RM6 - Medium Voltage Distribution: Civil Engineering and Installation Manual

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 92

RM6 - Medium Voltage Distribution

Civil engineering and installation manual


07897071EN01 Rev.12
10/2018

Validated for Quotation


Printed on 2018/10/17
Legal Information

The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred
to in this guide are the sole property of Schneider Electric SA and its subsidiaries. They may not be used for
any purpose without the owner's permission, given in writing. This guide and its content are protected, within
the meaning of the French intellectual property code (Code de la propriété intellectuelle français, referred
to hereafter as "the Code"), under the laws of copyright covering texts, drawings and models, as well as by
trademark law. You agree not to reproduce, other than for your own personal, noncommercial use as defined in
the Code, all or part of this guide on any medium whatsoever without Schneider Electric's permission, given in
writing. You also agree not to establish any hypertext links to this guide or its content. Schneider Electric does
not grant any right or license for the personal and noncommercial use of the guide or its content, except for a
non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No
responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

As standards, specifications, and designs change from time to time, please ask for confirmation of the
information given in this publication.

Validated for Quotation


Printed on 2018/10/17
RM6 - Civil engineering and installation manual

Table of Contents

Legal Information.............................................................................. 2

Foreword.......................................................................................... 6
Foreword................................................................................................................. 6
Safety Instructions................................................................................................... 7
Disposal of the Equipment at End-of-Life................................................................ 7

General Description.......................................................................... 8
Circuit-breaker and Switch Function........................................................................ 8
Switch-fuse Combination and Switch Function....................................................... 8
“Switchboard Coupling” Switch and Circuit-breakers.............................................. 8
Cable Connection Function..................................................................................... 9
Metering Cubicle...................................................................................................... 9
Example of Single-line Diagrams.......................................................................... 10
Range Sizes and Weights..................................................................................... 11
Transport............................................................................................................... 16
Handling................................................................................................................ 17
Unpacking on Site................................................................................................. 19
Storage.................................................................................................................. 21
Characteristics....................................................................................................... 22
Identification.......................................................................................................... 23
Before Installation and Energizing......................................................................... 24
Unit with Pressure Switch...................................................................................... 25

Installation Recommendation......................................................... 27
Reminder............................................................................................................... 27
Temperature.......................................................................................................... 27
Example of Correct Installation.............................................................................. 28

Sizing of the Civil Engineering........................................................ 29


For Network Switch or Network Circuit-breaker.................................................... 29
For Switch-fuse Combinations............................................................................... 30
For DE-Mt Metering Cubicle.................................................................................. 32
Duct Detail for Switchboard with MV Metering...................................................... 33

Fitting and Fixing on the Civil Engineering..................................... 34


Dimensions of RM6 RE with an Extension Module .............................................. 34
Preparing the Ground Fixing ............................................................................... 35
Fixing to the Ground.............................................................................................. 36
Installing the Substation for Resistance to Internal Arc........................................ 37

Connection Instructions.................................................................. 40
Foreword............................................................................................................... 40
Type of Usable Connections.................................................................................. 41
Connecting the HV Cables.................................................................................... 42
Instructions............................................................................................................ 43
Methods and Fabrication of Cable Connections for Single Pole Cables............... 44
LV Compartment Customer Power supply for DE-Mt Cubicle............................... 59
Current Transformer (CT) Intensities and Temperatures for DE-Mt Cubicle.......... 60
Switch, Circuit-breaker, Earthing Switch Indication............................................... 61
Fuse Blowing Indication (optional supply)............................................................. 61
Fault Tripping Indication (optional supply)............................................................. 61

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 3
RM6 - Civil engineering and installation manual

Table of Contents

Tripping Coil (optional supply)............................................................................... 62


Pressure Switch Connection................................................................................. 63
Connecting a Sepam 10 Relay.............................................................................. 64
VIP400 / VIP410 Connection................................................................................. 78
Installing an ATS (Automatic Transfer System)..................................................... 82
BTA Function......................................................................................................... 83
Installing an ATS/ACO........................................................................................... 83
Fitting the T200I Support Kit.................................................................................. 84
Installing the T200I and Connecting it to the RM6................................................. 84
Detection Sequence (ATS/VD23).......................................................................... 86

Validated for Quotation


4 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Notes

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 5
Foreword RM6 - Civil engineering and installation manual

Foreword
Foreword
Important Information

Notice
Read these instructions carefully and look at the equipment to become
familiar with the device before trying to install, operate, service or maintain it.
The following special messages may appear throughout this document or on
the equipment to warn of potential hazards or to call caution.

The addition of this symbol either to a “Danger” or “Warning” safety


label indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential


personal injury hazards. Obey all safety messages that follow this
symbol to avoid possible injury or death.

DANGER
DANGER indicates a hazardous situation which, if not avoided,
will result in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided,
can result in death or serious injury.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.

NOTICE
NOTICE is used to address practices not related to physical injury.

INFORMATION-ADVICE
We draw your attention on this particular point.

Important Remarks
Electrical equipment should be installed, operated, serviced, and
maintained only by qualified personnel. No responsibility is assumed
by Schneider Electric for any consequences arising out of the use
of RM6 equipment.
A qualified person is one who has skills and knowledge related to the
construction, installation, and operation of electrical equipment
and has received safety training to recognize and avoid the hazards
involved.

Validated for Quotation


6 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Foreword

Diffusion Rules Total or partial reproduction of this manual is prohibited and only Schneider Electric
agents have an exclusive right to use.

Safety Instructions
Safety Rules

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
● Apply appropriate personal protective equipment (PPE)
and follow safe electrical work practices.
● This equipment must only be installed and serviced by qualified
electrical personnel.
● Turn off all power supplies of the equipment before working on or inside
equipment.
● Always use a properly rated voltage sensing device to confirm power is off.
● Set all devices, doors and covers before turning on power to this equipment.
● Do not use solvents and alcohol for cleaning.
● Do not use high-pressure cleaner.
● Beware of potential hazards, and carefully inspect the work area for tools and
objects that may have been left inside the equipment.
Failure to follow these instructions will result with death or serious injury.

Disposal of the Equipment at End-of-Life


This equipment contains compressed springs.

WARNING
HAZARD OF MECHANICAL IMPACT
● Apply appropriate personal protective equipment (PPE) and follow
safe work practices.
● This equipment must only be dismantled by qualified personnel.
Failure to follow these instructions can result in death, serious injury
or equipment damage.

NOTE: This equipment contains SF6 gas. SF6 is a powerful greenhouse gas. Prior to
disposal of the equipment at end-of-life, the SF6 gas must be recovered in order for it
to be recycled, reclaimed or destroyed.

b Do not carry out any dismantling operations unless authorized.


b Do not handle SF6 gas unless certified according to local regulation.
b Do not release SF6 gas to the atmosphere.

Penalties may apply according to local regulations and rules


(Regulation (EU) N°517/2014 for all European countries).

Schneider Electric offers a complete service to dismantle and recycle Medium Voltage
equipment and SF6 gas at end-of-life. This service is compliant with IEC 62271-4 and
conforms to local regulations.
Please contact Schneider Electric for details.

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 7
General Description RM6 - Civil engineering and installation manual

General Description
I = Switch & earthing switch DE-Mt = Double extensible metering
Q = Switch-fuse combination & earthing switch
D = Circuit Breaker up to 200A & earthing switch
B = Circuit breaker up to 630A & earthing switch NE = No Extensible
Ic = Busbar coupling switch & earthing switch DE = Double Extensible
Bc = Busbar coupling circuit breaker up to 630A & earthing switch LE = Left Extensible
O = Cable connection RE = Right Extensible

Circuit-breaker and Switch Function


A: o perating mechanism front plate comprising
G C D K L N F E P
the mimic diagram
B: nameplate
C: earthing switch operating shaft
D: switch operating shaft B
E: function (switch or CB) position indicator A
F: voltage indicator
G: LV connection access trunking
H: connection bushing access panel M
K: VIP40/45 - VIP400/410 protection relays H
L: D function (CB opening pushbutton) opening
pushbutton
M: designation plate
N: pressure switch or gauge label
P: location of optimal pressure switch or gauge
IDI

Switch-fuse Combination and Switch Function


A: o
 perating mechanism front plate comprising G C D N F E P
the mimic diagram
B: nameplate
C: earthing switch operating shaft
D: switch operating shaft B
E: function position indicator A
F: voltage indicator
G: LV connection access trunking
H: connection bushing access panel J
J: designation plate H
N: pressure switch or gauge label
P: pressure switch or gauge

IQI

“Switchboard Coupling” Switch and Circuit-breakers


1: DE-Bc station with earthing switch D

A: control panel featuring the mimic panel


B
B: earthing switch operating shaft
C: switch operating shaft F
C
D: voltage indicator A
E: connection bushing access panel
F: nameplate E

Validated for Quotation


8 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual General Description

2: DE-Ic station with earthing switch


D
A: control panel featuring the mimic panel
B: earthing switch operating shaft
G B
C: switch operating shaft
D: voltage indicator C
E: connection bushing access panel A
F: customer’s designation plate F
G: nameplate E

Cable Connection Function


Example presented: DE-O

A: nameplate
A
B: designation plate
C: connection bushing access panel
B

Metering Cubicle
1: LV cabinet
2: voltage transformer access panel
3: nameplate
4: access panel to current transformer
5: LV compartment

3 2 4 5 1

without LV cabinet
sans caisson BT avec caisson
with LV cabinetBT

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 9
General Description RM6 - Civil engineering and installation manual

Example of Single-line Diagrams

NE - D RE - DIDI DE - IIBI

DE - III NE - IQI NE - IDI

DE - DD DE - IDD DE - IIBc

Validated for Quotation


10 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual General Description

Range Sizes and Weights


1 Function Range
function weight (kg) length (mm)
NE I 135 L = 572
D
B
DE I 135 L’ =
 472 + 30 + 30
= 532
D L’ =
 572 + 30 + 30
B = 632 1142
Q 185 L’ =
 472 + 30 + 30
= 532
30 30
cable connexion
RE O 135 L’ = 472 + 30 = 502
LE
DE L’ =
 472 + 30 + 30
= 532
bus coupler
DE Ic 145 L’ =
 572 + 30 + 30 L 710
Bc = 632 L’

30 30 30 30

NE RE LE DE

L L L L
L’ L’ L’

NE = No Extensible
DE = Double Extensible
LE = Left Extensible
RE = Right Extensible

2 Functions Range Basic


function weight (kg) length (mm)
NE QI 180 L = 829
DI, BI
II 155
RE II L’ = 829 + 30 = 859

1142

L
L’

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 11
General Description RM6 - Civil engineering and installation manual

2 Functions Range / Free Combination


function length (mm)
NE L = 1052
LE L’ = 1052 + 30 = 1082
RE
DE L’ = 1052 + 30 + 30 = 1112

L
L’

All function can be FREE combination

Below possible example:

function weight (kg)


II IO OI OO 205
ID DI IB BI 215
IQ QI OQ QO 240
DD BB 225
DQ QD BQ QB 250
QQ 275

3 Functions Range Basic


function weight (kg) length (mm)
NE IQI 275 L = 1186
III 240
IDI
IBI 250
RE RE-IQI 275 L’ = 1186 + 30 = 1216
RE-III 240
RE-IDI
RE-IBI 250
DE IQI 275 L’ = 1186 + 30 + 30
III 240 = 1246
IDI
IBI 250
L
L’

Validated for Quotation


12 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual General Description

3 Functions Range / Free Combination


function length (mm)
NE L = 1532
LE L’ = 1532 + 30 = 15622
RE
DE L’ = 1532 + 30 + 30 = 1592

L
L’
All function can be FREE combination

Below possible example:

function weight (kg)


III OOO 305
IIO IOI OII 305
IOO OIO OOI 305
IID IDI DII 315
IIB IBI BII 315
IIQ IQI QII 340
IDD DID DDI 325
IBB BIB BBI 325
IQD IDQ DIQ 350
QDI QID DQI 350
IQQ QIQ 375
DDD BBB 335
QQQ 410

With Bus Coupler


function length (mm)
NE L = 1532
DE L’ = 1532 + 30 + 30 = 1592

L
L’
Below possible example:

function weight (kg)


IIIc 320
IIBc IDIc IBIc 330
DIIc BIIc 330
IQIc QIIc 355
IQBc QIBc 365
DDIc BBIc 340
DDBc BBBc 350
QQIc 390
QQBc 400

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 13
General Description RM6 - Civil engineering and installation manual

4 Functions Range Basic


function weight (kg) length (mm)
NE IIQI 355 L = 1619
IIII 320
IIDI / IIBI 330
QIQI 390
BIBI / DIDI 340
DIDI 340
RE IIQI 355 L’ = 1619 + 30 = 1649
IIII 320
IIDI / IIBI 330
QIQI 390
BIBI 340
DIDI 340
DE IIQI 355 L’ =
 1619 + 30 + 30
IIII 320 = 1679 L
IIDI / IIBI 330
L’
NE = No Extensible
DE = Double Extensible
LE = Left Extensible
RE = Right Extensible

5 Functions Range
function weight (kg) length (mm)
NE IIIQI 485 L = 2000
IBIQI 495
IIIII 450
IIIDI / IIIBI 460
IQIQI 520
IBIBI / 470
IDIDI
RE / IIIQI 490 L’ = 2000 + 30 = 2030
LE IBIQI 500
IIIII 455
IIIDI/ IIIBI 465
IQIQI 525
IBIBI/ 475
IDIDI
DE IIIQI 495 L’ =
 2000 + 30 + 30
L
= 2060 L’
IBIQI 505
IIIII 460
IIIDI/ IIIBI 470
IQIQI 530
IBIBI/ 480
IDIDI

Option
Arrester option
Dimensions en mm
175

1142

710
859
Validated for Quotation
14 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual General Description

Metering Cubicle
With LV compartment
function weight (kg) length (mm)
DE-Mt 420 L = 1106

1606

L 901

Without LV compartment
function weight (kg) length (mm)
DE-Mt 400 L = 1106

1174

L 901

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 15
General Description RM6 - Civil engineering and installation manual

Transport
Centre of Gravity
Do not handle the cell from the face
plate. CAUTION
1: high centre of gravity
Handle the cell carefully so as not to
cause deformation or damage.

