Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

Copyright ABB AS. All rights reserved.

REUSE PG Design Description

KS Function Block

Resp.
Doc. kind Design Description Project Q000083 ATPA/AKU
dept.

Title REUSE KS PG Design Description REUSE Approved


Document identity Lang. Rev. ind. Sheet 1

ABB AS Q000083-SW-8PG-0030 en B No. of sh. 17


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 2 (17)


Contents
1. Introduction.............................................................................................................. 3
1.1 Definitions and Abbreviations ....................................................................... 3
1.2 Standards..................................................................................................... 3
1.3 Alarm Colors ................................................................................................ 3
1.4 Sets of Color Palettes................................................................................... 3
1.5 Text Configuration ........................................................................................ 4
2. PG Presentation ....................................................................................................... 5
2.1 Faceplate ..................................................................................................... 5
2.1.1 Conditions Tab ............................................................................................. 5
2.1.2 Action Tab.................................................................................................... 7
2.1.3 Conditions and Actions Tab.......................................................................... 9
2.2 Graphic Element Index............................................................................... 10
2.3 Graphic Elements....................................................................................... 11
2.3.1 reKSPG021 ................................................................................................ 11
2.3.2 reKSPG022 ................................................................................................ 12
2.3.3 reKSPG023 ................................................................................................ 13
2.3.4 reKSPG024 ................................................................................................ 14
3. References ............................................................................................................. 16
4. Revision.................................................................................................................. 17

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 3 (17)

1. Introduction
KS – Control of Sequence

The function block is for control and supervision of sequences. KS also includes HSI control from
operator stations, as well as indications and alarms.

The KS Function Block is described in detail in the REUSE KS Function Block Detail Description
ref. /1/.

It is assumed that the user has read the REUSE AC800M Libraries Overview, ref. /3/, for the
common details for HMI parts. The Graphics is implemented according to REUSE Library
Programming Guidelines, see ref. /4/. The Colors for the Graphics is described in REUSE
Libraries Colors Overview, see ref. /5/.

1.1 Definitions and Abbreviations

Abbreviation: Description:
Disabled Alarm Alarm hidden, suppressed or deactivated by PDAxx<>2
HMI Human Machine Interface
PG Process Graphics
PGE Process Graphics Editor
FP Faceplate
OPC OLE for Processing Control
PCS Process Control System
PSD Process Shutdown
SAS Safety and Automation System
Table 1.1 Abbreviations

1.2 Standards
See REUSE AC800M Libraries Overview ref. /3/ for details about the supported Standards.

1.3 Alarm Colors


The Graphic Elements and the Faceplate support both Alarm Colors based on Priority (EEMUA-
191 / YA-711) and alarm colors based on Category (NORSOK-SAS). This is configurable and
can be selected by the user. Each label and symbol in this document marked with “Priority or
Category Based Color” shows the Alarm colors according to the selected Color base. See
REUSE AC800M Libraries Overview ref. /3/ for more details.

1.4 Sets of Color Palettes


REUSE supports 2 sets of color palettes; Default and Traditional colors. This document shows
both these 2 options, see ref. /5/ for more details.

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 4 (17)


1.5 Text Configuration

All texts for the Sequence that are presented in the Faceplate are read from a General Property
aspect called ‘Sequence Texts’. This aspect is created by the Sequence programmer. The texts
are loaded from the aspect when the Faceplate is opened.

The Aspect in Fig. 1.5 shows how the Sequence texts should be named and structured.

Figure 1.5 Sequence Texts aspect

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 5 (17)

2. PG Presentation

2.1 Faceplate

2.1.1 Conditions Tab

4. Step no./
Step name
1. Status

3. Conditions
2. Operate

Figure 2.1.1 Conditions Tab

Presentation
Item Title Description
Eng. Nor. General
1 Status
Black Disabled from Parameter
/ / Warning (Deviation)
Priority or Category Based Color
/ / Manual / Auto mode
Not Available indication

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 6 (17)

Presentation
Item Title Description
Eng. Nor. General
2 Operate
Manual / Auto mode Button
/ /
Push Button Go to Next Step
Push Button Start Sequence
Push Button Confirmation to go to Next Step
Push Button Reset Sequence & go to first Step
3 Conditions
Process Status indication
Text Process Status Text
Value Process Value
4 Step number/Step
name
Value Sequence Step number
Text Sequence Step name

Table2.1.1 Conditions Tab

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 7 (17)


2.1.2 Action Tab

4. Step no./Step
name
1. Status

3. Conditions

2. Operate

Figure 2.1.2 Action Tab

Presentation
Item Title Description
Eng. Nor. General
1 Status
Black Disabled from Parameter
/ / Warning (Deviation)
Priority or Category Based Color
/ / Manual / Auto mode
Not Available indication
2 Operate
Manual / Auto mode Button
/ /
Push Button Go to Next Step
Push Button Start Sequence
Push Button Confirmation to go to Next Step
Push Button Reset Sequence & go to first Step

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 8 (17)

Presentation
Item Title Description
Eng. Nor. General
3 Conditions
Action Status indication
Text Action Status Text
4 Step number/Step
name
Value Sequence Step number
Text Sequence Step name

Table2.1.2 Action Tab

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 9 (17)


2.1.3 Conditions and Actions Tab

Figure 2.1.3 Conditions and Actions Tab

Presentation
Item Title Description
Eng. Nor. General
1 Conditions and
Actions
Refer Section 2.1.1 for Conditions
Refer Section 2.1.2 for Actions

Table2.1.3 Conditions and Actions Tab

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 10 (17)


2.2 Graphic Element Index

Graphic Descriptio Symbols HMI


Element n relati
on
reKSPG021 Sequence PCS
presentation
symbol

reKSPG022 Sequence PCS


presentation
symbol, step
number and
name
included.

reKSPG023 Sequence PCS


presentation
symbol, step
number,
name and
description
included.

reKSPG024 Sequence PCS


presentation
symbol. Step
number, next
step,
conditions,
actions,
alarm text,
name and
description
included.

