1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING W/ PROPOSED ADDITIONAL FLOOR
H.V. dela Costa St., Client: PLDT
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: - Date: 07/27/20 Date:
FOOTING F1 DETAIL
ORIGINAL DESIGN
L = 1600 m (Length)
W = 1600 m (Width)
t = 400 mm (Thickness)
Øm = 16 mm (Diameter of Rebars)
nL = 10 pcs (No. of Rebars along Length)
nW = 10 pcs (No. of Rebars along Width)
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING W/ PROPOSED ADDITIONAL FLOOR
H.V. dela Costa St., Client: PLDT
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: - Date: 07/27/20 Date:
Safety Factor
for the
Options Loads Original Size design to be
REMARKS SETTLEMENT CHECK
adequate
CONCLUSION
Safety Factor
for the
Options Loads Original Size design to be
REMARKS SETTLEMENT CHECK
adequate
CONCLUSION
Safety Factor
for the
Options Loads Original Size design to be
REMARKS SETTLEMENT CHECK
adequate
CONCLUSION
Material Properties:
f'c = Specified compressive strength of concrete, Mpa
fy = Specified yield strength of non-prestressed reinforcement, Mpa
λ = Shear Modification Factor for Light Weight Concrete
Soil Properties:
SBCA = Soil Bearing Capacity on laboratory test results
SF = Safety Factor
SBC = Soil Bearing Capacity to be use on Design
Column Dimension:
X = Column Dimension along Length of Footing
Y = Column Dimension along Width of Footing
Loc = Center
}
Location
Edge of Column
Corner
Footing Parameters:
Øm = Rebar Diameter to be Use
L = Length (Longer Dimension of Footing)
W = Width (Shorter Dimension of Footing)
t = Thickness of Footing
nL = quantity of rebar along side "L"
nW = quantity of rebar along side "W"
NSCP REQUIREMENTS
ρ = Reliability/Redundancy Factor, NSCP 208-3
Ca = Seismic Coefficient, NSCP table 208.7
I = Importance Factor, NSCP table 208.1
DESIGN SYMBOLS
Areqd = Area Required dX = Effective Depth along specified Side
Aprov = Area Provided fs = Elastic Steel Stress
a = Area of Punching Failure L' = Distance of Footing End to Column @ L
A = Area of Footing Mn = Nominal Moment Capacity
AsX = Area of Rebars along specified Side Mu = Ultimate Moment to be Resist
Ag = Concrete Area perpendicular to Rebar PS = Maximum Service Load Combination
αs = Column Location Factor PU = Maximum Ultimate Load Combination
bo = Perimeter of Punching Failure φ = 0.75 for shear, 0.65-0.9 for flexure
bW = Base width perpendicular to Rebar qu = Soil Uplift Pressure
βR = Ratio of Column Length to Width ρW = Steel Ratio to Concrete Area
βW = Whitneys Constant Vc = Reinforced Concrete Shear Strength