Respect of Transport

Wedge the RM6 unit securely during transport.

DO NOT
STACK

CAUTION
Do not place anything on the RM6 unit.
Do not walk on the RM6 unit.

Acceptance
b Make sure the delivered RM6 unit is complete.
b Carry out a visual inspection of the functional components.
b Verify the characteristics indicated on the nameplates, compared to the initial order.
Refer to the “Characteristics” chapter.
b The plastic cover must be in position on the RM6 unit and in good condition when it
arrives.

Validated for Quotation


16 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual General Description

Handling
A handling pallet is fixed beneath the RM6 switchgear. This device enables fork
handling of the devices.

Silk-screen Printed Instructions on the Transport Cover

CAUTION
It is important to pay particular attention to the information affixed to the
transport cover before carrying out any kind of handling operations.

Protéger de la pluie Manipuler avec soin Soulever dans ce sens Protéger du soleil

maxi 70°C
Température de stockage Centre de gravité haut Ne pas marcher dessus Ne pas empiler
mini --- 40°C

Handling by Forklift Truck

CAUTION
Comply with the positioning of the forks.
The truck’s forks must be engaged underneath the entire width of the RM6 unit.

1 2

RM6

The handling solution 1 is to be used Make sure that in case 1 the forks
only for narrow areas where handling are considerably longer than half the
solution 2 is impossible. length of the pallet.

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 17
General Description RM6 - Civil engineering and installation manual

Handling by Slings with Hooks


If the minimum sling lengths cannot be implemented, use a lifting beam.

CAUTION
Do not handle a substation using slings, if the LV trunking or mimic panel front plate
are not fitted. The handling by lugs are reserved only for handling RM6 substations.

A: nut and screws HM12


B: WLL (Working Load Limit) = 400 kg CE
C: if the holes are deformed (roundness) replace the
lugs.
L
120o
maxi

B
A

For 5 Functions
A: bolt and screws HM12
B: WLL = 550 kg CE
C: if the holes are deformed (roundness) replace the
lugs.

SCHNEIDER
ELECTRIC
<90°
CMU= 550 daN
CE B
A
B

lifting beam (capacity > 550 kg)

Handling by slings Handling by lifting beam

Choice of slings to be used


RM6 2 functions (mm) 3 functions (mm) 4 functions (mm)
width cubicle (L) 829 1186 1619
length cable minimun 700 700 1000

For free combination

FREE combination 2 functions for 3 functions for 5 functions (mm)


free combination free combination
(mm) (mm)
width cubicle (L) 1052 1532 2000
length cable minimun 700 1000 1500

Validated for Quotation


18 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual General Description

Handling Using Rollers


After unpacking and dismantling of the handling kit. Slide the RM6 unit:
bb either on several cylindrical rollers (A);
bb or using 4 cycling corners (B) (not supplied by Schneider Electric).
Move it in this way to its permanent place.

B
A x4

or

Unpacking on Site
After unpacking, the remaining materials (plastic cover + wooden
pallet) must be sorted and routed to the appropriate recycling
systems. When unpacking, check the functioning of the RM6 units
by carrying out a few actions.

Remove the packing cover. Place the device on the ground.

Remove the handling pallet.


NB: the front plinth MUST remain in position.

Lift up the substation in order to remove the handling pallet.

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 19
General Description RM6 - Civil engineering and installation manual

Checking the Accessories Delivered with the Unit


We draw your attention to this specific point. The actuating lever is
a MANDATORY requirement in order to install the RM6 unit and put
it into operation.

CAUTION
Reminder: the original RM6 lever must be used; it is delivered with the RM6 unit.

If the lever is missing ?


Call your sales representative who will put you contact with the closest Schneider
Electric group service centre.
You can log on to: www.schneider-electric.com

Validated for Quotation


20 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual General Description

Storage
CAUTION
When stored, the equipment must remain in its original packing.
It must be stored under shelter, on a dry floor or on a material insulating it from the
damp.

Clean using a sponge and clear water. Do not use alcohol or other solvents to clean.
Following prolonged storage, all the insulating parts must be thoroughly cleaned
before use. The panels must be dusted using a dry, clean cloth.

Keep away from rain Handle with care This way up Keep away from sunlight

maxi 70°C
Storage temperature High gravity center Do not walk on it Do not stack
mini --- 40°C

t
in
pa

Keep away from rain Handle with care This way up Keep away from sunlight Keep away from rain Handle with care This way up Keep away from sunlight
Keep away from rain Handle with care This way up Keep away from sunlight

maxi 70°C maxi 70°C


maxi 70°C
Storage Temp High gravity center Do not walk on it Do not stack Storage Temp High gravity center Do not walk on it Do not stack
mini --- 40°C mini --- 40°C Storage Temp High gravity center Do not walk on it Do not stack
mini --- 40°C

Specific Recommendations for Long-Term Storage

CAUTION
Regularly check the condition of the protective cover.

After a long-term storage, we ensure thoroughly clean all insulating parts before
commissioning.The clothing will be dusted using a clean, dry cloth. Cleaning with a
sponge and clean water.

REMINDER

SOLVENTS AND ALCOHOL FORBIDDEN

HIGH-PRESSURE CLEANER FORBIDDEN

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 21
General Description RM6 - Civil engineering and installation manual

Characteristics
CAUTION
Check that the information marked on the rating plate matches the equipment
ordered.

PP YYYY Www D nnnn

sequence number
day of week

week of manufacture

year of manufacture

plant code

1: function switch
2: function circuit-breaker
3: function switch-fuse combination
4: connection busbar

1 2 3 4

Validated for Quotation


22 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual General Description

Identification
A: unit serial n° engraved on top of the case.
B: unit serial n° engraved on connection bushing
access panel

A
RM6 UNIT PRIOR TO 2005.04.11
1st case
R XX XX XXX XX

R XX XX XXX XX

Manufacturing site

Order number

Week of manufacture

Year of manufacture

RM6 UNIT BETWEEN 2005.04.11


AND MARCH 2009 SUBSEQUENT TO 11.04.05
2nd case

Year of manufacture

Week of manufacture

Order number
B
Manufacture site

RM6 UNIT FROM MARCH 2009 SUBSEQUENT TO 11.04.05


AND FROM MARCH 2009
3th case
PP YYYY Www D nnnn

Plant code FROM MARCH 2009


Year of manufacture

Week of manufacture

Day of week A
Sequence number

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 23
General Description RM6 - Civil engineering and installation manual

Before Installation and Energizing


Check the SF6 gas pressure for units fitted with a manometer or a pressure switch.

Unit with Manometer


Case 1: Needle in Green Zone
INFORMATION
For a correct reading of the manometer, look at the position of the needle
according to the ambient temperature.

+40°
+20°

-25°

-100 mbar Filling +500 mbar


pressure
0.2 bar

b If the needle is in the green zone, RM6 unit can be operated normally.

Case 2: Needle in Red Zone


INFORMATION
For a correct reading of the manometer, look at the position of the needle
according to the ambient temperature.

+40°
Scale : Tolerancing Standard :
+20° Units of measure :
2 0° millimeter
STD PRESSURE GAUGE SERIGRAPHY
-25° STD
SERIGRAPHIE MANOMETRE
Number : Rev : Sheet :

S1A8662804 01 1/2
-100 mbar
All informations and data contained in this document are the exclusive property of Schneider Electric StateFilling
*: +500 mbar
Industries SAS and may neither be used nor disclosed without its prior written consent
pressure FORMAT A4

0.2 bar

b If the needle is in the red zone, the RM6 pressure is too low to operate.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
● DO NOT make any operation on RM6 if pressure is too low.
● Contact immediately Schneider Electric service center.
Failure to follow these instructions will result in death
or serious injury.
Scale : Tolerancing Standard : Units of measure :
2 for Quotation Validated millimeter
24 Printed
STD PRESSURE GAUGE on 2018/10/17
SERIGRAPHY
07897071EN01-12
SERIGRAPHIE MANOMETRE STD
Number : Rev : Sheet :
RM6 - Civil engineering and installation manual General Description

Unit with Pressure Switch


LCD Display Check
NOTICE
HAZARD OF WRONG INFORMATION
Every devices emitting waves (GSM, walkie-talkie, ...) must be above a distance of
2 meters of the cubicle while performing density check.
Failure to follow these instructions can lead you to make a wrong action.

Press the “TEST” button. The LCD screen displays:

b If nothing is displayed, check that the 8-point connector on the pressure switch
wiring harness at the rear of the LCD display is correctly connected.
b Contact the after sales service.

NOTE: the LCD display is self-powered by piezoelectric buttons («TEST» and


«DENSITY SWITCH»). Pressing one of these buttons displays a few seconds.

Pressure Check
Press the “DENSITY CHECK” button.
The LCD screen displays:

b Case 1: OK
The RM6 unit is in normal operational status (ready for energizing).

b Case 2: LOW / OK
The RM6 unit is degraded operational status.
Replacement need to be planned.
Can stay energized and can be operated.

b Case 3: VERY LOW / NOT OK

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
● Do not make any operation on RM6 if pressure is too low.
● Contact immediately Schneider Electric service center.
Failure to follow these instructions will result in death or
serious injury.

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 25
General Description RM6 - Civil engineering and installation manual

Warning Label
Recalls the Safety Rules
There are two types of pressure indicating unit in RM6:
manometer and LCD Density Display. See the image
below where those units can be found.

Information
In the event of an anomaly, indicate the necessary issues to the
carrier. The functional unit must remain on its base in its original
packing materials when it is stored, until it is taken to its installation
site.

CAUTION
In a case of visible damage or anomalies, do not install the RM6 unit.
Contact Schneider Electric immediately.

Validated for Quotation


26 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Installation
General
recommendation
Description

Installation Recommendation
Reminder
It is important to control heating phenomena causing condensation problems in
sub-stations. Condensation is determined directly by the temperature of the
components and the humidity level of the air introduced by the ventilation.
This humidity level can be modified considerably by the presence of water in the
basement.

Temperature
+60° C**
+40° C

- 25° C

When the RM6 is operating, the ambient temperature must be between -25°C and
+40°C.

CAUTION
**Above 40°C, but only up to 60°C, carry out a current derating.

temperature 40°C 45°C 50°C 55°C 60°C


nominal current 400 A 400 A 400 A 355 A
630 A 575 A 515 A 460 A 425 A

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 27
Installation recommendation RM6 - Civil engineering and installation manual

Example of Correct Installation


Ageing withstand of switchgear in an MV substation depends on several factors that
must be complied with before or while installing the equipped substation.