Table 2.2 Graphic Element Index

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 11 (17)


2.3 Graphic Elements

3.Status Square/
2.3.1 reKSPG021 Step Indicator

2.Alarm

1.Mode

Figure 2.3.1 KSPG021

Presentation
Item Title Description
Eng. Nor. General
1 Modus
“M” for Manual modus
“A” for Auto modus
2 Alarm
/ / Warning Alarm
Priority or Category Based Color
Otherwise invisible
3 Status Square /
Step Indicator
Step Number = 0

Unfilled
Step Number > 0

Filled
When Sequence Not available
and Step number is 0
Unfilled
When Sequence Not available
and Step number >0
Filled
Table 2.3.1 KSPG021

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 12 (17)


2.3.2 reKSPG022

2. Alarm 3.Mode 4.Step number and Name

1. Status square

Figure 2.3.2 KSPG022

Presentation
Item Title Description
Eng. Nor. General
1 Status square
Step Number = 0
Unfilled
Step Number > 0
Filled
When Sequence Not available
Black(X) and Step number is 0
When Sequence Not available
Filled and Step number >0
Black(X)
2 Alarm
/ / Warning Alarm
Priority or Category Based Color
Otherwise invisible
3 Modus
“M” for Manual modus
“A” for Auto modus
4 Step number and
Name
Grey Shows the Step number and
Name of the Step
Table 2.3.2 KSPG022

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 13 (17)


2.3.3 reKSPG023

3.Mode 4.Description

2. Alarm

1. Status Square 5.Step number and name

Figure 2.3.3 KSPG023

Presentation
Item Title Description
Eng. Nor. General
1 Status square
Step Number = 0
Unfilled
Step Number > 0
Filled
When Sequence Not available
Black(X) and Step number is 0
When Sequence Not available
Filled and Step number >0
Black(X)
2 Alarm
/ / Warning Alarm
Priority or Category Based Color
Otherwise invisible
3 Modus
“M” for Manual modus
“A” for Auto modus
4 Description
Black Sequence description
5 Step number and
Name
Grey Shows the Step number and
Name of the Step
Table 2.3.3 KSPG023

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 14 (17)


2.3.4 reKSPG024

1.Name/
Description
2. Alarm 9.Modus

3.Status Square 8.Alarm Text

4.Action Description

7.Step number & name


5. Condition Description

6. Next Step Number

Figure 2.3.4 KSPG024

Presentation
Item Title Description
Eng. Nor. General
1 Name/
Description
Black Sequence Name and Sequence
Description
2 Alarm
/ / Warning Alarm
Priority or Category Based Color
Otherwise invisible
3 Status Square
Step Number = 0

Unfilled
Step Number > 0

Filled
When Sequence Not available
and Step number is 0
Black(X)
When Sequence Not available
and Step number >0
Filled
Black(X)
4 Action
Description
Action Black Action description for current
Step step
(visible if configured). The first
action in faceplate which has the
Action Status to false will be
listed.

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 15 (17)

Presentation
Item Title Description
Eng. Nor. General
5 Condition
Description
Condition Black Condition description for current
Text step (visible if configured). The
first condition in faceplate which
has the Condition State to false
will be listed.
6 Next Step
number
Next Step Number and
escription. The next step has to
be given by the NextStepNo
parameter in Function Block. Not
visible if NextStepNo=-1
7 Step number,
Description
Grey Current step Number and
Description
8 Alarm Text
Black Alarm Description
9 Modus
“M” for Manual modus
“A” for Auto modus
Table 2.3.4 KSPG024

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 16 (17)

3. References

Reference Document Title Document Number


/1/ REUSE KS FB Design Description Q000083-SW-8FB-0030

/2/ REUSE Large screen Solution Q000083-SW-LS-0001

/3/ REUSE AC800M Libraries Overview Q000083-SW-OV-0002

/4/ REUSE Library Programming Guidelines Q000083-SW-GL-0001

/5/ REUSE Libraries Colors Overview Q000083-SW-OV-0004

Table 3.1 References

Oil, Gas & Petrochemicals OGP REUSE Solutions


REUSE KS PG Design Description Q000083-SW-8PG-0030

Issued by department Date Language Rev Page

ATPA/AKU 2010-07-09 en B 17 (17)

4. Revision
The revision handling is described in detail in document Q000083-SW-GL-0004.

Rev. ind. Chapter Description Date/Init.


-d1 All Created for REUSE solutions 2009-03-19/AD
- All Approved 2009-03-25/TSN
Ad1 All Added Faceplate 2009-04-01/AD
A All Approved 2009-07-01/EL
Bd1 2 Corrected the names of all PG elements 2010-03-11/EL
Bd2 1.5 Added ‘Text Configuration’ 2010-03-18/SJ
B All Small adjustments. Ready for Approval. 2010-07-09 /EL
QE: Erik Lundmark
Table 4.1 – Revision