameproof apparatus, do the following. (For (d) Before starting to service the apparatus, be sure to check
details, see Chapter 10 “MAINTENANCE OF EXPLOSION- all parts necessary for retaining the requirements for
PROTECTED ELECTRICAL INSTALLATION” in the flameproof apparatus. For this, check that all screws,
USER’S GUIDELINES for Electrical Installations for bolts, nuts, and threaded connections have properly been
Explosive Gas Atmospheres in General Industry.) tightened.
(1) Maintenance servicing with the power on. (3) Prohibition of specification changes and
modifications
Flameproof apparatus shall not be maintenance-serviced with
Do not attempt to change specifications or make modifica-
its power turned on. However, in cases where maintenance
tions involving addition of or changes in external wiring
servicing is to be conducted with the power turned on, with
connections.
the equipment cover removed, always use a gas detector to
check that there is no explosive gas in that location. If it
cannot be checked whether an explosive gas is present or not,
maintenance servicing shall be limited to the following two
items: 7. Selection of Cable Entry De-
vices for Flameproof Type
(a) Visual inspection
Visually inspect the flameproof apparatus, metal
conduits, and cables for damage or corrosion, and other CAUTION
mechanical and structural defects.
(b) Zero and span adjustments The cable glands (cable entry devices for flameproof
These adjustments should be made only to the extent type) conforming to IEC Standards are certified in
that they can be conducted from the outside without combination with the flameproof apparatus. So,
opening the equipment cover. In doing this, great care Yokogawa-specified cable entry devices for flameproof
must be taken not to cause mechanical sparks with tools. type shall be used to meet this demand.
(2) Repair
If the flameproof apparatus requires repair, turn off the power
References:
and transport it to a safety (non-hazardous) location. Observe
(1) Type Certificate Guide for Explosion-Protected Con-
the following points before attempting to repair the apparatus.
struction Electrical Machinery and Equipment (relating
(a) Make only such electrical and mechanical repairs as will to Technical Standards Conforming to International
restore the apparatus to its original condition. For the Standards), issued by the Technical Institution of
flameproof apparatus, the gaps and path lengths of joints Industrial Safety, Japan
and mating surfaces, and mechanical strength of (2) USER’S GUIDELINES for Electrical Installations for
enclosures are critical factors in explosion protection. Explosive Gas Atmospheres in General Industry (1994),
Exercise great care not to damage the joints or shock the issued by the Japanese Ministry of Labour, the Research
enclosure. Institute of Industrial Safet
(b) If any damage occurs in threads, joints or mating
surfaces, inspection windows, connections between the
transmitter and terminal box, shrouds or clamps, or
external wiring connections which are essential in
flameproofness, contact Yokogawa Electric Corporation.
CAUTION
3 EX-B03E
REVISION RECORD
Title: AXFA14G/C Magnetic Flowmeter Remote Converter
[Hardware Edition/Software Edition]
AXF Magnetic Flowmeter Integral Flowmeter [Software Edition]
Manual No.: IM 01E20C02-01E
6th Oct. 2005 6-3 to 6-7 6.3 Corrected the data range from "0.00001" to "0.0001".(B23, C42,
C49, F30 to F34)
Corrected the position of decimal point from "0 to 5" to "0 to 4".
(B23, B31, B33, C42, C46, C49, D11, E11, F30 to F34)"
"Corrected the position of decimal point from "0 to 5" to "0 to
2".(C32)
11-3 Added the "IECEx" to the hazardous area classification.
11-7 SF2 Added the "IECEx Certification (SF2)" to the optional specifications.
12-4 12.4 Added the "IECEx".
7th June 2006 1-1 Added the postscript about FOUNDATION Fieldbus protocol type.
4-4 4.4.2 Added the postscript about FOUNDATION Fieldbus protocol type.
4-7 4.4.6 (2) Added the “IECEx”.
4.4.7 Added the postscript about FOUNDATION Fieldbus protocol type.
4-7 Added the important note on pulse rate range of active pulse output.
5-1 Added the important note on “write protect”.
7-3 7.2.1 Added the important note on “write protect”.
8-1 Added the important note on “write protect”.
10-3 10.1.3 Added the postscript about FOUNDATION Fieldbus protocol type.
10-4 10.2.1 Added the postscript about FOUNDATION Fieldbus protocol type.
10.2.2 Added the postscript about FOUNDATION Fieldbus protocol type.
11-1,2 Added the postscript about FOUNDATION Fieldbus protocol type.
11-4 to 8 Added the postscript about FOUNDATION Fieldbus protocol type.
11-5 Added the “-F” (FOUNDATION Fieldbus protocol)
8th May 2007 1-2 (4) Changed the warning note of "Maintenance".
1-3 1.3 Added the IECEx to CAUTION.
1-5 1.4 Added the ATEX documentation.
4-3 4.3 Added the important note for the wiring ports.
4-5 4.4.4 Added the important note for a 24 V power supply version (power
supply code 2).
Corrected the graph of "Supply Voltage and Cable Length".
5-1 Changed the "SET", "SHIFT" and "" from character to figure.
5-3 5.2 Corrected the flow chart.
Changed the note of entry mode.
Added the NOTE for display unit setting.
5-4 to 5-6, 5-8, Added the NOTE for display unit setting.
5-9, 9-2, 9-4
6-30 to 6-31 J10, J11, J12 Added the sentence about indications action of display unit.