Rules to be complied with


bb 1
Need for proper implementation of connections:
the new cold-slip-on or retractable technologies offer an ease of installation that
encourages long-term withstand.
bb 2
The effect of the relative humidity factor:
implementation of a heating resistor in the LV compartment is vital in climates with a
high rate of relative humidity and with large temperature differences.
bb 3
Ventilation control:
grid size must be suited to the power lost in the substation.These grids must be placed
only near the transformer, to avoid air circulation on the MV switchboard.
bb 4
The need for brickwork construction for the ducts, equipped with a device
guaranteeing absence of water stagnation:
either by installation of perfect tightness at cable routing level, at the entrance to the
MV substation enclosure or by installation of a device allowing evacuation of
water that has accidentally entered the duct.
bb 5
Preparation of the ground guaranteeing absence of water penetration in the
ducts and rapid evacuation of water that has accidentally entered the ducts:
by installation of a drain under and around the substation (sufficiently thick gravel
layer).
bb 6
Stabilisation of the ground before installing the MV substation guaranteeing
absence of all ground movement and thus of the MV substation at a later stage.

2 3
(3)

HV/LV transfo

LV panel
1

RM6

3
(3)

4
(6)
6

Validated for Quotation


28 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Sizing of the civil engineering

Sizing of the Civil Engineering


For Network Switch or Network Circuit-breaker
Cables can be routed from the front, rear, left or right. In the case of civil engineering
without trench, a raising plinth can be optionally supplied.

70 mm mini
40 mm mini 80 mm maxi
50 mm maxi
P1 P1
R
40 mm mini
90 mm mini
50 mm maxi
120 mm maxi

Determining Trench Depth (P1) (for information)


For more detailed information, please contact the cable supplier.

connection cable insulation cable cross- radius of depth


section curvature (mm)
(mm2) (mm)
plug-in sockets dry insulator single-pole ≤ 50 370 270
draw-out sockets 70 à 95 440 340
120 à 150 500 400
185 à 240 590 520
300 640 540
heat-shrinkable dry insulator single-pole ≤ 50 370 270
ends 70 à 95 440 340
120 à 150 500 400
185 à 240 590 520
300 640 540
three-pole ≤ 95 550 660
150 610 720
185 650 770
paper three-pole ≤ 50 550 660
impregnated 95 635 750
with non-
150 670 790
draining
material 240 775 900
300 835 970

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 29
Sizing of the civil engineering RM6 - Civil engineering and installation manual

For Switch-fuse Combinations


H1: 700 mm minimum for changing fuses
A: plug-in (elbow type socket)
B: plug-in (straight socket)

H1 H1

800

A
B

P2 P2

The sectional area of the “transformer” output cable (functions Q and D) is usually less
than that of “network” output cables (functions I and B).
All the cables then pass through the same space. When using HV straight power
outlets or bases, the depth “P2” indicated above may be greater than that of “network”
“P1” cables.

In the Case of a Connection with Heat-Shrinkable Sleeve


Installation of the square of connection TH
C: heat-retractable

1: to fix the square of connection under the fuse well


using screw HM8.20 like its disc diameter 8 (delivered
srews and bolts)

CAUTION
The curvature of the cables may cause partial deterioration of the fuse
compartments.
It is mandatory to use 520 mm bases.

Validated for Quotation


30 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Sizing of the civil engineering

Determining Trench Depth (P2)


cable cable crosssection radius of curvature plug-in plug-in heatshrinkable
insulation (mm2) (mm) elbow type straight (mm)
isolant sec unipolaire 35 335 100 520 335
50 à 70 400 100 520 400
95 440 100 550 440
tripolaire 35 435 100 520 725
50 à 70 500 100 520 800
95 545 100 550 860

Additional Raising Block


The RM6 may be optionally equipped with a 260 or 520 mm raising plinth.
This addition, which simplifies civil engineering works, allows a reduction in trench
depth or even complete elimination of trenches when cable radius of curvature
so allows.

CAUTION
For these bases Internal Arc resistance, please contact the Schneider Electric
department.

A: base 260 mm
B: base 520 mm

703 mm
703 mm

520 mm
B
B
703 mm

260 mm

A
A

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 31
Sizing of the civil engineering RM6 - Civil engineering and installation manual

For DE-Mt Metering Cubicle


CAUTION
The width of the metering cubicle’s duct must be taken into consideration in the
event of a future extension.

CAUTION
INTERNAL ARC RESISTANCE OF THE INSTALLATION
Make sure that the positioning of the evacuation flap on the duct is respected, as
described on the following page.

P1
146 mm maxi 244 mm maxi
136 mm mini 214 mm mini

CAUTION
The handling rollers must not be in line with the duct.

Validated for Quotation


32 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Sizing of the civil engineering

Duct Detail for Switchboard with MV Metering


Bottom view
A: membrane
B: flap
C: duct

10 mini 10 mini

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 33
Fitting and fixing on the civil engineering RM6 - Civil engineering and installation manual

Fitting and Fixing on the Civil Engineering


Dimensions of RM6 RE with an Extension Module

Example:
RM6 RE 4 functional units with circuit-breaker
A = 2264 mm (619+43+572+30)

(*) B = 900 for DE function


B = 1600 for 3 DE functions standard or free
combinaison ( 2 functions)
B = 2000 for 4 DE functions standard or free
combinaison ( 3 functions)
These dimensions can be reduced under special
conditions, consult us.

D/B

CAUTION
C: the distance between the wall and the last cubicle varies according to the type of
function.
D / B / Q functions others functions
C: minimum 250 mm C: minimum 150 mm
(to allow operations on the last cubicle)

Validated for Quotation


34 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Fitting and fixing on the civil engineering

Preparing the Ground Fixing


Sizing for RM6
function type A (mm) B (mm) C (mm)
RM6 (1 function) basic 542 416 63
RM6 (1 function) basic 642 516 63
RM6 (2 functions) basic 899 773 63
RM6 (2 functions) free combinaison 1122 996 63
RM6 (3 functions) basic 1256 1130 63
RM6 (3 functions) free combinaison 1602 1476 63
RM6 (4 functions) basic 1689 1563 63
RM6 (5 functions) 2073 1959 63

A
35 mm

C RM6
645 mm

B
25 mm

FRONT FACE
FACE AVANT

For RM6 Extensible to the Right (RE) or Left (LE) or (DE)


A A
43 43

RM6
RM6 DE or LE 645mm DE or RE RE =( Right)RM6
ExtensibleàDroite

B B

FRONT FACE

NE = No Extensible
DE = Double Extensible
LE = Left Extensible
RE = Right Extensible

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 35
Fitting and fixing on the civil engineering RM6 - Civil engineering and installation manual

Fixing to the Ground


The RM6 must be fixed by at least 3 points for the first cubicle then in the case
of extensibility, we can limit at 2 fixing points on the plinth.
Position the RM6 on the civil engineering then fix it.Drilling holes can accept screw
diameter ...

Verification before Installation

CAUTION
● The finishing on the civil engineering slab must be of high quality
● There must be no evenness defect greater than 7 mm over a length of 2 m
and a width of 1 m.

A Threaded Expansion Anchor (not supplied)


This anchor will allow the fixation to the ground fixing cells.
1: chamfered extremity of the stud making it possible to hammer it in without damaging
the threads
2: class 8 nut for bichromate steel or A4 stainless steel studs depending on the version
3: washer
6 5 4 3 2 1
4: smoothe stud shaft without marking
5: rolled expansion ring made up of two segments linked together on one side. Each
segment has a boss.
6: tapered part of the stud performing expansion

Validated for Quotation


36 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Fitting and fixing on the civil engineering

Installing the Substation for Resistance to Internal Arc


When an installation is requested with protection against internal arcing faults, consult
the diagrams below. The parts to guide the gases towards the evacuation openings
(stacks) and the cooling walls are not part of the switchgear supply. These components
should be adapted to each type of use.

The gas evacuation kits listed below are available in the


RM6 accessories.

Exhaust Gas to the Rear Adaptation


Classification according to IEC62271-200: IAC A-FL
Internal arc resistance: maxi 24 kV-16 kA.1s.

In the case
evacuation of the SF6 gas after ignition of
the internal arc

70 mm mini
internal arc ignition zone
2000 mm mini

In the cable box


evacuation of the SF6 gas after ignition of
the internal arc
70 mm mini

internal arc ignition zone


2000 mm mini

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 37
Fitting and fixing on the civil engineering RM6 - Civil engineering and installation manual

Exhaust Gas to the Bottom Adaptation Kit


Classification according to IEC62271-200: IAC
A-FLR
Interior arc resistance: maxi 24 kV-20 kA.1s.
CAUTION
All the elements allowing the evacuation of the gas (duct or cable trench and floor)
must be tightness sufficient to withstand pressure and hot gases.
Failure to follow these instructions can result in equipment damage and not
maintain the internal arc performance.

In the case
evacuation of the SF6 gas after ignition of
the internal arc 70 mm mini

internal arc zone ignition zone

2000 mm mini

In the cable box


evacuation of the SF6 gas after ignition of
the internal arc 70 mm mini

internal arc zone ignition zone


2000 mm mini

If possible the downstream compartment should open into a


room that is not used. Otherwise, keep to a minimum volume
of 1.5 m3 before opening.

Validated for Quotation


38 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Fitting and fixing on the civil engineering

Exhaust Gas to the Bottom Adaptation Kit for DE-Mt Cubicle


Classification according to IEC62271-200: IAC A-F
Internal arc resistance: Maxi 24 kV-16 kA.1s.

evacuation of the SF6 gas after ignition of


the internal arc

70 mm mini

internal arc zone ignition zone in the case

2000 mm mini

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 39
Connection instructions RM6 - Civil engineering and installation manual

Connection Instructions
Foreword
CAUTION
● Before connecting the cables, ensure that the functional unit is in the earthing
switch closed position.
● The cables MUST be connected with the RM6 substation fixed to the ground.
● The operations described below apply to all connection types.
● The connections will be made and used according to the manufacturer’s manual.

Connecting the RM6 Frame to the Substation Earth

Before connecting the HV cables, you must connect the RM6 frame to the main earth
bar.

Access to the HV Connection Bushings


Removing the panels

Remove the fuse compartment cover (lift and pull it towards you), then remove the 3
front panels (2 screws per panel).
Remove the 2 top plates on the cable connection compartments (6 screws per plate).
If the cable compartment is equipped with bottom plates (optional supplies), dismantle
the front bottom plate and the tightness horns.

Validated for Quotation


40 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Case of a Compartment with Resistance to Internal Arc

Remove the fuse compartment cover (lift and pull it towards you), then remove the 3
front panels. Remove the 2 top plates from the cable connection compartments (6
screws per plate), then withdraw the internal arc protection (1 plate + 1 insulator), 4
F/90M5 screws.

Type of Usable Connections


The RM6 connection interfaces are defined by draft project EN50181.
The type of connections to be used depend on the interface equipping your RM6.
It is defined when you place your order and depends on very precise criteria such as:
b the current of the connected equipment: 200 A, 400 A, 630 A,
b short-time withstand current: 12,5 KA;16 KA; 25 KA,
b socket type:
□ draw-out: sliding contact,
□ disconnectable: screw-on lug.

CAUTION
● Use the connectors indicated in the catalogue.
● We do not guarantee the dielectric withstand over time if other types of connectors
are used.
● If 2 cables are connected to the same bushing , use connectors designed for this
purpose.

Draw-out Sockets with Controlled Field

Mount on the interface:


b 200 A; 12,5 KA 1s; 31,5 KA peak (A type).
b 400 A; 16 KA 1s; 40 KA peak (B type).
Interface fitted with a sliding contact.
To install the socket at the end of the cable, comply with the accessory manufacturer’s
manual.

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 41
Connection instructions RM6 - Civil engineering and installation manual

Disconnectable Sockets with Controlled Field or Non-controlled Field


Mount on the interface: 630 A ; 25 KA 1s ; 62,5 KA peak (C type)
Interface containing a M16 tapping. To install the socket at the end of the cable, comply
with the accessory manufacturer’s manual.
Tightening torque: refer to the manufacturer’s manual, maximum 50 N.m.

max. 50 N.m

Cable Ends with Heat-shrinkable Elements

max.
50 N.m

Mount on the interface: 630 A; 25 kA 1s; 62,5 kA peak (C type)


Interface containing a M16 tapping.
Tightening torque: refer to the manufacturer’s manual, maximum 50 N.m.
For implementation of heat-shrinkable elements, comply with the accessory
manufacturer’s manual. To thighten the cable end terminal, use a screw M16x40.

Connecting the HV Cables


Preparing the Cable Ends

The curvature and length of the cables must be adjusted so that no stress is exerted on
the connection interfaces. Fit the tightness horns on the cables, if the cable
compartment is equipped with bottom plates. Prepare the cable ends according to the
instructions of the accessory manufacturer.

Validated for Quotation


42 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Instructions
CAUTION
The MV cable characteristics must be taken into account when the connectors are
installed on the product’s bushings. Since no mechanical load is exerted on the
bushing it is possible to guarantee complete absence of damage to the product
during installation.