c = Neutral Axis to Extreme Fiber Vu = Ultimate Shear Load
D/C = Demand-Capacity Ratio W' = Distance of Footing End to Column @ W
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: - Date: 07/27/20 Date:
DESIGN OF FOOTING : FORMULAS
}
Least of
= (0.16λ√f'c + 17ρw)bWdW the 3 ρw = AsW / bwdW
= 0.29λ√f'c bwd bw = L
2
AsW = nWπØm / 4
CHECK FOR SHEAR ALONG SIDE "W"
TO SATISFY : Vu ≤ φVc WHERE:
FORMULAS qu = Pu / Aprov
Vu = quW(L' - dL) L' = 0.5 ( L - X )
Vc = (0.16λ√f'c + 17ρwVudL/Mu)bwdL dL = t - 75mm - Øm/2
}
Least of
= (0.16λ√f'c + 17ρw)bwdL the 3 ρw = AsL / bwdL
= 0.29λ√f'c bwd bw = W
AsL = nLπØm2 / 4
CHECK FOR PUNCHING
TO SATISFY : Vu ≤ φVc WHERE:
FORMULAS qu = Pu / Aprov
Vu = qu(A - a) A = LW
Vc = 0.33λ√f'c bodmin a = ( Y + dL ) ( X + dW )
}
Least of
= 0.17(1+2/β)λ√f'c bodmin the 3 bo = 2 ( Y + dL + X + dW )
= 0.083(2+αsd/bo)λ√f'c bodmin βR = X/Y or Y/X whichever is Larger
αs = 40 for Center Column
30 for Edge Column
20 for Corner Column
CHECK FOR MOMENT (REBAR ALONG "W")
TO SATISFY : Mu ≤ φMn WHERE:
As ≤ As,min qu = Pu / Aprov
FORMULAS W' = 0.5 ( W - Y )
Mu = quLW'(W'/2) βW = 0.85 > 0.85*0.05(f'c-28)/7 > 0.65
Mn = 0.85f'cβc(dW-βc/2) c = 600dW/(600+fs)
As = nWπØm2 / 4 Ag = Lt
As,min = 0.002Ag if fy<420 bw = L
= 0.0014Ag if fy≥420
= 0.756Ag/fy if fy≥420
= 0.25bwd√f'c / fy
= 1.4bwd / fy }
To be disregard
if 3*Mu ≤ φMn
WIDTH
SF = 3 800
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 539.00 kN
LC1 = 539.00 kN Areqd = 3.59 m2
LC2 = 264.00 kN Aprov = 2.56 m2
LC3 = 299.71 kN D/C = 1.40
ALTERNATE BASIC LOAD COMBINATION ∴ NOT SAFE
LC4 = 404.25 kN
LC5 = 431.04 kN PUNCHING SHEAR CHECK
Vu = 596.68 kN
ULTIMATE LOAD COMBINATIONS Vc = 1358.08 kN ∴ φVc=1018.56 kN
LC1 = 369.60 kN = 2698.52 kN
LC2 = 756.80 kN ∴ qu=295.63 kPa = 2097.53 kN
LC3 = 591.80 kN D/C = 0.29
LC4 = 707.80 kN ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 107.84 kN Mu = 71.54 β = 0.85
Vc = 391.63 kN ∴ φVc=293.73 kN fs = 4953.99 As = 2010.62
= 409.22 kN c = 34.79 Asmin = 1280 OKAY
= 679.77 kN Mn = 255.73
D/C = 0.21 φ = 0.90 D/C = 0.31
∴ SAFE φMn = 230.15 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 150.89 kN Mu = 92.38 β = 0.85
Vc = 373.49 kN ∴ φVc=280.12 kN fs = 4678.016 As = 2010.62
= 390.59 kN c = 34.79 Asmin 1655.652 OKAY
= 645.99 kN Mn = 242.41
D/C = 0.31 φ = 0.90 D/C = 0.42
∴ SAFE φMn = 218.17 kNm ∴ SAFE
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: 3s-org' Date: 07/27/20 Date:
DESIGN OF FOOTING
INPUT DATA:
1600
Material Properties:
f'c = 20.7 MPa
1400
fy = 414 MPa
λ = 1 1200
WIDTH
SF = 2 800
