Check For Corona of The Conductor (3 Phase, Bundle Conductor, Based On Ieee 6905)
Check For Corona of The Conductor (3 Phase, Bundle Conductor, Based On Ieee 6905)
Where,
E0 = Empirical constant = 21.1 kV/cm
C = Empirical constant = 0.301 cm-1
m = The conductor irregularity factor = 0.85
rc = Conductor outside radius = 1.92 cm
T0 = Common basis of temperature = 250 C
T = The temperature of ambient air = 400 C
Da = The relative air density
273+T 0 P 273+T 0 A
=( 273+T ) P 0 =( 273+T ) (1- 10 )
= 0.9378
Average voltage gradient at the surface of 3 phase bundle conductor
V1
Ea = nrln 2 he = 5.64 kV/cm (eqn. D.12 IEEE 605-2008)
ℜ
= 6.2 cm
= 5.88 kV/cm
= 6.2 cm
he = the equivalent distance from center of conductor to ground plane for three
phases
hD
= (eqn. D.8. IEEE 605-2008)
√ 4 h 2+ D 2
= 148.84 cm
h= the conductor center distance from ground = 1200 cm
D = the phase to phase spacing for three phases = 300 cm
Conclusion: Maximum voltage gradient (Em) is lower than corona onset gradient
(Ec)
Em: 5.88 kV/cm (rms) < Ec: 20.59 kV/cm (rms)