Recommendation for Connecting Cables


b types of MV cables (single pole or three pole)
The depth of the cable duct must be compatible with the cable’s curvature radius.
Refer to the following chapter «Civil engineering dimensioning».
The unit must fixed to the ground before the MV cables are connected.

Details

INCORRECT ASSEMBLY 1 2

1 CORRECT ASSEMBLY

CAUTION
● Incorrect assembly:
make sure the cable does not pull on the bushing (1) otherwise there is a risk of
damage being caused to the RM6 unit.
● Correct assembly:
it is mandatory to correctly align the plug-in socket (2) on the bushing (1).

In the absence of any mechanical load, the terminal line must be perfectly aligned with
the line of the bushing. Only the tool recommended by the socket manufacturer must
be used to facilitate installation of the socket on the bushings. The cut length of the MV
cable must be adjusted for each phase (three pole cables in particular).

INCORRECT ASSEMBLY

Never use a bar to pull the cable and bring the connection eyelet onto the
bushing. This could damage the bushing and irrevocably damage the unit.

Remember
b Comply with the tightening torque values indicated in the “connection instructions”
chapter.
b When installation of the MV cables is completed, check no load is exerted by
installation of the cable tightening clamps.

The force exerted by the cable on the bushing should not exceed 300 N.m.
(standard IEC 137 and NFC 66-550)

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 43
Connection instructions RM6 - Civil engineering and installation manual

DANGER
The following operation should be performed with the unit
POWERED DOWN.

Methods and Fabrication of Cable Connections for Single Pole


Cables
1

2 mounting screws

1: remove the front bottom panel (a).

2
2
X3

2: cut the incoming cable to the right length. Adjust the


cable length with the bushing of the RM6 unit.
(b)
(c)
3
X3
3

3: slide the horn (b) inside the cable until it is embedded (a)
in the rear bottom panel (c).

Fabrication of Cable Heads


Refer to the socket manufacturer.

(e) (d)

X3

Keep to the alignment between the socket (d) and the bushing (e).

Validated for Quotation


44 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Plugging the Socket on the Bushing


5

X3
6

Before plugging the socket in remember to clean


the bushing and the inside of the socket with a
clean cloth and then lubricate (see details below).

5 bis
X3
6

Grease the inside of the socket.

X3 Grease the bushing


complement.

Cable Clamping

X3
7

18 N.m

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 45
Connection instructions RM6 - Civil engineering and installation manual

Lift up the Front Bottom Panel


8

2 mounting screws
perform the removal actions

Connection for NE 1 Function Cubicle


A: incoming power
B: outgoing power
>150 mm (NE B/D)

703 mm

437 mm A

A B
NE - I

Validated for Quotation


46 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Connection of Cable Earth Straps


A: transformer protection function
B: loop switch function

B
A
B

Connect the earth straps of the 3 cables to the fuse compartment foil acting as the
earth collector (M10 nuts).
Tightening torque: 28 N.m.
Connect the earth straps from the switch’s 3 cables (B) to the flange support acting as
the earth collector (M10 screws).
Tightening torque: 28 N.m.
RM6 encorporating a general cable earth collector (option). Connect the straps to the
collector located at the bottom of the cable compartment.

Installing the Sockets on the RM6 Interfaces


Follow the instructions of the accessory’s
manufacturer.
Make sure you comply with the phases: L1-L2-L3.

In the case of detachable sockets installation of the pin under the fuse compartment.

Before using the silicon lubricant supplied with the connection accessories, clean the
interfaces with a dry cloth.

Cable Clamping Assembly of Bottom Panels


Single pole cable

It is essential to clamp the cables, whatever type of cable is used.


Tightening torque: 18 N.m.
Embed the sealing horns in the rear bottom panel.
Assemble the front bottom panel (4 HM6 screws).

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 47
Connection instructions RM6 - Civil engineering and installation manual

DANGER
The following operation should be performed with the unit
POWERED DOWN.

Methods and Fabrication of Cable Connections for Three Pole Cables


The RM6 unit arrives on the operator’s site equipped with these fittings in order to
connect the cables.

CAUTION
It is recommended to carefully follow the instructions below.

Preparation of the Cable Compartment


Dismantling procedure

1 1 2
(a)

Unscrew the flange support (a), panel (b).

(b)

(a)

2 (c)
(b) (c)

(d)

(d)

Unscrew the 2 front bottom panel screws


(d); they are held in place by the chassis Remember to recover the grommet.
stiffeners (c).

Validated for Quotation


48 Printed on 2018/10/17 07897071EN01-12
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

B
A

D
C
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.
echniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S

Rev
Ind.
1
utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
s plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
nt en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

Date

.
Date Modification / Modification
00 08-03-2018 Edition originale / First issue
2

2 CT WITH 2 SECONDARY WIDINGS


TP CONNECTES A GAUCHE DES TC
and VT diagram

2 TP11 ENROULEMENT SECONDAIRE

VT CONNECTED ON THE LEFT OF CT


2 TC 2 ENROULEMENTS SECONDAIRES

TP CONNECTES A DROITE DES TC

07897071EN01-12
2 CT WITH 2 SECONDARY WINDINGS
filmed
Micro-

VT CONNECTED ON THE RIGHT OF CT


2 TC 2 ENROULEMENTS SECONDAIRES
Rev
Archiv. Ind.
3

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


SANS FUSIBLES

Date
Date
3

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


Correspondence table with CT

2 TP 1 ENROULEMENT SECONDAIRE SANS FUSIBLES


B
A

Modification / Modification

D
echniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
4

utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
s plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

B
A

D
nt en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

Cubicle
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S

.
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and

41
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

Cubicle label

Cubicle label
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

C number

C Cubicle number
2 CT WITH
Drawing number

2 CT WITH
Drawing number
.

Rev
1
RM6 - Civil engineering and installation manual

Diagram CT

PHA2316001

Date
PHA2311901

filmed
PHA2312501
PHA2312001
PHA2312101
PHA2312001
PHA2312001
PHA2312101
PHA2312101

Micro-
Ind. Archiv.
VT CONNECTED

VT CONNECTED
2 TC ON
5

2 SECONDARY

Date Modification / Modification


2 TP 1 ENROULEMENT

00 08-03-2018 Edition originale / First issue


2

2 ENROULEMENTS

2 CT WITH 2 SECONDARY WIDINGS


-

-
-
Diagram VT

TP CONNECTES A GAUCHE DES TC

VT CONNECTED ON THE LEFT OF CT


PHA2311501
PHA2311001
PHA2311001
PHA2311401
PHA2311201
PHA2311401
PHA2311201

MFR3297000

2 TC 2 ENROULEMENTS SECONDAIRES
SINGLE LINE DIAGRAM
52 WINDINGS

OF CT

2 SECONDARY WINDINGS
TP CONNECTES A DROITE DES TC

ON THE RIGHT OF CT
2 CT WITH 2 SECONDARY WINDINGS
6

VT CONNECTED ON THE RIGHT OF CT


THE LEFT SECONDAIRES
PHA2311201 - PHA2312101

PHA2311201 - PHA2312101
filmed
Micro-
63

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


2 TP 1 ENROULEMENT SECONDAIRE SANS FUSIBLES
Rev
Archiv. Ind.
3

PHA23161012 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


SECONDAIRE SANS FUSIBLES

Date
Date

Validated
2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


PHA2319401
PHA2317301
PHA2315301
PHA2316801
PHA2318001
PHA2314701

MFR3325500
7

RM6 DE-MT
SINGLE LINE DIAGRAM
Single line diagram

Printed on 2018/10/17
Modification / Modification
2 7CT
4

for Quotation
Cubicle label

Cubicle label
Cubicle number

Cubicle number
Drawing number

Drawing number
Single line diagram of the different metering cubicle configurations

PHA2315601
PHA2315901
PHA2317401
PHA2315401
PHA2317001
PHA2317701
PHA2314801
PHA2316001 PHA2315901

MFR3325600
8

filmed
Micro-
Archiv.
85
WITH 2 SECONDARY
5

-
-

-
PHA2317501
PHA2315501
PHA2317101
PHA2317901
PHA2314901
PHA2316101

MFR3325700
9

2 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT
VT CONNECTED ON THE RIGHT OF CT
WINDINGS 96

SINGLE LINE DIAGRAM

Project - Order No.


PHA2311201 - PHA2312101

PHA2311201 - PHA2312101
6

Projet - No commande

RM6 DE-MT

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


Rev
2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES

00
PHA2317601
PHA2317201
PHA2318201
PHA2315001
PHA2315601

Indice
MFR3325800
10
Connection instructions

49
Sheet
Folio

003
7
10

PHA2316001
Format SEE A3 suite - 08/2002
B
A

D
C
7

RM6 DE-MT

B
A

D
C
SINGLE LINE DIAGRAM
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

B
A

D
C

Rev
Ind.
1
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

Date
.

Rev
Ind.
1

Date

50
Date Modification / Modification
00 08-03-2018 Edition originale / First issue
TP CONNECTES

Date Modification / Modification


00 08-03-2018 Edition originale / First issue

TP CONNECTES A GAUCHE DES TC

2 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT
2 TC 2 ENROULEMENTS SECONDAIRES

filmed
Micro-
2 A GAUCHE DES TC

2 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT

Rev
Archiv. Ind.
2 TC 2 ENROULEMENTS SECONDAIRES
3
Connection 2instructions

filmed
Micro-

Date
2 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES

Date
2 TP 2 ENROULEMENTS SECONDAIRES SANS FUSIBLES
Rev
Archiv. Ind.
3

2 VT WITH 2 SECONDARY WINDINGS WITH FUSES

Date
Date
2 TP 2 ENROULEMENTS SECONDAIRES AVEC FUSIBLES

Modification / Modification
B
A

D
C
4
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
B
A

Modification / Modification
D
C
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
4

et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and

Rev
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

Ind.
1

Cubicle label
Cubicle label
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

Cubicle number
Cubicle number

2 VT WITH

Drawing number
Drawing number

Rev
Ind.
1

Date

filmed
Micro-
PHA2314901
PHA2314701

Archiv.
Date
filmed
Micro-
Archiv.
Date Modification

Date Modification / Modification


5

2 VT WITH 22 SECONDARY
2 CT WITH 2TPSECONDARY

00 08-03-2018 Edition originale / First issue


2

/ Modification
00 08-03-2018 Edition originale / First issue
2

-
-
-
-

SINGLE LINE DIAGRAM


2 SECONDARY WINDING

CONNECTES A DROITE DES TC


2 CT WITH 2 SECONDARY WINDINGS

2 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT

WINDINGS
VT CONNECTED ON THE LEFT OF CT

VT CONNECTED ON THE RIGHT OF CT


6

TC 2 ENROULEMENTS SECONDAIRES
TP CONNECTES A DROITE DES TC

2 CT WITH 2 SECONDARY WINDINGS

SINGLE LINE DIAGRAM

filmed
Micro-
PHA2311401 - PHA2312101
PHA2311401 - PHA2312101

VT CONNECTED ON THE RIGHT OF CT


2 TC 2 5ENROULEMENTS SECONDAIRES

Rev
Archiv. Ind.
filmed
Micro-
6

Rev
Archiv. Ind.

Date
Date
WITH FUSES
3

2 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES


2 VT WITH 2 SECONDARY WINDINGS WITH FUSES

2 TP 2 ENROULEMENTS SECONDAIRES SANS FUSIBLES


Date
Date

Validated
2 TP 2 ENROULEMENTS SECONDAIRES AVEC FUSIBLES

WINDINGS WITHOUT FUSES


7

RM6 DE-MT
Modification / Modification
SINGLE LINE DIAGRAM
RM6 DE-MT
RM6

Printed on 2018/10/17
4

Modification / Modification
2 VT

SINGLE LINE DIAGRAM


4

for Quotation
Cubicle label
Cubicle label

Cubicle number
Cubicle number

Drawing number
Drawing number
7 - Civil

PHA2315001
PHA2314801

filmed
Micro-
Archiv.
filmed
Micro-
Archiv.
8

5
WITH 2 SECONDARY
engineering

-
-

2 CT WITH 2 SECONDARY WINDINGS


2 CT WITH 2 SECONDARY WINDINGS

SINGLE LINE DIAGRAM


VT CONNECTED ON THE RIGHT OF CT
VT CONNECTED ON THE RIGHT OF CT

Project - Order No.


