Flow control

D
POSITIONER Angle-seat valves E 290 with

POSITIONERD
Pressure-operated series 290 or 390 2- or 3-way valves combined with a Positioner D offer a simple and cost-
effective solution for flow control.
This type of valve can be used in the most different processes. With the right body material, the valve are suit-
able for use with gases and neutral or aggressive liquids.
For installations where space is limited, the Positioner D, which is directly mounted onto the valve, is a simple
and cost-effective solution. The optionally available double-loop (cascaded) control feature enables direct con-
trol of pressure, flow, temperature etc. A frequency signal input allows using low-cost turbine flow sensors to
control the flow of liquids.
The valve can be adjusted to a specific application using the PosCom software.

Pressure supply
over the P ositioner D

Outlet Fluid entry under the disc,


no waterhammer

Profiled disc

34
D
O P E R A T I N G P R I N C I P L E

POSITIONER
1
The position of the disc is adjust-
t
ed over two pulsed solenoid
er
So
llw
valves which apply pressure to
3 rt
or exhaust pressure from the
we
Ist
control cylinder.
2

Closed
The disc is pressed down by
spring force to block the flow
between port 2 and port 1.
The PosCom software and the RS232 interface
allow the controller to be optimally adjusted to
the control loop. 1 2
For more information, see page 14.
1
Control position
er
t The parabolic shape of the disc
llw
So
ensures a Kv which is propor-
we
rt tional to the valve opening.
3 Ist

1 2

1
Open
er
t The disc is lifted to release the
llw
So
flow between port 2 and port 1.
rt
we
Ist
3
2
Flow

1 2
Control signal

More information on
T E C H N I C A L C H A R A C T E R I S T I C S P ositioner D Page 79

Fluids: Vacuum, air, gases, liquids Features: ■ Digital control


and steam ■ Two power loss options available:
Pressure range: 0 to 16 bar - Pressure held
Ports: G 1/2 to G2 1/2 - Pressure released
Flow: Kv 4,6 to Kv 74 (m3 /h) ■ Minimum hysteresis
Construction: Profiled disc (2/2) or ■ Compact design
standard flat disc (3/2)) ■ Easy operation
Antrieb: Pulsed 2/2-way valves ■ Standard 25 µm filtration
Setpoint: 0 - 10 V, ■ Cost effective
4 - 20 mA
■ Double-loop (cascaded) control (option)
■ LED position display