Power Cables Megger QC-115

CONTRACT# CLIENT / PROJECT SYSTEM

JOB# CWP

CLIENT REF:
Mark “N/A” where Not Applicable
NSULATION RESISTANCE / CONTINUITY TEST Test Equipment Log#:
Megger Tested By
From To Continuity
No. Type Rated Test Test
Cable Tag Size From Check To Check Test
Cond. (Teck, TC etc.) Volts *1 *1 (Pass/Fail) Volts Result Initial Date
*2 *3

*1. Verify at source & destination ends: All conductor and ground connections are completed and tight, Cable Tags are installed, Phasing tape, Cable support, Lighting & Recept circuits are identified.
*2. Insulation Test Optional for Lighting and Receptacles Cables.
*3. Test performed with other phases jumpered to ground. Test duration - 1 minute.
Test Voltage for Insulation Tests (unless specified otherwise by Project Specifications):
Cable Insulation Rating (Volts) Test Voltage (DC) Cable Insulation Rating (Volts) Test Voltage (DC)
120 – 300 500 601 – 2400 2500
301 – 600 1000 Greater than 2400 V 5000

TESTED BY: CHEMCO QC OTHER CLIENT


NAME: NAME: NAME: NAME:
SIGNATURE: SIGNATURE: SIGNATURE: SIGNATURE:
DATE: DATE: DATE: DATE:
Revision 0 July 29, 2004 QC-115 R0 Power Cables Megger.doc Page 1 of 1