9

SINGLE LINE DIAGRAM


6

PHA2311401 - PHA2312101
PHA2311401 - PHA2312101

WINDINGS WITH

Projet - No commande
6

RM6 DE-MT
Project - Order No.
5 and installation

Projet - No commande
FUSES

RM6 DE-MT

Rev

00
Indice
10

2 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES

07897071EN01-12
manual

Rev

Sheet
Folio
00

003
Indice

PHA2314901
10

Format SEE A3 suite - 08/2002


7

RM6 DE-MT
B
A

D
C
Sheet
Folio

003
7

RM6 DE-MT

SINGLE LINE DIAGRAM


PHA2314701
Format SEE A3 suite - 08/2002
B
A

D
C

SINGLE LINE DIAGRAM


Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

B
A

D
C
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S

Rev
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and

Ind.
1
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

.
Date

Rev
Ind.
Date
Date Modification / Modification
00 08-03-2018 Edition originale / First issue
2

Date Modification / Modification


00 08-03-2018 Edition originale / First issue
2

3 CT WITH 2 SECONDARY WIDINGS


TP CONNECTES A GAUCHE DES TC
2 TP1 1 ENROULEMENT SECONDAIRE

VT CONNECTED ON THE LEFT OF CT


3 TC 2 ENROULEMENTS SECONDAIRES

TP CONNECTES A DROITE DES TC

07897071EN01-12
3 CT WITH 2 SECONDARY WINDINGS
filmed
Micro-

VT CONNECTED ON THE RIGHT OF CT


3 TC 2 ENROULEMENTS SECONDAIRES
Rev
Archiv. Ind.

filmed
Micro-
3

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


SANS FUSIBLES

Date
Date

Rev
Archiv. Ind.
3

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


2 TP 1 ENROULEMENT SECONDAIRE SANS FUSIBLES

Date
Date
B
A

Modification / Modification
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
4

pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

B
A

Modification / Modification
D
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

Cubicle
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S

Rev
Ind.
4
1

et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

Cubicle label
Cubicle label
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

C number
C Cubicle number

3 CT WITH

Drawing number
Drawing number

Date

Rev
Ind.
2 TP2
RM6 - Civil engineering and installation manual

PHA2317901
PHA2318001

Date
filmed
Micro-
Archiv.
VT CONNECTED

Date Modification

filmed
Micro-
Archiv.
5

Date Modification
/ Modification
3 TC 2 ENROULEMENTS

00 08-03-2018 Edition originale / First issue


2

/ Modification
00 08-03-2018 Edition originale / First issue
2

3 CT WITH 2 SECONDARY WIDINGS

-
-

TP CONNECTES A GAUCHE DES TC


1 ENROULEMENT SECONDAIRE

VT CONNECTED ON THE LEFT OF CT


ON THE SECONDAIRES
1 SECONDARY5 WINDINGS

SINGLE LINE DIAGRAM


LEFT OF CT

3 CT WITH 2 SECONDARY WINDINGS

TP CONNECTES A DROITE DES TC


VT CONNECTED ON THE RIGHT OF CT

3 CT WITH 2 SECONDARY WINDINGS


filmed
Micro-
6

VT CONNECTED ON THE RIGHT OF CT

SINGLE LINE DIAGRAM


3 TC 2 ENROULEMENTS SECONDAIRES
PHA2311201 - PHA2312001
PHA2311201 - PHA2312001

Rev
Archiv. Ind.

filmed
Micro-
6
3

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


SANS FUSIBLES

Date
Date

Rev
Archiv. Ind.
3

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


2 TP 1 ENROULEMENT SECONDAIRE SANS FUSIBLES

Date
Date

Validated
2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


7

RM6 DE-MT

Modification / Modification
SINGLE LINE DIAGRAM
4

RM6 DE-MT

Printed on 2018/10/17
Modification / Modification
SINGLE LINE DIAGRAM
4

for Quotation
Cubicle label

Cubicle label
Cubicle number

Cubicle number
3 7CT WITH
Drawing number

Drawing number
PHA2318201
PHA2317701

filmed
Micro-
Archiv.
8

filmed
Micro-
Archiv.
8
5

2 SECONDARY
-

-
-
9

SINGLE LINE DIAGRAM

3 CT WITH 2 SECONDARY WINDINGS


5 WINDINGS

VT CONNECTED ON THE LEFT OF CT

VT CONNECTED ON THE RIGHT OF CT


9
6

SINGLE LINE DIAGRAM


Project - Order No.
PHA2311201 - PHA2312001

PHA2311201 - PHA2312001
6

Project - Order No.


Projet - No commande

RM6 DE-MT

Projet - No commande

RM6 DE-MT
2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES
2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES

Rev

00
Indice
10
Connection instructions

51
Rev

00
Indice
Sheet
7

Folio

003
10

RM6 DE-MT
PHA2318001
Format SEE A3 suite - 08/2002
B
A

D
C

SINGLE LINE DIAGRAM

Sheet
Folio

003
7

RM6 DE-MT
PHA2317901
Format SEE A3 suite - 08/2002
B
A

D
C

SINGLE LINE DIAGRAM


et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

B
A

D
C

Rev
Ind.
1
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

Date
.

Rev
Ind.
1

Date

52
Date Modification / Modification
00 08-03-2018 Edition originale / First issue
2
TP CONNECTES

Date Modification / Modification


00 08-03-2018 Edition originale / First issue

TP CONNECTES A GAUCHE DES TC

3 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT
3 TC 2 ENROULEMENTS SECONDAIRES

filmed
Micro-
A GAUCHE DES TC

3 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT

Rev
Archiv. Ind.
3 TC 2 ENROULEMENTS SECONDAIRES
3
Connection 2instructions

filmed
Micro-

Date
2 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES

Date
2 TP 2 ENROULEMENTS SECONDAIRES SANS FUSIBLES
Rev
Archiv. Ind.
3

2 VT WITH 2 SECONDARY WINDINGS WITH FUSES

Date
Date
2 TP 2 ENROULEMENTS SECONDAIRES AVEC FUSIBLES

Modification / Modification
B
A

D
C
4
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
B
A

Modification / Modification
D
C
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
4

et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and

Rev
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

Ind.
1

Cubicle label
Cubicle label
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

Cubicle number
Cubicle number

2 VT WITH

Drawing number
Drawing number

Rev
Ind.
1

Date

filmed
Micro-
PHA2317101
PHA2316801

Archiv.
Date
filmed
Micro-
Archiv.
Date Modification

Date Modification / Modification


5

2 VT WITH 23 SECONDARY
3 CT WITH 2TPSECONDARY

00 08-03-2018 Edition originale / First issue


2

/ Modification
00 08-03-2018 Edition originale / First issue
2

-
-
-
-

SINGLE LINE DIAGRAM


2 SECONDARY WINDING

CONNECTES A DROITE DES TC


3 CT WITH 2 SECONDARY WINDINGS

3 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT

WINDINGS
VT CONNECTED ON THE LEFT OF CT

VT CONNECTED ON THE RIGHT OF CT


6

TC 2 ENROULEMENTS SECONDAIRES
TP CONNECTES A DROITE DES TC

3 CT WITH 2 SECONDARY WINDINGS

SINGLE LINE DIAGRAM

filmed
Micro-
PHA2311401 - PHA2312001
PHA2311401 - PHA2312001

VT CONNECTED ON THE RIGHT OF CT


3 TC 2 5ENROULEMENTS SECONDAIRES

Rev
Archiv. Ind.
filmed
Micro-
6

Rev
Archiv. Ind.

Date
Date
WITH FUSES
3

2 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES


2 VT WITH 2 SECONDARY WINDINGS WITH FUSES

2 TP 2 ENROULEMENTS SECONDAIRES SANS FUSIBLES


Date
Date

Validated
2 TP 2 ENROULEMENTS SECONDAIRES AVEC FUSIBLES

WINDINGS WITHOUT FUSES


7

RM6 DE-MT
Modification / Modification
SINGLE LINE DIAGRAM
RM6 DE-MT
RM6

Printed on 2018/10/17
4

Modification / Modification
2 VT

SINGLE LINE DIAGRAM


4

for Quotation
Cubicle label
Cubicle label

Cubicle number
Cubicle number

Drawing number
Drawing number
7 - Civil

PHA2317201
PHA2317001

filmed
Micro-
Archiv.
filmed
Micro-
Archiv.
8

5
WITH 2 SECONDARY
engineering

-
-
-

3 CT WITH 2 SECONDARY WINDINGS


3 CT WITH 2 SECONDARY WINDINGS

SINGLE LINE DIAGRAM


VT CONNECTED ON THE RIGHT OF CT
VT CONNECTED ON THE RIGHT OF CT

Project - Order No.


9

SINGLE LINE DIAGRAM


6

PHA2311401 - PHA2312001
PHA2311401 - PHA2312001

WINDINGS WITH

Projet - No commande
6

RM6 DE-MT
Project - Order No.
5 and installation

Projet - No commande
FUSES

RM6 DE-MT

Rev

00
Indice
10

2 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES

07897071EN01-12
manual

Rev

Sheet
Folio
00

003
Indice

PHA2317101
10

Format SEE A3 suite - 08/2002


7

RM6 DE-MT
B
A

D
C
Sheet
Folio

003
7

RM6 DE-MT

SINGLE LINE DIAGRAM


PHA2316801
Format SEE A3 suite - 08/2002
B
A

D
C

SINGLE LINE DIAGRAM


et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

B
A

D
C

Rev
Ind.
1
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

Date
.

Rev
Ind.
1

Date

Date Modification / Modification


00 08-03-2018 Edition originale / First issue
2
TP CONNECTES

Date Modification / Modification


00 08-03-2018 Edition originale / First issue
2

TP CONNECTES A GAUCHE DES TC

3 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT
3 TC 2 ENROULEMENTS SECONDAIRES

filmed
Micro-

07897071EN01-12
A GAUCHE DES TC

3 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT

Rev
Archiv. Ind.
3 TC 2 ENROULEMENTS SECONDAIRES
3
RM6 - Civil engineering

filmed
Micro-

Date
2 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES

Date
2 TP 2 ENROULEMENTS SECONDAIRES SANS FUSIBLES
Rev
Archiv. Ind.
2 VT WITH 2 SECONDARY WINDINGS WITH FUSES

Date
Date
2 TP 2 ENROULEMENTS SECONDAIRES AVEC FUSIBLES
B
A

Modification / Modification
D
C
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S

4
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

Modification / Modification

B
A

D
C
.

Rev
Ind.
1

Les informations techniques contenues dans ce docu ment sont la propriete exclusive de Schneider Elec tric Industries S.A.S The technical information contained in this docu ment is the exclusive property of Schneider Electr ic Industries S.A.S
4

et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. S euls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après en registrement de la commande. Les appareils représen tés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

Cubicle label
Cubicle label
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mech anism discharged and all power sources off.

Date

Cubicle number
Cubicle number

3 VT WITH
2 CT WITH

Drawing number
Drawing number

Rev
Ind.
1
and3 installation manual

filmed
Micro-
PHA2315501
PHA2315301

Archiv.
Date
VT CONNECTED

00 08-03-2018 Edition originale


Date Modification /filmed
Micro-
5

Archiv.

Modification
/ First issue
2

2 TC 2 ENROULEMENTS
5

3 VT WITH 2 SECONDARY
2 CT WITH 2 SECONDARY

Date Modification / Modification


00 08-03-2018 Edition originale / First issue
2

3 TC 2 ENROULEMENTS
-
-
-
-

TP CONNECTES A GAUCHE DES TC

2 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT

SINGLE LINE DIAGRAM


2 SECONDARYSECONDAIRES
WINDINGS

WINDINGS
TP CONNECTESWINDINGS
ON THE RIGHT OF CT

VT CONNECTED ON THE RIGHT OF CT


filmed
Micro-
6

A GAUCHE DES TC

3 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE LEFT OF CT
SINGLE LINE DIAGRAM

PHA2311401 - PHA2312001
PHA2311401 - PHA2312001

Rev
Archiv. Ind.

3 TP 2 ENROULEMENTS SECONDAIRES
SECONDAIRES
3
6

filmed
Micro-
Date
3 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES

Date
3 TP 2 ENROULEMENTS SECONDAIRES SANS FUSIBLES

Rev
Archiv. Ind.
3 VT WITH 2 SECONDARY WINDINGS WITH FUSES
3
2 SECONDARY WINDINGS WITH FUSES

Date
Date

Validated
WITHOUT FUSES
7

RM6 DE-MT
Modification / Modification

Modification /
SINGLE LINE DIAGRAM
4
7

RM6 DE-MT

Printed on 2018/10/17
Modification
SINGLE LINE DIAGRAM
4

for Quotation
Cubicle label

Cubicle label
Cubicle number

Cubicle number
Drawing number

Drawing number
filmed
Micro-
PHA2317301
PHA2315401

Archiv.
8

filmed
5

Micro-
Archiv.
8

5
-
-

-
9

SINGLE LINE DIAGRAM

3 CT WITH 2 SECONDARY WINDINGS


2 CT WITH 2 SECONDARY WINDINGS

VT CONNECTED ON THE LEFT OF CT


VT CONNECTED ON THE LEFT OF CT
6

Project - Order No.


