A New HEPA Solution For GT Inlet Air Filtration: Tom Kelmartin, PE W.L. Gore & Associates, Inc
A New HEPA Solution For GT Inlet Air Filtration: Tom Kelmartin, PE W.L. Gore & Associates, Inc
Air Filtration
Tom Kelmartin, PE
W.L. Gore & Associates, Inc.
June 18, 2013
tkelmart@wlgore.com
1
Agenda
• The Problem
• What is HEPA Filtration?
• Gore’s HEPA Technical Approach
• Case Studies
5
Sub-Micron Distribution in Urban Air
Particle Distribution (urban)
0.7
0.6
Particle
Number 0.5
(normalized)
0.4
Visible particle = 40µ
0.3
0.2
0.1
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
0.9
0.8
EN779
0.7
0.6
Particle
Number (normalized)
0.5
ASHRAE 52.2
0.4
0.3
0.2
0.1
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Particle Size [µm]
0.9
0.8
EN779
0.7
0.6
Particle
Number (normalized)
0.5
ASHRAE 52.2
0.4
0.3
0.2
0.1 EN1822
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Particle Size [µm]
MPPS*
0.9 90
0.8
MERV15/F9 80
0.7 70
0.6 60
Particle
Nanofibers / Synthetic Particle
0.5 50 Capture
Number (normalized)
Efficiency [%]
0.4
Nanofibers / Cellulose 40
0.2
Cellulose 20
0.1 10
0 0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
X= 0.09 lb/yr
Filter Grade
90 9.00
80 8.00
Inlet Temp °F
70 7.00
60 6.00
Eff%, DegF, Pwr MW
η comp
MW Predicted
DP Inch H2O
50 Predicted MW 5.00 MW Actual
T-Inlet
DP Inlet
40 4.00
30 3.00
Actual MW Inlet Filter DP
20 2.00
10 1.00
0 0.00
7/10/12 12:00 8/29/12 12:00 10/18/12 12/7/12 12:00 1/26/13 12:00 3/17/13 12:00 5/6/13 12:00 6/25/13 12:00
AM AM 12:00 AM AM AM AM AM AM
G2 Change
G2 Change
G2 Change Prefilter and G2 Total DP
G2 Change
Change
MERV12 Prefilter
G2 Change
+G2 Wrap
G2 Wrap
V-Panel
Continuing Ops
2 Years
Total DP
V-Panel
Prefilter + G2
G2
GT Upgrade
100 5
Filter Eff
Comp Approaching End of Service Lifetime
90 4.5
80 4
70 3.5
DP Inch WG
Comp Eff %
40 2
30 1.5
20 DP 1
10 0.5
0 0
8/10/2010 2/26/2011 9/14/2011 4/1/2012 10/18/201 5/6/2013 11/22/201
0:00 0:00 0:00 0:00 2 0:00 0:00 3 0:00
A-Train Raw MW
8,000+ hrs
No Wash Frame 6B
Compressor Efficiency
Power Load
Temperature
34.4 MW (GORE)
31.0 MW (F8)
Power Load 3.4 MW Gain
Compressor Efficiency
90.2% (GORE)
87.6% (F8)
2.6% Gain
1800
1600 $80/MWHr
1400
1200 $60/MWHr
$1,000's
1000
800 $40/MWHr
600
400 $20/MWHr
200
0
0 1 2 3 4 5
MW Lost Between Washes
1800
1600 $80/MWHr
1400
1200 $60/MWHr
$1,000's
1000
800 $40/MWHr
600
400 $20/MWHr
200
0
0 1 2 3 4 5
MW Lost Between Washes
For Example: 3MW loss at $40/MWHr replacement cost = $480,000 annual cost
Compressor Fouling:
Simple retrofit
• Similar initial pressure drop
• Similar filter life
• JC Rawls
• Mike Wenschlag