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 539.00 kN
LC1 = 539.00 kN Areqd = 2.40 m2
LC2 = 264.00 kN Aprov = 2.56 m2
LC3 = 299.71 kN D/C = 0.94
ALTERNATE BASIC LOAD COMBINATION ∴ SAFE
LC4 = 404.25 kN
LC5 = 431.04 kN PUNCHING SHEAR CHECK
Vu = 596.68 kN
ULTIMATE LOAD COMBINATIONS Vc = 1358.08 kN ∴ φVc=1018.56 kN
LC1 = 369.60 kN = 2698.52 kN
LC2 = 756.80 kN ∴ qu=295.63 kPa = 2097.53 kN
LC3 = 591.80 kN D/C = 0.29
LC4 = 707.80 kN ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 107.84 kN Mu = 71.54 β = 0.85
Vc = 391.63 kN ∴ φVc=293.73 kN fs = 4953.99 As = 2010.62
= 409.22 kN c = 34.79 Asmin = 1280 OKAY
= 679.77 kN Mn = 255.73
D/C = 0.21 φ = 0.90 D/C = 0.31
∴ SAFE φMn = 230.15 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 150.89 kN Mu = 92.38 β = 0.85
Vc = 373.49 kN ∴ φVc=280.12 kN fs = 4678.016 As = 2010.62
= 390.59 kN c = 34.79 Asmin 1655.652 OKAY
= 645.99 kN Mn = 242.41
D/C = 0.31 φ = 0.90 D/C = 0.42
∴ SAFE φMn = 218.17 kNm ∴ SAFE
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: 4s-org Date: 07/27/20 Date:
DESIGN OF FOOTING
INPUT DATA:
1600
Material Properties:
f'c = 20.7 MPa
1400
fy = 414 MPa
λ = 1 1200
WIDTH
SF = 3 800
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 804.00 kN
LC1 = 804.00 kN Areqd = 5.36 m2
LC2 = 391.00 kN Aprov = 2.56 m2
LC3 = 443.86 kN D/C = 2.09
ALTERNATE BASIC LOAD COMBINATION ∴ NOT SAFE
LC4 = 603.00 kN
LC5 = 642.64 kN PUNCHING SHEAR CHECK
Vu = 890.92 kN
ULTIMATE LOAD COMBINATIONS Vc = 1358.08 kN ∴ φVc=1018.56 kN
LC1 = 547.40 kN = 2698.52 kN
LC2 = 1130.00 kN ∴ qu=441.41 kPa = 2097.53 kN
LC3 = 882.20 kN D/C = 0.44
LC4 = 1053.95 kN ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 161.03 kN Mu = 106.82 β = 0.85
Vc = 391.63 kN ∴ φVc=293.73 kN fs = 4953.99 As = 2010.62
= 409.22 kN c = 34.79 Asmin = 1742.222 OKAY
= 679.77 kN Mn = 255.73
D/C = 0.32 φ = 0.90 D/C = 0.46
∴ SAFE φMn = 230.15 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 225.29 kN Mu = 137.94 β = 0.85
Vc = 373.49 kN ∴ φVc=280.12 kN fs = 4678.016 As = 2010.62
= 390.59 kN c = 34.79 Asmin 1655.652 OKAY
= 645.99 kN Mn = 242.41
D/C = 0.47 φ = 0.90 D/C = 0.63
∴ SAFE φMn = 218.17 kNm ∴ SAFE
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: 4s-org' Date: 07/27/20 Date:
DESIGN OF FOOTING
INPUT DATA:
1600
Material Properties:
f'c = 20.7 MPa
1400
fy = 414 MPa
λ = 1 1200
WIDTH
SF = 2 800
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 804.00 kN
LC1 = 804.00 kN Areqd = 3.57 m2
LC2 = 391.00 kN Aprov = 2.56 m2
LC3 = 443.86 kN D/C = 1.40
ALTERNATE BASIC LOAD COMBINATION ∴ NOT SAFE
LC4 = 603.00 kN
