2 Separators for downstream critical services in Refineries/ Gas Processing & Petrochemical Plants
(i) High level alarm and High-High level interlock on separator (e.g. suction KOD of compressor etc.) to cut-
off the compressor for preventing liquid ingress into it
(ii) Low level alarms for hydrocarbon (HC) level & water interphase level. In cases, where the downstream
equipment is not equipped to handle gas breakthrough resulting from
loss of liquid level, provision of Shut off valve should be made on the HC liquid outlet and water outlet
and to be configured on Low-Low level.
(iii) Two independent level tapings & transmitters, in case of congealing fluid or dirty service like sour
water.
(i) Column bottom level shall be monitored by two different smart level instruments with separate
tappings.
(iii)The column top temperature shall be monitored through minimum two temperature points -- one for
control and another for indication with alarms on high & low temperature.
(v) Pressure indications for fractionating column top and flash zone.
In the following cases, automatic shut down valve should be provided at the column
bottom outlet for column isolation at low low bottom level to avoid gas passing to the
downstream systems:
(i) Where column bottom operating temperature is above auto ignition temperature.
(ii) Where column would need immediate isolation in case of any incident of fire below the column.
(iii) Where downstream facility viz. Storage tank has not been designed to handle gas released from the
column bottom.