SINGLE LINE DIAGRAM
Connection

PHA2311001 - PHA2312101

PHA2311001 - PHA2312001

Projet - No commande
6

RM6 DE-MT
Project - Order No.
Projet - No commande

3 VT WITH 2 SECONDARY WINDINGS WITH FUSES


RM6 DE-MT

Rev

00
Indice
10
3 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES
9 instructions

53
Rev

Sheet
Folio
00

003
7

SINGLE LINEIndice
RM6 DE-MT

PHA2317101
10

Format SEE A3 suite - 08/2002


B
A

D
C
Sheet
DIAGRAM
Folio

003
7

RM6 DE-MT
PHA2316801
Format SEE A3 suite - 08/2002
B
A

D
C

SINGLE LINE DIAGRAM


Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S

B
A
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and

D
C
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and

.
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

Rev
Ind.
1
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

Rev
Ind.
1

Date
Date

54
Date Modification / Modification
00 08-03-2018 Edition originale / First issue
2

Date Modification / Modification


00 08-03-2018 Edition originale / First issue
3 TP 2 ENROULEMENTS

TP CONNECTES A DROITE DES TC

2 CT WITH 2 SECONDARY WINDINGS


VT CONNECTED ON THE RIGHT OF CT
TP CONNECTES A DROITE DES TC

2 TC 2 ENROULEMENTS SECONDAIRES
3 CT WITH 2 SECONDARY WINDINGS

filmed
Micro-
VT CONNECTED ON THE RIGHT OF CT
3 TC 2 ENROULEMENTS SECONDAIRES
Connection 2instructions

filmed

Rev
Micro-

Archiv. Ind.
SECONDAIRES AVEC

Rev
Archiv. Ind.

Date
Date
3

2 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES


3 VT WITH 2 SECONDARY WINDINGS WITH FUSES

2 TP 2 ENROULEMENTS SECONDAIRES SANS FUSIBLES


Date
Date
3 FUSIBLES

Modification / Modification
4

Modification / Modification

B
A
B
A

D
C
D
3 VT
Cubicle
exclusive
Les informations techniques contenues dans ce docu ment sont la propriete exclusive de Schneider Elec tric Industries S.A.S The technical information contained in this docu ment is theLes property
informations of Schneider
techniques contenues ic Industries
Electrdans ce document
S.A.S sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
4

et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. S euls nous engagent without
and cannot be used or disclosed to third parties of any kindet its written
ne peuvent etre consent.
utilisees Only those drawings
ou divulguees a desand
tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après en registrement de la commande. Les appareils représen tés diagrams remitted after order booking are binding for execution.
pourAll devices shown
execution les plansin this diagrams
et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams

Cubicle label

Cubicle label
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mech anism discharged and all
sur ce schéma power
sont en position
sourcesouvert
off. - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

C number

Cubicle number
Drawing number

Drawing number

.
.

Rev
Rev

Ind.
Ind.
1
1

PHA2317601
PHA2317401

Date
Date

Date
VT CONNECTED

filmed
Micro-
Micro-
2 TCON

Archiv.
00 08-03-2018 Edition
5
WITH 2 SECONDARY
3 CT WITH 2 SECONDARY
5

3 VT WITH 2 SECONDARY
3 CT WITH 2 SECONDARY

WITH OPEN DELTA


Date Modification / Modification

Archiv. Modification / Modification


2 TP 1 ENROULEMENT

filmed originale / First issue

00 08-03-2018 Edition originale / First issue


2
2

2 ENROULEMENTS

2 TC 1 ENROULEMENTS
-
-

AVEC TRIANGLE OUVERT


WINDINGS

WINDINGS
TP CONNECTESWINDINGS

SINGLE LINE DIAGRAM


TP CONNECTES A DROITE DES TC
OF CT

VT CONNECTED ON THE RIGHT OF CT


A DROITE DES TC
2 CT WITH 2 SECONDARY WINDINGS

2 CT WITH 1 SECONDARY WINDINGS


VT CONNECTED ON THE RIGHT OF CT

SINGLE LINE DIAGRAM

VT CONNECTED ON THE RIGHT OF CT


6

THE RIGHTSECONDAIRES
PHA2311001 - PHA2312001

PHA2311401 - PHA2312101

SECONDAIRES
WINDINGS WITH
6

filmed
filmed

Micro-
Micro-

Rev
Rev

Archiv. Ind.
Archiv. Ind.
3
3

3 VT WITH 2 SECONDARY WINDINGS WITH FUSES


FUSES

2 VT WITH 1 SECONDARY WINDING WITHOUT FUSES


SECONDAIRE SANS FUSIBLES

Date
Date

Date
Date

Validated
3 TP 2 ENROULEMENTS SECONDAIRES AVEC FUSIBLES

WITHOUT FUSES

Modification /
7

RM6 DE-MT
RM6 DE-MT
RM6

Printed on 2018/10/17
SINGLE LINE DIAGRAM

Modification
Modification / Modification
SINGLE LINE DIAGRAM
4

for Quotation
4

Cubicle label

Cubicle label
Cubicle number

Cubicle number
Drawing number

Drawing number
PHA2319401
PHA2317501

WITH OPEN DELTA

filmed
filmed

Micro-
Micro-

Archiv.
Archiv.
8

3 VT WITH 2 SECONDARY
5
5
7 - Civil engineering

-
-

2 CT WITH 1 SECONDARY WINDING


3 CT WITH 2 SECONDARY WINDINGS
VT CONNECTED ON THE LEFT OF CT

VT CONNECTED ON THE RIGHT OF CT


9

SINGLE LINE DIAGRAM


SINGLE LINE DIAGRAM
PHA2311201 - PHA2312101

PHA2312501 - PHA2311501

Project - Order No.


6
6

Project - Order No.


and installation

Projet - No commande

RM6 DE-MT
Projet - No commande

RM6 DE-MT

Rev

00
3 VT WITH 2 SECONDARY WINDINGS WITHOUT FUSES

Indice
WINDINGS9 WITHOUT FUSES 10

07897071EN01-12
manual

Rev

00
Indice
SINGLE
10

Sheet
Folio

003
PHA2315001
Format SEE A3 suite - 08/2002
LINESheet
Folio

003
7

B
A

D
C
7

RM6 DE-MT
RM6 DE-MT
PHA2317401
Format SEE A3 suite - 08/2002
B
A

D
C

SINGLE LINE DIAGRAM


DIAGRAM
et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind withoutetits
newritten
peuventconsent. Only those
etre utilisees drawings and
ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés devices
diagrams remitted after order booking are binding for execution. Allpour execution in this
shown les diagrams
plans et schémas remis après enregistrement de la commande. Les appareils représentés diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged sur and all power
ce schéma sources
sont en position
off. ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

.
Rev

Rev
Ind.

Ind.
1
1

Date

Date
Date Modification / Modification

Date Modification / Modification


0 01-10-2018 Edition originale / First issue

0 01-10-2018 Edition originale / First issue


2

TP CONNECTES A DROITE DES TC


TP CONNECTES A DROITE DES TC

3 CT WITH 1 SECONDARY WINDING


3 CT WITH 1 SECONDARY WINDING

3 TC 1 ENROULEMENT SECONDAIRE
3 TC 1 ENROULEMENT 2SECONDAIRE

VT CONNECTED ON THE RIGHT OF CT


VT CONNECTED ON THE RIGHT OF CT

filmed

07897071EN01-12
filmed
Micro-

Micro-
3 VT WITH 1 SECONDARY WINDING WITH FUSES
3 VT WITH 1 SECONDARY WINDING WITH FUSES

Rev

Rev
Archiv. Ind.

Archiv. Ind.
3
3

3 TP 1 ENROULEMENT SECONDAIRE AVEC FUSIBLES


3 TP 1 ENROULEMENT SECONDAIRE AVEC FUSIBLES

Date

Date
Date

Date
Modification /
Modification / Modification

Modification
B
A
B
A

D
C
D
C
Les informations techniques contenues dans ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive Les informations
property techniques
of Schneider contenues
Electric dans
Industries ce document sont la propriete exclusive de Schneider Electric Industries S.A.S The technical information contained in this document is the exclusive property of Schneider Electric Industries S.A.S
S.A.S
4

et ne peuvent etre utilisees ou divulguees a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its ne peuvent
et written consent. utilisees
etreOnly those ou divulguees
drawings and a des tiers quels qu'ils soient sans son accord écrit. Seuls nous engagent and cannot be used or disclosed to third parties of any kind without its written consent. Only those drawings and
pour execution les plans et schémas remis après enregistrement de la commande. Les appareils représentés pour execution
diagrams remitted after order booking are binding for execution. All devices shown in this plans et schémas remis après enregistrement de la commande. Les appareils représentés
les diagrams diagrams remitted after order booking are binding for execution. All devices shown in this diagrams
sur ce schéma sont en position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism dischargedsur andce allschéma
power sources
sont enoff.position ouvert - désarmés - débrochés - toutes sources coupées. are in open position, drawn out with operating mechanism discharged and all power sources off.

.
.

Rev
Rev

Ind.
Ind.
1

Cubicle label
Cubicle label

Date
Date

Cubicle number
Cubicle number

34 VT WITH

TP
3 VT WITH
3 CT WITH
Drawing number
Drawing number

3 TP
RM6 - Civil engineering and installation manual

filmed

filmed
Micro-

Micro-
MFR3325700
MFR3325500

Date Archiv.

Date Archiv.
CONNECTES
5
5

Modification / Modification
Modification / Modification
3 TC 1 ENROULEMENT

0 01-10-2018 Edition originale / First issue


0 01-10-2018 Edition originale / First issue
2

1 SECONDARY

11SECONDARY
3 TC11SECONDARY
DROITE DES
TP CONNECTES A DROITE DES TC

TC
3 CT WITH 1 SECONDARY WINDING

-
-
-
-

3 CT WITH 1 SECONDARY WINDING


2SECONDAIRE

ENROULEMENT SECONDAIRE
ENROULEMENT SECONDAIRE
VT CONNECTED ON THE RIGHT OF CT

VT CONNECTED ON THE RIGHT OF CT

SINGLE LINE DIAGRAM


SINGLE LINE DIAGRAM
3 CT WITH 1 SECONDARY WINDING

WINDING
WINDING
AVEC
VT CONNECTED ON THE RIGHT OF CT

VT CONNECTED ON THE RIGHT OF CT


6

filmed
Micro-
filmed
Micro-
WINDING WITH

MFR3297000- PHA2311901

WITH
3 VT WITH 1 SECONDARY WINDING WITH FUSES
MFR3297000 - PHA2311901

3 VT WITH 1 SECONDARY WINDING WITH FUSES

Rev
Rev

Archiv. Ind.
Archiv. Ind.
3

3
3 TP 1 ENROULEMENT SECONDAIRE AVEC FUSIBLES

FUSIBLES

Date
Date

Date
Date
FUSES

FUSES

Validated
Modification /

Modification /
7

RM6 DE-MT
RM6 DE-MT

Modification
Modification

SINGLE LINE DIAGRAM


SINGLE LINE DIAGRAM
4

Printed on 2018/10/17
for Quotation
Cubicle label
Cubicle label

Cubicle number
Cubicle number

Drawing number
Drawing number

filmed
filmed

Micro-
Micro-
MFR3325800
MFR3325600

Archiv.
Archiv.
8
8
5

5
34 VT WITH 1 SECONDARY
-
-

-
9
9

WINDING

SINGLE LINE DIAGRAM

3 CT WITH 1 SECONDARY WINDING


3 CT WITH 1 SECONDARY WINDING

SINGLE LINE DIAGRAM


VT CONNECTED ON THE RIGHT OF CT
VT CONNECTED ON THE RIGHT OF CT
6
6

Project - Order No.

Project - Order No.


WITH
MFR3297000 - PHA2311901

MFR3297000 - PHA2311901

Projet - No commande
Projet - No commande

RM6 DE-MT

RM6 DE-MT
3 VT WITH 1 SECONDARY WINDING WITH FUSES
FUSES

Rev

Rev
00

00
Indice
Indice
10
10
Connection instructions

55
Sheet

Sheet
Folio
Folio

003

003
7
7

RM6 DE-MT

RM6 DE-MT
MFR3325700
MFR3325500

Format SEE A3 suite - 08/2002


Format SEE A3 suite - 08/2002

B
A

D
C
B
A

D
C

SINGLE LINE DIAGRAM

SINGLE LINE DIAGRAM


Connection instructions RM6 - Civil engineering and installation manual

Reminder
For the rest of the intervention, you must be positioned as shown in
the illustration below.