LC5 = 642.64 kN PUNCHING SHEAR CHECK
Vu = 890.92 kN
ULTIMATE LOAD COMBINATIONS Vc = 1358.08 kN ∴ φVc=1018.56 kN
LC1 = 547.40 kN = 2698.52 kN
LC2 = 1130.00 kN ∴ qu=441.41 kPa = 2097.53 kN
LC3 = 882.20 kN D/C = 0.44
LC4 = 1053.95 kN ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 161.03 kN Mu = 106.82 β = 0.85
Vc = 391.63 kN ∴ φVc=293.73 kN fs = 4953.99 As = 2010.62
= 409.22 kN c = 34.79 Asmin = 1742.222 OKAY
= 679.77 kN Mn = 255.73
D/C = 0.32 φ = 0.90 D/C = 0.46
∴ SAFE φMn = 230.15 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 225.29 kN Mu = 137.94 β = 0.85
Vc = 373.49 kN ∴ φVc=280.12 kN fs = 4678.016 As = 2010.62
= 390.59 kN c = 34.79 Asmin 1655.652 OKAY
= 645.99 kN Mn = 242.41
D/C = 0.47 φ = 0.90 D/C = 0.63
∴ SAFE φMn = 218.17 kNm ∴ SAFE
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: 4s-ret Date: 07/27/20 Date:
DESIGN OF FOOTING
INPUT DATA:
2000
Material Properties:
f'c = 20.7 MPa 1800
fy = 414 MPa
1600
λ = 1
1400
Soil Bearing Capacity 1200
SBCA = 450 kPa
WIDTH
SF = 2 1000
600
Axial Loads (Service Condition):
PDL = 391 kN 400
PLL = 413 kN
200
PEQ = 74 kN
0 LENGTH
PWL = 0 kN
0 500 1000 1500 2000 2500 3000
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 804.00 kN
LC1 = 804.00 kN Areqd = 3.57 m2
LC2 = 391.00 kN Aprov = 3.61 m2
LC3 = 443.86 kN D/C = 0.99
ALTERNATE BASIC LOAD COMBINATION ∴ SAFE
LC4 = 603.00 kN
LC5 = 642.64 kN PUNCHING SHEAR CHECK
Vu = 960.46 kN
ULTIMATE LOAD COMBINATIONS Vc = 1358.08 kN ∴ φVc=1018.56 kN
LC1 = 547.40 kN = 2698.52 kN
LC2 = 1130.00 kN ∴ qu=313.02 kPa = 2097.53 kN
LC3 = 882.20 kN D/C = 0.47
LC4 = 1053.95 kN ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 224.81 kN Mu = 145.71 β = 0.85
Vc = 465.74 kN ∴ φVc=349.31 kN fs = 4896.136 As = 2412.74
= 486.38 kN c = 35.15 Asmin = 2068.889 OKAY
= 807.22 kN Mn = 306.72
D/C = 0.37 φ = 0.90 D/C = 0.53
∴ SAFE φMn = 276.04 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 278.93 kN Mu = 178.61 β = 0.85
Vc = 442.83 kN ∴ φVc=332.13 kN fs = 4623.036 As = 2412.74
= 464.25 kN c = 35.15 Asmin 1966.087 OKAY
= 767.11 kN Mn = 290.73
D/C = 0.48 φ = 0.90 D/C = 0.68
∴ SAFE φMn = 261.66 kNm ∴ SAFE
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: 3s-org Date: 07/27/20 Date:
DESIGN OF FOOTING
INPUT DATA:
1800
Material Properties:
f'c = 20.7 MPa 1600
fy = 414 MPa
λ = 1 1400
1200
Soil Bearing Capacity
SBCA = 450 kPa 1000
WIDTH
SF = 3
800
SBC = 150 kPa
600
Axial Loads (Service Condition):
400
PDL = 159 kN
PLL = 97 kN 200
PEQ = 28 kN
0 LENGTH
PWL = 0 kN
0 500 1000 1500 2000 2500 3000
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 256.00 kN
