Amps X 100 H-520-PDC-001 (Nom. KV 10, Plot Ref. KV 10) : H-520-RP-012 - P OC1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Amps X 100 H-520-PDC-001 (Nom. kV=10, Plot Ref.

kV=10)
.5 1 5 10 50 100 500 1K 5K 10K
1K 1K
H-520-PDC-001
H-520-RP-010 - P H-520-RP-006 - P
ABB ABB BARRA LLEGADA 138 KV

500 H-510-XF-001 REF 543 500


REF 543
H-510-DS-001 H-510-RP-001

FLA - ONAF 65 CT Ratio 1500:5


o

OCR

H-520-RP-012 - P CT Ratio 600:5 H-510-CB-001

OC1 OC1
OC1
Very Inverse Very Inverse H-510-XF-001

ABB 26.6 MVA

Pickup = 1 (0.1 - 5 xCT Sec) Pickup = 1.1 (0.05 - 40 xCT Sec)


REF 543
Time Dial = 1 Time Dial = 0.4
CT Ratio 400:5
3x = 2.7 s, 5x = 1.35 s, 8x = 0.771 s
Tripolar Line 1

Extremely Inverse 3x = 6.75 s, 5x = 3.38 s, 8x = 1.93 s 2-3/C 500


2-3/C 500

Inst = 6.7 (0.1 - 40 xCT Sec) Inst = 7 (0.1 - 40 xCT Sec)


Pickup = 1 (0.1 - 5 xCT Sec)
100 Time Delay = 0.05 s Time Delay = 0.05 s 100
Time Dial = 0.8 H-520-RP-006

3x = 8 s, 5x = 2.67 s, 8x = 1.02 s OC2 OC2 o


H-520-CB-006

Inst = 11 (0.05 - 40 xCT Sec)


OCR

Inst = 15 (0.1 - 40 xCT Sec) Inst = 10 (0.1 - 40 xCT Sec)


50 Time Delay = 0.05 s Time Delay = 0.05 s Time Delay = 0.2 s 50 H-520-PDC-001

H-520-CB-017

H-520-CB-005

H-520-CB-010
H-510-RP-001 - P

H-520-CB-007
H-520-CB-002

H-520-CB-011

H-520-CB-012
H-520-RP-005 - P
OC1

H-520-CB-001

H-520-RP-010
ABB
ABB
o
o o
o

OCR

H-520-RP-005
H-520-RP-017
REF 543
OCR OCR

H-520-RP-002
OCR

H-520-RP-001
o

REF 543
o

H-520-RP-012
o

CT Ratio 600:5

H-520-RP-007
OCR
o OCR

H-520-RP-011-T-W2
o
OCR

CT Ratio 150:5
R
o

OC1
Very Inverse
Very Inverse
Pickup = 0.85 (0.05 - 40 xCT Sec)
10 Pickup = 1.1 (0.05 - 40 xCT Sec) 10
Time Dial = 0.5
Time Dial = 0.66
3x = 3.38 s, 5x = 1.69 s, 8x = 0.964 s
3x = 4.46 s, 5x = 2.23 s, 8x = 1.27 s
Inst = 12 (0.1 - 40 xCT Sec)
Inst = 6 (0.05 - 40 xCT Sec)
5 Time Delay = 0.05 s 5
Time Delay = 0.5 s
OC2
H-520-RP-011-T-W2 - P
Inst = 9.5 (0.05 - 40 xCT Sec) OC1
Time Delay = 0.05 s
ABB
RET 543
CT Ratio 600:5

Seconds
Seconds

Extremely Inverse
1 H-520-RP-017 - P Pickup = 1.01 (0.05 - 40 xCT Sec) 1
OC1 Time Dial = 0.3
3x = 3 s, 5x = 1 s, 8x = 0.381 s
ABB
Inst = 13.64 (0.05 - 40 xCT Sec)
.5 REF 543 .5
Time Delay = 0.05 s
CT Ratio 600:5
Extremely Inverse
Pickup = 0.5 (0.1 - 5 xCT Sec)
Time Dial = 0.5
3x = 5 s, 5x = 1.67 s, 8x = 0.635 s H-510-XF-001
Inst = 6.95 (0.05 - 40 xCT Sec) H-510-XF-001
Time Delay = 0.05 s Inrush
BARRA LLEGADA 138 KV - Source PD Ia
.1 H-520-RP-002 - P 8.212kA @ 138kV .1
ABB
REF 543 H-520-RP-006 - 3P
CT Ratio 100:5 21.307kA @ 10.138kV H-510-RP-001 - 3P
.05 OC1 (Sym) .05
H-520-RP-001 - P 8.012kA @ 138kV
Very Inverse H-520-RP-010 - 3P
(Sym)
Pickup = 1.2 (0.1 - 5 xCT Sec) ABB 21.307kA @ 10.138kV
Time Dial = 0.7 REF 543 (Sym)
3x = 4.73 s, 5x = 2.36 s, 8x = 1.35 s CT Ratio 100:5 H-520-RP-011-T-W2 - 3P
Inst = 7.5 (0.05 - 40 xCT Sec) OC1 H-520-RP-012 - 3P 30.843kA @ 10.138kV
Time Delay = 0.2 s Extremely Inverse 21.307kA @ 10.138kV (Asym)
OC2 Pickup = 1.05 (0.05 - 40 xCT Sec) (Sym)
.01 Inst = 16.05 (0.05 - 40 xCT Sec) Time Dial = 1 .01
H-520-RP-005 - 3P
Time Delay = 0.05 s 3x = 10 s, 5x = 3.33 s, 8x = 1.27 s H-520-RP-017 - 3P
21.307kA @ 10.138kV
Inst = 3.5 (0.1 - 40 xCT Sec) 21.307kA @ 10.138kV
(Sym)
.005 Time Delay = 0.5 s (Sym) .005
OC2 H-520-RP-002 - 3P
Inst = 9.5 (0.1 - 40 xCT Sec) 21.307kA @ 10.138kV
Time Delay = 0.05 s (Sym)

H-520-RP-001 - 3P
H-520-PDC-001 - Source PD Ia
21.307kA @ 10.138kV
0.622kA @ 10.138kV (Sym)
.001 .001
.5 1 5 10 50 100 500 1K 5K 10K

Amps X 100 H-520-PDC-001 (Nom. kV=10, Plot Ref. kV=10)


120.2 500 1K 5K 10K 50K 100K 500K 1000K 2404K

Amps (Plot Ref. kV=4.16) ETAP Star 16.0.0C

Actual coord. PDC1

Project: Est. de Op. Conc. C1 e Hidro. Date: 26-12-2017


Location: Arequipa-Perú Rev: Base
Engineer: CELICON INGENIEROS SAC Fault: Phase

You might also like