Correct Visual
You must have in your possession the following 3 items:
(a): “horn” grommet
(b): front bottom plate
(c): cable flange support

(a)

(b)

(c)

Cable Fabrication for Three Pole Cable

Cut the incoming cable to the right length.


Adjust the cable length with the bushing of the RM6
unit.
4

4 (a)

Slide the horn (a) inside the cable until it is


embedded in the rear bottom panel (d). (d)

Validated for Quotation


56 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Fitting the Cable Flange Support

5
(e)

5
Fix the cable flange support (c) under the rear
bottom panel using the 2 screws (e).

(c)

(c)

Plugging the Socket on the Bushing


6

X3
6

Before plugging the socket in remember to clean


the bushing and the inside of the socket with a clean
cloth and then lubricate (see previous section). 6

Cable Clamping

18 N.m

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 57
Connection instructions RM6 - Civil engineering and installation manual

Reassemble the Front bottom Panel


8

(b)

2 mounting screws perform the


removal actions in reverse order

(b)

Fitting the Panels

Fit the 2 top plates on the cable connection compartments, (6 screws per HM6X16
plate). If the cable compartment is fitted with an internal arc protection, put back the
protection.
Ensure that you respect the layers: 1 plate + 1 insulator + top plate.

Access to the MV Compartment

Put back the front panels on the cable connection compartments (2 HM6x16 screws
per panel). Put back the fuse compartment cover.

Access to the LV Compartment

Open the LV compartment access trunking by removing the 6 HM6X16 screws.


Remove the trunking vertically.

Validated for Quotation


58 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

LV Compartment Customer Power supply for DE-Mt Cubicle

DANGER
The following operation should be performed with the unit
POWERED DOWN.

Without LV Compartment

sealable screw

HM6.12 screw
1

customer power supply

1: Remove the 6 HM6.12 screws, and the 2 sealable


screws.
2
2: LV connecting terminal

Access Preparation Customer LV Power Supply


Drill a hole in the LV compartment sheeting (A) to the desired diameter.

CAUTION
To avoid all risk of damage, the drilling zones must be respected.

Top view

35 35

200 565 225


37

2
80

1 3
110
120

12
1, 2, 3, 4: AUTHORISED DRILLING ZONE
4
7
85

290

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 59
Connection instructions RM6 - Civil engineering and installation manual

Customer Connection Example


1: power supply cable provided by the customer 1

CAUTION
The customer connection must guarantee a protection index of IP3X.

Current Transformer (CT) Intensities and Temperatures for DE-Mt


Cubicle
CAUTION
CHECK and RESPECT:
● The maximum allowable intensity: this depends on the type of CT
(and primary ratio used).
● The maximum ambient temperature: this depends on the type of CT installed.

Intercubicle Link

Wiring passage

Wiring passage

RM6 DE- Mt

Validated for Quotation


60 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Switch, Circuit-breaker, Earthing Switch Indication


2O + 2F B

Marking the Connection Terminal Block

1 2 3 4 5 6 7 8 14 15 16

Position of the closed HV switch: terminals 1-2 and 5-6.


Position of the open HV switch: terminals 3-4 and 7-8.
Position of the closed earthing switch: terminals 16-15.
Position of the open earthing switch: terminals 14-16.

Fuse Blowing Indication (optional supply)


A: marking the connection terminal block
A
24 25 26

Fault Tripping Indication (optional supply)


Circuit-breaker Function Only
A: marking the connection terminal block
A
20 21

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 61
Connection instructions RM6 - Civil engineering and installation manual

Tripping Coil (optional supply)


The operation of this accessory is guaranteed for a supply voltage of +10% and -15%
of nominal voltage.

Marking the Connection Terminal Block

CAUTION
Follow the polarity of the 24 Vdc coil.

+
_ +
_
22 23 22 23

Gear Motor on Switch-fuse Combination or Switch or Circuit-breaker Operating Mechanism


The operation of this accessory is guaranteed for a supply voltage of +10% and -15%
of nominal voltage.

connection terminal block


A Connection terminal block

power supply
- +

A
9 10 11 12 13

close open

Validated for Quotation


62 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Pressure Switch Connection


The pressure switch checks the pressure of the RM6 unit and transmits the data via 2
auxiliary contacts: ”Level 1” and ”Level 2”.

Pressure Switch Functional Table


Pressure ”P” of the RM6 unit contact status contact status Pressure check on LCD display
(absolute bar) “Level 1” “Level 2” (”DENSITY SWITCH” button(2))
P > 1,08 bar Closed Closed Case n° 1: OK
1,04 bar < P ± 1,08 bar Closed Open Case n° 2: OK/LOW
P ± 1,04 bar Open Open Case n° 3 : NOT OK/VERY LOW

(2) see “Checks before energising”

This data is available by connection (B):


bb 4 wires available under the cable trough for connection to a terminal defined by the
customer for remote relay of the RM6 unit pressure status:
□□ wires N°3 and 4: “Level 1” auxiliary contact
□□ wires N°7 and 8: “Level 2” auxiliary contact

A: heat-shrinkable sheath
B: customer power supply (please refer to the ”Contacts characteristics” table)
C: GMD 216 pressure switch
D: pressure switch display

4 7
C

3 8
A

CLIC !

Contact characteristics
See “Start-up instructions”.

Operating voltage Inductive load (A)


24 Vdc 2,0 L/R = 20 msec
48 Vdc 1,0 L/R = 20 msec
127 Vdc 0,5 L/R = 20 msec
220 Vdc 0,15 L/R = 20 msec
100-240 Vac 1

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 63
Connection instructions RM6 - Civil engineering and installation manual

Connecting a Sepam 10 Relay


The accessories fitted to the circuit-breaker must be identified before connecting the
relay:
bb type of Sepam fitted to your RM6 (identified by the code on the front panel of the
Sepam)
bb RM6 circuit-breaker type:
□□ 200 A
□□ 630 A
bb whether the circuit-breaker is fitted with a motor operating mechanism.

1: identification code
1
2: supply voltage

Interpreting the Identification Code


Note the following information:

Sepam 10

Sepam 10 family

Model
B: phase and earth current maximum protection settings
Sepam model: A or B A: phase and earth current maximum protection
settings, logic inputs and communication port

Number of current inputs


4: 3 phase current inputs + 1 earth current input

Sensitivity of earth current maximum protection


1: standard (0.1...24 In) CT
Presence of a CSH200 3: very sensitive (0.2...24 A and 2...240 A) CSH200
core balance CT
Supply voltage
A: 24...125 V DC and 100...120 V AC
Supply voltage E: 110...250 V DC and 100...240 V AC

Using this information, connect the relay in accordance with the appropriate wiring
diagram (below).
Connection of the inputs/outputs and the power supply to the circuit-breaker are made
on terminal block (A). The Sepam and circuit-breaker accessories have a common
supply.

Validated for Quotation


64 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Motor Operated circuit-breaker type B or D with Sepam 0A + MX


Standard sensibility

CAUTION
Respect voltage and polarity.

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 65
Connection instructions RM6 - Civil engineering and installation manual

Sensitive earth default

Validated for Quotation


66 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Connecting customer terminal bloc

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 67
Connection instructions RM6 - Civil engineering and installation manual

Motor Operated Circuit-breaker Type B or D with Sepam 10B + MX


Standard sensibility

CAUTION
Respect voltage and polarity.

Validated for Quotation


68 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Sensitive earth default

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 69
Connection instructions RM6 - Civil engineering and installation manual

Connecting customer terminal bloc

Validated for Quotation


70 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Circuit-breaker Type B or D with Sepam 10B + MX


Standard sensibility

CAUTION
Respect voltage and polarity.

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 71
Connection instructions RM6 - Civil engineering and installation manual

Sensitive earth default

Validated for Quotation


72 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Connecting customer terminal bloc

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 73
Connection instructions RM6 - Civil engineering and installation manual

Circuit-breaker Type B or D with Sepam 10A + MX


Standard sensibility

CAUTION
Respect voltage and polarity.

Validated for Quotation


74 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Sensitive earth default

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 75
Connection instructions RM6 - Civil engineering and installation manual

Connecting customer terminal bloc

Validated for Quotation


76 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Connecting the communication port


The Sepam 10A is able to communicate via a 2-wire EIA RS 485 communication port.
Connection to bus connector C is made directly without accessories.
A daisy chain connection is used which requires a 150 Ω end of line resistor.
Resistor ref: VW3A8306DR

Terminals Connected Information Description


1 C: common Terminal connected to 0V of the communication interface
2 S: shielding Terminal connected to the Sepam earthing terminal
3 D0 Terminal to be connected to terminal A (or L-) of the supervisor port
4 D1 Terminal to be connected to terminal B (or L+) of the supervisor port

Connection is made directly to the Sepam connector C.

C C

Connecting a CSH200 core balance CT


The core balance CT must only measure the sum of the phase currents. The currents
circulating in the screens of the 3 HV cables must be excluded.
Pass the screens’ earthing braid through the CT. Check the direction the braid passes
through the CT.

CAUTION
The CSH200 is not MV insulated. It should be fitted to the part of the cable with the
earthed screen.
Serious injury may result if this instruction is not followed.

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 77
Connection instructions RM6 - Civil engineering and installation manual

Connection
Position the CSH200 under the RM6, in the duct, or if this is not possible, in the raising
block. Use the pre-mounted shielded cable that is inside the RM6 HV connection
compartment.

VIP400 / VIP410 Connection


All the VIP connectors can be accessed on the rear panel. They are removable.

Identification of the connectors on the rear panel


A: connector for the auxiliary power supply and output relays O1 to O3 (VIP410)
B: connector for the self powered supply
C: 2-wire RS 485 communication port (VIP410)
D: connector for the Mitop trip unit
E: connector for the phase and earth fault current inputs
F: connector for the sensitive earth fault current and external trip inputs (VIP410)
: protective earth

Validated for Quotation


78 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Connecting the Auxiliary Power Supply and Outputs O1 to O3 (VIP410)


Connection characteristics

DANGER
HAZARD OF FIRE
● Ensure the product phase (L) and neutral (N) are correctly connected
to the installation.
● Failure to follow these instructions can result in death, serious injury,
or equipment damage.
● In the phase (L) and neutral (N) connections are swapped over, there is a risk of
fire in the event of internal product failure.

ref. diagram wiring type of screwdriver tightening


terminal torque
A b wiring without fittings: M2.5 2.5 mm 0,4...0,5
□ 1 wire: 0,2...2,5 mm2 (AWG 24...12) screw flat N.m
□ 2 wires: 0,2...1 mm2 (AWG 24...18) blade (3.5...4.4
□ stripped length: 8...10 mm (0.31...0.39 (0.09 in.) lbin.)
in.)

b wiring with fittings:


□ 1 1,5 mm2 wire (AWG 16) with
DZ5CE015D fitting
□ 1 2,5 mm2 wire (AWG 12) with
DZ5CE025D fitting
□ 2 1 mm2 wire (AWG 18) with
DZ5CE010D fitting
□ stripped length: 8 mm (0.31 in.)

Connecting a core balance CT (VIP410)


The specifically designed CSH120, CSH200, GO110 and CSHU core balance CTs are
for direct earth fault current measuement. They should be used with the VIP410 for
very sensitive earth fault protection.
They can be connected to 2 earth fault current inputs with different sensitives:
b 10-240 A input
b 1-24 A input
For detailed characteristics of core balance CTs, refer to the following sections:
b CSH120, CSH200 and GO110 core balance CTs
b CSHU core balance CT
NOTE: the CSHU CT is dedicated to operation in a Premset switchboard. It is
integrated in the switchgear in the factory.

Connection diagram
The diagram below shows the connection of a core balance CT to measure the earth
fault current:

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 79
Connection instructions RM6 - Civil engineering and installation manual

Connection precautions
Connect terminal 3 of connector F to earth.
bb Connect the CT secondary to terminals 6 and 4 (10-240 A rating) or to terminals 5
and 4 (1-24 A rating).
bb Flatten the cable against the metal frames of the cubicle.
bb Connect the cable shielding (terminal 4) in the shortest manner possible to the
protective earth of connector F.
bb Do not ground the cable by any other means.
For more information about the CT wiring, refer to the CSH120, CSH200 and GO110
Core Balance CTs section..

ref. core wiring type of screwdriver tightening


balance CT terminal torque
F CSH120, CSH200, GO110 bb sheathed cable shielded by tinned M2.5 Plat 0,4...
copper strap screw 2,5 mm 0,5 N.m
bb minimum cable cross-section: 0.93  mm2 (0.09 in.) (3.5...
(AWG 18) 4.4 lb-in.)
bb linear resistance: <100 m /m (30.5 m /ft)
bb minimum dielectric withstand: 1000 V
(700 V RMS)
CSHU Supplied with the CSHU CT

Note: the maximum resistance of the VIP410 connection wiring must not exceed 4 Ω
(i.e. 20 m maximum for 100 mΩ/m or 66 ft pour 30.5 mΩ/ft).