LC1 = 256.00 kN Areqd = 1.71 m2
LC2 = 159.00 kN Aprov = 3.06 m2
LC3 = 179.00 kN D/C = 0.56
ALTERNATE BASIC LOAD COMBINATION ∴ SAFE
LC4 = 192.00 kN
LC5 = 207.00 kN PUNCHING SHEAR CHECK
Vu = 254.77 kN
ULTIMATE LOAD COMBINATIONS Vc = 2007.59 kN ∴ φVc=1505.69 kN
LC1 = 222.60 kN = 4251.76 kN
LC2 = 346.00 kN = 2445.65 kN
LC3 = 287.80 kN D/C = 0.08
LC4 = 355.55 kN ∴ qu=116.1 kPa ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 31.09 kN Mu = 28.00 β = 0.85
Vc = 489.43 kN ∴ φVc=367.07 kN fs = 5779.954 As = 2211.68
= 511.50 kN c = 34.98 Asmin = 1575 OKAY
= 858.94 kN Mn = 327.00
D/C = 0.05 φ = 0.90 D/C = 0.10
∴ SAFE φMn = 294.30 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 59.73 kN Mu = 42.92 β = 0.85
Vc = 472.14 kN ∴ φVc=354.11 kN fs = 5505.548 As = 2211.68
= 491.12 kN c = 34.98 Asmin 1575 OKAY
= 822.00 kN Mn = 312.35
D/C = 0.10 φ = 0.90 D/C = 0.15
∴ SAFE φMn = 281.12 kNm ∴ SAFE
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: 4s-org Date: 07/27/20 Date:
DESIGN OF FOOTING
INPUT DATA:
1800
Material Properties:
f'c = 20.7 MPa 1600
fy = 414 MPa
λ = 1 1400
1200
Soil Bearing Capacity
SBCA = 450 kPa 1000
WIDTH
SF = 3
800
SBC = 150 kPa
600
Axial Loads (Service Condition):
400
PDL = 229 kN
PLL = 146 kN 200
PEQ = 40 kN
0 LENGTH
PWL = 0 kN
0 500 1000 1500 2000 2500 3000
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 375.00 kN
LC1 = 375.00 kN Areqd = 2.50 m2
LC2 = 229.00 kN Aprov = 3.06 m2
LC3 = 257.57 kN D/C = 0.82
ALTERNATE BASIC LOAD COMBINATION ∴ SAFE
LC4 = 281.25 kN
LC5 = 302.68 kN PUNCHING SHEAR CHECK
Vu = 371.21 kN
ULTIMATE LOAD COMBINATIONS Vc = 2007.59 kN ∴ φVc=1505.69 kN
LC1 = 320.60 kN = 4251.76 kN
LC2 = 508.40 kN = 2445.65 kN
LC3 = 420.80 kN D/C = 0.12
LC4 = 518.05 kN ∴ qu=169.16 kPa ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 45.29 kN Mu = 40.80 β = 0.85
Vc = 489.43 kN ∴ φVc=367.07 kN fs = 5779.954 As = 2211.68
= 511.50 kN c = 34.98 Asmin = 1575 OKAY
= 858.94 kN Mn = 327.00
D/C = 0.07 φ = 0.90 D/C = 0.14
∴ SAFE φMn = 294.30 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 87.03 kN Mu = 62.54 β = 0.85
Vc = 472.14 kN ∴ φVc=354.11 kN fs = 5505.548 As = 2211.68
= 491.12 kN c = 34.98 Asmin 1575 OKAY
= 822.00 kN Mn = 312.35
D/C = 0.14 φ = 0.90 D/C = 0.22
∴ SAFE φMn = 281.12 kNm ∴ SAFE
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: 3s-ednew Date: 08/03/20 Date:
DESIGN OF FOOTING
INPUT DATA:
1400
Material Properties:
f'c = 20.7 MPa
fy = 414 MPa 1200
λ = 1
1000
WIDTH
SF = 3
SBC = 150 kPa 600
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 256.00 kN