6-32 J31 Added the parameter setting table for "Power supply code 2".
8-2 8.1.2 Deleted the section of "Communication Line Requirements".
10-1 10.1 Changed the warning note and important note of "Maintenance".
10.1.1 Changed the caution note of "Fuse Replacement".
Deleted the Figure 10.1.1.
10-2 10.1.2 Changed the content of section "Display Unit Replacement" to
"Changing the Direction of the Display Unit".
10-3 10.1.3 Deleted the section "Display Unit Replacement" and section
"Amplifier Replacement".
10-4 10.2 Added the important note for "Setting of Switches".
11-1 Deleted the "Communication Distance" and "Cable length
for Specific Applications" from item of "HART".
Added the "Mounting" to item of "Mounting/Shapes".
11-3 Changed the certificate number of TIIS.
11-5 Corrected the graph of "Supply Voltage and Cable Length for
Power Supply Code 2".-
11-7 Added the note to optional codes C1, C2, C3, EM, and G13.
12-4 Added the "Excitation Circuit" to "IECEx Flameproof Type".
12-5 12.5(1) Changed the certificate number of TIIS.
IM 01E20C02-01E
Edition Date Page Revised Item
9th Jan. 2008 1-1 Added the postscript about PROFIBUS PA protocol type.
1-2 1.1 Added the warning note on "write protect".
4-4 4.4.2 Added the postscript about PROFIBUS PA protocol type.
4-7 4.4.7 Added the postscript about PROFIBUS PA protocol type.
5-1 5 Added the postscript about FOUNDATION Fieldbus protocol
type and PROFIBUS PA protocol type.
Added the warning note on "write protect".
6-1 6.1 Added the postscript about FOUNDATION Fieldbus protocol
type and PROFIBUS PA protocol type.
7-3 7.2.1 Added the warning note on "write protect".
Corrected the Figure 7.2.
8-1 8 Added the warning note on "write protect".
9-1 9 Added the postscript about FOUNDATION Fieldbus protocol
type and PROFIBUS PA protocol type.
9-3 9.1.2 Corrected the characters.
10-4 10.3.1 Changed the flow chart.
11-1 Added the postscript about PROFIBUS PA protocol type.
Corrected the frequency of "Input Impedance of Communicating Device".
11-4 Added the CAUTION to "EMC Conformity Standard".
11-5 Changed the unit of "Vibration Conditions" from "G" to "m/s2".
Added the "-G" (PROFIBUS PA protocol).
IM 01E20C02-01E
Edition Date Page Revised Item
IM 01E20C02-01E
Edition Date Page Revised Item
11th Sep. 2015 1-1 1. Added the NOTE for this manual.
1-2, 1-3 1.1 (1), (3), (4) Added the WARNING for installation, operation and maintenance.
1-3 1.1 (6) to (8) Added the WARNING and sentences.
1-4 1.3 Changed the IMPORTANT for combination remote flowtubes.
2-1 2.1 Changed the name plate.
4-1 4.1 Added the IMPORTANT for signal cable and excitation cable.
4-4 4.3 Changed the figure in Figure 4.3.1, Figure 4.3.4.
4-5 4.4.3 Changed the numbers of “IEC”.
4-7 4.4.7 Changed the load resistance value for BRAIN in Figure 4.4.7.
4-8 Changed the figure in Figure 4.4.9.
6-16 6.4 (2) Changed the name plate for C22.
6-18 6.4 (3) Changed the sentences and added the IMPORTANT for D20.
6-40 6.6 Changed the name plate.
7-3 7.2.1 Added the IMPORTANT for communication.
10-3 10.2.2 Changed the NOTE for write protect switch.
10.3 Added the CAUTION for maintenance of the LCD display.
11-3 Added the note for maximum power consumption.
Changed the values and the CAUTION for withstand voltage.
11-4 Added applied “EN” standard in Safety Requirement Standards.
Added the performance specification in EMC Conformity Standards.
Deleted the logos.
11-5 Changed the table for model and suffix code.
11-6 to 11-7 Deleted the note for optional code.
11-9 Changed the table of flameproof packing adapter for TIIS certification.
12-3 12.2 (2) Added the figure for FM certification.
12-4 12.3 (1) Changed applied “Applicable Standard” for CSA certification.
12-7 12.5 (2) Changed the table of flameproof packing adapter for TIIS certification.
Changed the figure in Figure 12.4.2.
12-8 Changed the figure in Figure 12.4.4.
12-1 to 12-3 12.1 Added and changed the sentences, notes and figure for ATEX certification.
12-5 to 12-6 12.4 Added and changed the sentences, notes and figure for IECEx certification.
12th May 2016 1-3 1.1 (5) Added the sentences for explosion proof type.
1-4 1.4 Deleted the ATEX Documentation.
8-1 8. Corrected the trademarks.
10-4 to 10-6 10.4 Changed the flow chart for troubleshooting.
11-1 11. Corrected the sentences for HART and Protection.
11-4 Added the sentence for CE marking.
11-5 Corrected the table for AXFC signal cable.
11-7 Corrected the sentence for optional code G13.
12-1 12. Adde the sentences for explosion proof type.
12.1 Deleted the sentences for ATEX explosion proof type.
Added the NOTE for ATEX explosion proof type.
12-3 12.4 Deleted the sentences for IECEx explosion proof type.
Added the NOTE for IECEx explosion proof type.
IM 01E20C02-01E