Connection of the External Trip Input (VIP410)


The VIP410 has an external trip input that can be used to take account of a trip order
issued by an external protection device (Buchholz, gas, pressure, temperature
detectors).

Caractéristiques de raccordement
Connect both pins on the external protection device volt - free contact to terminals 1
and 2 on connector F.

ref. diagram wiring type of screwdriver tightening


terminal torque
F bb wiring without fittings: M2.5 Plat 0,4...0,5
□□ 1 wire: 0,2...2,5 mm2 (AWG24...12) screw 2,5 mm N.m
□□ maximum length: 2 x 50 m (0.09 in.) (3.5...4.4
□□ stripped length: 8...10 mm (0.31...0.39 lbin.)
in.)
bb wiring with fittings:
□□ 1 wire 1,5 mm2 (AWG 16) with
DZ5CE015D fitting
□□ 1 wire 2,5 mm2 (AWG 12) with
DZ5CE025D fitting
□□ stripped length: 8 mm (0.31 in.)

Connecting the Modbus Communication Port (VIP410)


The VIP410 can communicate using a 2-wire RS 485 Modbus communication port.
Connection to the Modbus network is direct, via an RJ45 connector.

Connection diagram
Connection to the Modbus network is in a daisy-chain and requires a line termination
resistor: depending on the bus configurations, daisy-chain wiring can require the use
of a Modbus branching box.
In cases where the VIP410 is used with SC100 modules (control and monitoring of MV
equipment), daisy-chain wiring is created directly by these modules using the 3 RJ45
connectors present (“T” Modbus function).

Modbus termination
Junction Junction Junction Junction
box box box box

Validated for Quotation


80 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Connection precautions
Connect the Modbus network RJ45 cable to connector C on the VIP410.
NOTE: the number of connected VIP410s must not exceed 31 and the total cable
length must not exceed 500 m so that the maximum network speed (38.4 kbps) can be
used.

Recommended connection accessories


description length reference
Modbus RJ45 cable 0,3 m VW3 A8 306 R03
1m VW3 A8 306 R10
3m VW3 A8 306 R30
Modbus line termination - VW3 A8 306 RC
Modbus branching box - TWDXCAT3RJ

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 81
Connection instructions RM6 - Civil engineering and installation manual

Installing an ATS (Automatic Transfer System)


This unit automatically manages the power sources for the distribution network
upstream of T200 to ensure the availability of the power supply downstream in case of
failure of one of the sources.

ACO Function
ACO (Auto Change Over) is an automatic power source switching function with two
incoming lines (SW1 and SW2).
bb Network ATS: changeover between two MV network sources (SW1 and SW2)
bb Generator ATS between a distribution system line and a generator (SW1 and SW2)

Operating mode
When the power is lost on the line in service, switch-over to the other line is automatic.
One line can be given priority over the other, with return or not to the priority line if
necessary.

Single Line Diagram of an AOC Function


A: power supply
B, C, D: controle cables
E, F: fault detection cables

RM6 pre- equipped with ATS

I D I

M M
Cables fault detection

T200I Interface Interface


terminal block terminal block

A BC DEF VPIS-V0 VPIS-V0

SPLIT SPLIT
SENSORS SENSORS

SW1 SWG SW2


G

Other Functions
ATS in ON/OFF mode:
The ATS system can be switched ON or OFF from the local control panel (T200I) or
remotely (SCADA system).

ATS in parallel mode upon Auto return:


Enables paralleling of the channels during the phase of automatic return to the priority
channel (allows return to the main line without any power interruption).

Generator ON override command:


Activation of the ATS and transfer on Generator can be activated upon an order.
Allows periodic maintenance tests of the ATS/Generator system for example.

Validated for Quotation


82 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

BTA Function
BTA (Bus Tie Automatism) is an automatic power source switching function with 2
incoming lines (SW1 and SW2) and a coupler switch (SW3).

Operating Mode
Standard mode:
When the power is lost on one line, the automatic function opens the line in question
and closes the coupler switch. The coupler switch is conditioned by the absence of
fault current on the main power source.
Locking mode after loss of power following switch-over:
After automatic switch-over in standard mode, the power supply is checked over a
configurable period. If the power is lost during this period, the SW3 coupler switch is
opened and the automatic function is locked.

SINGLE LINE DIAGRAM OF AN BTA FUNCTION 2/3


Fault detection cables
Control cables
Power supply

Interface Interface
terminal terminal
block block

Split sensors Split sensors

CAUTION
The switching function will not work with faulty batteries. Remember to check the
T200I batteries regularly (see T200I manual).

Installing an ATS/ACO
The following equipment is required in order to install an ATS with ACO (Auto Change
Over).
b RM6 pre-equipped for the ATS function
b 1T200I support kit
b 1T200I (TI04M - ABBM22)
b 2 pilot wires
b 2 CTs (optional split sensors or pre-equipped)
b 2 wires for CTs

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 83
Connection instructions RM6 - Civil engineering and installation manual

Fitting the T200I Support Kit


CAUTION
Do not transport the RM6 + T200I once assembled.

The kit can be fitted to the left or right of the RM6. The T200I earthing cable (A)
should be connected to the RM6 earth bar.

Installing the T200I and Connecting it to the RM6


Fit the RM6 connection cables (A) and connect them to the interface terminals (B) in
the RM6 LV compartment.

CAUTION
Take care with channel markings and mismatch. The ACO unit is only available on
channels 1 and 2 of the T200I.

Validated for Quotation


84 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Switch Wiring Diagram


INTERFACE TEMINAL BLOCK

1
VD23
2
3
4
5
6
7
VPIS VO
8
9
AVAILABLE
SWITCH MOTOR

AVAILABLE
10

Fitting the T200I Enclosure


Fit the T200I and earth the enclosure (diameter 8 earth stud). Use the instructions on
the CD supplied with the T200I to:
bb fit and connect the core balance CTs;
bb fit and connect the battery;
bb connect the AC supply.

Locking the Source Transfer


This input makes it possible to forbid commands from:
bb the local control panel;
bb the automatic switching function;
bb the supervisor.

To be wired to terminal J1 of the T200I, terminals 1-2.


RM6 circuit-breaker complete with a Sepam 10 relay, terminals 29-30.
RM6 circuit-breaker complete with a VIP relay, terminals 20-21.

Locking
the source transfer
Channels 1 to 4 fault
reset output
Channels 1 to 4
external
indicator lamp

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 85
Connection instructions RM6 - Civil engineering and installation manual

Detection Sequence (ATS/VD23)


Configuration: voltages V1,V2,V3, direct mode
R1: terminal = relay rest position: threshold paramater
voltage loss on at least one of the phases
R2: terminal = relay rest position: voltage presence
on at least one of the phases

A configurable time delay is applied for control of R1


and R2:
T12 = time delay for R1 changeover upon voltage loss
T11 = time delay for R1 changeover upon voltage
recovery
T21 = time delay for R2 changeover upon voltage loss
T22 = time delay for R2 changeover upon voltage
recovery

Indicator
Indicator

Suggested Choice for VD23 Settings


Voltage detector Earthed or impedant grounding Isolated neutral Compensated neutral

3 4 5 6
SW 1 V1+V2+V3+V0
V1.V2.V3.V0
SW 2
R1
VD23

3 4 5 6 3 4 5 6
SW 1 U12+U13+U23 U12+U13+U23
U12.U13.U23. U12.U13.U23.
SW 2
R1

Recommendated settings thresholds


Phase voltage detection 50%
Voltage detection - residual earth fault voltage 54%

T200I specific settings


For each channel, set the control and automation parameters
Access ’ Control & Automation configuration.

RM6 control settings


Standard control Standard
Await return of switch command position time delay 5000 ms
Await return of circuit-breaker command position time 14000 ms
delay
Non-complementarity filtering time delay 3000 ms
Operating time delay 500 ms

Validated for Quotation


86 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Mode selection Measuring


mode
Product Software
Test mode name version
Network frequency Digits test

ou

Type of Relay Phase Phase Phase Residual


measurement output 1 2 3 voltage
Configuration mode
Parameters defined line- to- line inverted measured measured measured measured
by micro switches

line- to- neutral direct not not not not


measured measured measured measured
Phase voltage % of nominal voltage
Parameters setup threshold
to
(10% increments)
mode
Voltage Residual voltage to % of nominal voltage
To set the parameter presence threshold (10% increments)
values, see the 0 to 1 s (0.1s increments)
Activation time
section below to 1 to 21 s (2s increments)
delay R1 (direct)
Release time delay 0 to 1 s (0.1s increments)
to 1 to 3 s (0.5s increments)
R1 (direct)

Phase voltage % of nominal voltage


à (10% increments)
threshold
Voltage Activation time 0 to 1 s (0.1s increments)
absence à
delay R2 (direct) 1 to 21 s (2s increments)
Release time delay 0 to 1 s (0.1s increments)
à
R2 (direct) 1 to 3 s (0.5s increments)

Automatic Set to OFF to retain the last calibration


Calibration mode or
calibration performed

Forced Calibration performed normally


1s
calibration Error in calibration:
voltage levels too low

Parameter Display (ATS/VD23)


The and buttons allow navigation in the parameter tree structure in accordance
with the following diagram. At any time, a press on the “Esc” key (Return) allows you to
return to the preceding stage.

Configuration of Thresholds and Time Delays(ATS/VD23)


The parameter values (white screen in the above diagram) can be modified as follows:
bb when the value of the parameter is displayed, a press on the key causes the
display to flash for 5 s;
bb during flashing, press successively to display the desired value;
bb confirm this value by pressing the ; button; without confirmation within a period of
15 s, return to display of the parameters without change in the value. Each press on
the “Esc” button takes you back to the preceding stage.

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 87
Connection instructions RM6 - Civil engineering and installation manual

VD23 Relay Only


Wiring of VD23 when there is no 48V DC motor.

INTERFACE TEMINAL BLOCK

1
VD23
2
3
4
R1 5
6
7
VPIS VO
8
9
Available
MANUFACTURING WIRE 10
Available

Wiring reference according configuration or installation type

R1 R2
24V - 48V
+ -
A

13 14 15 16 17 18 19 20

VD23

Fault current detector selectivity


The Imax and Io thresholds must be configured corresponding to those configured on
the protection of the upstream system circuit-breaker.
The thresholds and time delays to be configured on the T200I must be slightly lower
than those of the upstream circuit-breaker protection in order to allow the T200I to
detect the presence of the fault current before the upstream circuit-breaker opens.
For the other parameters, use the instruction manual on the CD supplied with
the T200I.

Validated for Quotation


88 Printed on 2018/10/17 07897071EN01-12
RM6 - Civil engineering and installation manual Connection instructions

Remote Control
Connecting the RM6 to the Talus 200 remote control interface
A: TALUS 200 remote control interface
B: connectors (of the Harting type)
C: connecting leads

Cabling a connecting lead


D: RM6 terminal block
E: connection lead D 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
F: harting contact pin

F 5 4 2 3 1 6 7

Polarisation of the HARTING connectors


Trunnion positions
(pin side views)

PLUG CONNECTORS
1 6 1 6 1 6 1 6
2 7 2 7 2 7 2 7
SOCKET CONNECTORS
3 8 3 8 3 8 3 8
4 9 4 9 4 9 4 9
polarisation is archived by screw-on runnions 5 10 5 10 5 10 5 10

6 1 6 1 6 1 6 1
7 2 7 2 7 2 7 2
8 3 8 3 8 3 8 3
9 Y 4 9 Y 4 9 Y 4 9 Y 4
10 5 10 5 10 5 10 5

Validated for Quotation


07897071EN01-12 Printed on 2018/10/17 89
Notes RM6 - Civil engineering and installation manual

Validated for Quotation


90 Printed on 2018/10/17 07897071EN01-12
Validated for Quotation
Printed on 2018/10/17
Schneider Electric
35, rue Joseph Monier
92500 Rueil Malmaison - France
Tél.: +33 (0)1 41 29 70 00
www.schneider-electric.com

As standards, specifications and designs change from time


to time, please ask for confirmation of the information given
in this publication.

© 2018 Schneider Electric. All rights reserved.

07897071EN01-12 - 10/2018
Validated for Quotation