LC1 = 256.00 kN Areqd = 1.71 m2
LC2 = 159.00 kN Aprov = 2.08 m2
LC3 = 179.00 kN D/C = 0.82
ALTERNATE BASIC LOAD COMBINATION ∴ SAFE
LC4 = 192.00 kN
LC5 = 207.00 kN PUNCHING SHEAR CHECK
Vu = 223.48 kN
ULTIMATE LOAD COMBINATIONS Vc = 1633.74 kN ∴ φVc=1225.3 kN
LC1 = 222.60 kN = 3460.00 kN
LC2 = 346.00 kN = 1882.60 kN
LC3 = 287.80 kN D/C = 0.09
LC4 = 355.55 kN ∴ qu=170.94 kPa ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 80.41 kN Mu = 49.23 β = 0.85
Vc = 370.07 kN ∴ φVc=277.56 kN fs = 5997.519 As = 1608.50
= 383.75 kN c = 27.83 Asmin = 1280 OKAY
= 645.99 kN Mn = 195.89
D/C = 0.17 φ = 0.90 D/C = 0.28
∴ SAFE φMn = 176.31 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 56.22 kN Mu = 36.74 β = 0.85
Vc = 314.83 kN ∴ φVc=236.12 kN fs = 6921.028 As = 1206.37
= 325.23 kN c = 25.69 Asmin 1040 OKAY
= 552.31 kN Mn = 155.37
D/C = 0.14 φ = 0.90 D/C = 0.26
∴ SAFE φMn = 139.83 kNm ∴ SAFE
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: 4s-ednew Date: 08/03/20 Date:
DESIGN OF FOOTING
INPUT DATA:
1400
Material Properties:
f'c = 20.7 MPa
fy = 414 MPa 1200
λ = 1
1000
WIDTH
SF = 3
SBC = 150 kPa 600
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 375.00 kN
LC1 = 375.00 kN Areqd = 2.50 m2
LC2 = 229.00 kN Aprov = 2.52 m2
LC3 = 257.57 kN D/C = 0.99
ALTERNATE BASIC LOAD COMBINATION ∴ SAFE
LC4 = 281.25 kN
LC5 = 302.68 kN PUNCHING SHEAR CHECK
Vu = 359.22 kN
ULTIMATE LOAD COMBINATIONS Vc = 1633.74 kN ∴ φVc=1225.3 kN
LC1 = 320.60 kN = 3460.00 kN
LC2 = 508.40 kN = 1882.60 kN
LC3 = 420.80 kN D/C = 0.14
LC4 = 518.05 kN ∴ qu=205.58 kPa ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 145.79 kN Mu = 90.66 β = 0.85
Vc = 417.78 kN ∴ φVc=313.33 kN fs = 5337.768 As = 2010.62
= 435.14 kN c = 30.92 Asmin = 1862.609 OKAY
= 726.74 kN Mn = 243.77
D/C = 0.27 φ = 0.90 D/C = 0.41
∴ SAFE φMn = 219.40 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 101.60 kN Mu = 65.57 β = 0.85
Vc = 341.81 kN ∴ φVc=256.35 kN fs = 5474.677 As = 1608.50
= 355.51 kN c = 31.80 Asmin 1524.444 OKAY
= 594.79 kN Mn = 205.42
D/C = 0.23 φ = 0.90 D/C = 0.35
∴ SAFE φMn = 184.88 kNm ∴ SAFE
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: 3s-org Date: 07/27/20 Date:
DESIGN OF FOOTING
INPUT DATA:
1800
Material Properties:
f'c = 20.7 MPa 1600
fy = 414 MPa
λ = 1 1400
1200
Soil Bearing Capacity
SBCA = 450 kPa 1000
WIDTH
SF = 3
800
SBC = 150 kPa
600
Axial Loads (Service Condition):
400
PDL = 93 kN
PLL = 49 kN 200
PEQ = 16 kN
0 LENGTH
PWL = 0 kN
0 500 1000 1500 2000 2500 3000
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 142.00 kN
LC1 = 142.00 kN Areqd = 0.95 m2
