This document provides a specifications table for the NOVA series of three-phase online UPS models ranging from 10kVA to 40kVA nominal power. The table lists technical details like input voltages and frequencies, output power factors and voltages, battery specifications, efficiencies, protections, operating conditions and mechanical dimensions for each UPS model.
This document provides a specifications table for the NOVA series of three-phase online UPS models ranging from 10kVA to 40kVA nominal power. The table lists technical details like input voltages and frequencies, output power factors and voltages, battery specifications, efficiencies, protections, operating conditions and mechanical dimensions for each UPS model.
This document provides a specifications table for the NOVA series of three-phase online UPS models ranging from 10kVA to 40kVA nominal power. The table lists technical details like input voltages and frequencies, output power factors and voltages, battery specifications, efficiencies, protections, operating conditions and mechanical dimensions for each UPS model.
Nominal Power 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA Active Power 10 kW 15 kW 18 kW 27 kW 36 kW MAIN INPUT Grid system 3 Phases + Neutral + Ground Rated voltage / Frequency 380/400/415VAC (Phase-Phase), 50/60Hz 304~478Vac (Phase-Phase), full load; Voltage range 228V~304Vac (Phase-Phase), load decreases linearly according to the min phase voltage Frequency range 40~70 Hz Power factor >0.99 Current THDi <4% (full Linear Load) <3% (full Linear Load) BYPASS INPUT Grid system 3 Phases + Neutral + Ground Rated voltage / Frequency 380/400/415VAC (Phase-Phase), 50/60Hz Default: -20% ~ +15% Voltage range Selectable: -40% ~ +25% Frequency range Selectable, ±1Hz, ±3Hz, ±5Hz ±2Hz 125% Long term operation; Bypass overload 125%~130% for 10min; 130%~150% for 1min; OUTPUT Rated voltage / Frequency 380/400/415VAC (Line-Line), 50/60Hz Power factor 1 0,9 <1% (linear load); <1% linear load; Voltage THDv <5.5% (non-linear load) according to IEC/EN62040-3 <6% (non-linear load) according to IEC/EN62040-3 Voltage precision ±1.5%(0-100% linear load) Transient response <5% for step load (20% - 80% -20%) Transient recovery < 30ms for step load (20% - 100% -20%) <110%, 60min; Inverter overload 110%~125%,10min; 125%~150%,1min; Frequency regulation 50/60Hz ±0.1% Synchronized range Settable, ±0.5Hz ~ ±5Hz Synchronized slew rate Settable, 0.5Hz/S ~ 3Hz/s Crest Factor 3:1 BATTERIES Battery rate voltage ±240 VDC Charger voltage precision 1% Batteries arrangement Internal or external Battery type Pb SYSTEM Efficiency Normal Operation 95% >95% >96% Efficiency Battery Operation 94.5% >95% >96% Display LED + LCD standard Protection degree IP20 ENVIRONMENT Operating temperature 0 ~ 40 °C Storage temperature -40 ~ 70 °C Relative humidity 0 ~ 95% (Non condensing) Noise (dBA at 1 meter far) 58dB @ 100% load, 52dB @ 45% load 65dB @ 100% load, 62dB @ 45% load Altitude >1000m; load derated 1% per 100m from 1000 ~ 2000m MECHANICAL DATA Cabinet dimensions W*D*H (mm) 380x840x1400 mm 500x965x1400 mm Cabinet weight (Kg) 100 kg 140 kg Color Black, RAL 7021
Note: technical specifications and data could be changed without notification