LC2 = 93.00 kN Aprov = 3.06 m2
LC3 = 104.43 kN D/C = 0.31
ALTERNATE BASIC LOAD COMBINATION ∴ SAFE
LC4 = 106.50 kN
LC5 = 115.07 kN PUNCHING SHEAR CHECK
Vu = 143.20 kN
ULTIMATE LOAD COMBINATIONS Vc = 2007.59 kN
LC1 = 130.20 kN = 4251.76 kN
LC2 = 190.00 kN = 1967.06 kN ∴ φVc=1475.29 kN
LC3 = 160.60 kN D/C = 0.04
LC4 = 199.85 kN ∴ qu=65.26 kPa ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 17.47 kN Mu = 15.74 β = 0.85
Vc = 489.43 kN ∴ φVc=367.07 kN fs = 5779.954 As = 2211.68
= 511.50 kN c = 34.98 Asmin = 1575 OKAY
= 858.94 kN Mn = 327.00
D/C = 0.03 φ = 0.90 D/C = 0.05
∴ SAFE φMn = 294.30 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 33.57 kN Mu = 24.12 β = 0.85
Vc = 472.14 kN ∴ φVc=354.11 kN fs = 5505.548 As = 2211.68
= 491.12 kN c = 34.98 Asmin 1575 OKAY
= 822.00 kN Mn = 312.35
D/C = 0.05 φ = 0.90 D/C = 0.09
∴ SAFE φMn = 281.12 kNm ∴ SAFE
1009 Cityland 10 Tower 2 Project: 3 STOREY STEEL PARKING BUILDING
H.V. dela Costa St., Client: PLDT GRACE PARK CALOOCAN
Salcedo Village, Location: GRACE PARK, CALOOCAN CITY
Makati City Job. No.: 1 Design by: SAC Checked by: SCM
Tel. no.: 519-8268 Subject: 4s-org Date: 07/27/20 Date:
DESIGN OF FOOTING
INPUT DATA:
1800
Material Properties:
f'c = 20.7 MPa 1600
fy = 414 MPa
λ = 1 1400
1200
Soil Bearing Capacity
SBCA = 450 kPa 1000
WIDTH
SF = 3
800
SBC = 150 kPa
600
Axial Loads (Service Condition):
400
PDL = 130 kN
PLL = 73 kN 200
PEQ = 22 kN
0 LENGTH
PWL = 0 kN
0 500 1000 1500 2000 2500 3000
DESIGN COMPUTATION:
SERVICE LOAD COMBINATIONS FOOTING DIMENSION CHECKING
BASIC LOAD COMBINATION Ps = 203.00 kN
LC1 = 203.00 kN Areqd = 1.35 m2
LC2 = 130.00 kN Aprov = 3.06 m2
LC3 = 145.71 kN D/C = 0.44
ALTERNATE BASIC LOAD COMBINATION ∴ SAFE
LC4 = 152.25 kN
LC5 = 164.04 kN PUNCHING SHEAR CHECK
Vu = 203.15 kN
ULTIMATE LOAD COMBINATIONS Vc = 2007.59 kN
LC1 = 182.00 kN = 4251.76 kN
LC2 = 272.80 kN = 1967.06 kN ∴ φVc=1475.29 kN
LC3 = 229.00 kN D/C = 0.06
LC4 = 283.50 kN ∴ qu=92.57 kPa ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "L" CHECK FOR MOMENT (REBAR ALONG "W")
Vu = 24.79 kN Mu = 22.33 β = 0.85
Vc = 489.43 kN ∴ φVc=367.07 kN fs = 5779.954 As = 2211.68
= 511.50 kN c = 34.98 Asmin = 1575 OKAY
= 858.94 kN Mn = 327.00
D/C = 0.04 φ = 0.90 D/C = 0.08
∴ SAFE φMn = 294.30 kNm ∴ SAFE
CHECK FOR SHEAR ALONG SIDE "W" CHECK FOR MOMENT (REBAR ALONG "L")
Vu = 47.63 kN Mu = 34.22 β = 0.85
Vc = 472.14 kN ∴ φVc=354.11 kN fs = 5505.548 As = 2211.68
= 491.12 kN c = 34.98 Asmin 1575 OKAY
= 822.00 kN Mn = 312.35
D/C = 0.08 φ = 0.90 D/C = 0.12
∴ SAFE φMn = 281.12 kNm ∴ SAFE