LVMCC Budgetary Checklist

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 3

LV MCC Budgetary Checklist

Per Lineup (if Different) provide the following information. Check all that apply.

1. Service Voltage and Neutral (if required): ___480_ Voltage __60____HZ (x ) Neutral Bus

2. Short Circuit Rating: ( ) 42KAIC or Below (x ) 43KAIC to 65KAIC ( ) 66KAIC to 100KAIC

3. Nema Wiring Class Type: ( ) Class I (x ) Class II-2B ( ) BD ( ) BT ( ) C ( ) IA ( ) IA EXPRESS

4. MCC Mounting: (x ) Front Only ( ) Back to Back

5. Incoming Method: ( ) MLO (x ) Main CB ( ) Main Switch ( x ) Transition to Swbd or XFRM


( ) Bus Duct. If Splice to existing we will not provide budgetary, contact factory.

a. Note: Transition to Utility Arizona Public Service

6. If Main CB also Specify if Req:( x )Long Time ( x )Short Time ( x )Instantaneous ( x )GF ( x )SE
Rated

7. Incoming Cables: QTY__2___ Size / MCM__500_____ ( ) Top Entry ( x ) Bottom Entry

8. Specify Main Metering if required: ( x ) PQM II ( ) PL2000 ( ) Analog Voltmeter & Ammeter

9. Main Bus Rating: ( x ) 600A ( ) 800A ( ) 1200A ( ) 2000A ( ) 2500A

10. Main Bus: ( x ) Tin-CU ( ) Silver ( ) Insulated

11. Vertical Bus Rating: ( ) 300A ( x ) 600A ( ) 850A (Requires 1200A Main Bus or Higher)

12. Ground Bus Rating: (x ) 300A ( ) 600A ( ) Vertical Ground Bus ( ) Unit / Load GND Lug

13. Enclosure Type: ( ) NEMA 1G ( ) NEMA 1HG ( ) UL TYPE 12 ( ) NEMA 2 ( x ) NEMA 3R NWI

14. Enclosure Options: ( x ) Vertical Bus Shutters (x ) Section Space Heaters ( ) Rodent Barriers
( ) Bottom Plates ( x ) Structural Floor Sills ( ) Rear Main Bus Barriers

15. Unit Options: ( x ) Standard wire ( ) SIS Wire for ( ) Control ( ) Power
Wiremarkers for (x ) Control ( ) Power ( x ) Standard Wiremarkers ( ) Heat Shrunk
Wire Termination ( ) Standard ( x ) Ring ( ) Spade for ( x ) Control ( )Power

16. Feeder Disconnect Options: ( ) Fused switch ( x ) Thermal Mag CB


( ) Aux Contacts ( ) CB Shunt Trip ( ) CB Bell Alarm ( ) GF

17. Feeders: Frame Amp Size ______20A/3P_________ Trip Amps________ QTY ___1____
Frame Amp Size _______60A/2P________ Trip Amps________ QTY ___1____
Frame Amp Size _______________ Trip Amps________ QTY _______
Frame Amp Size _______________ Trip Amps________ QTY _______
Frame Amp Size _______________ Trip Amps________ QTY _______
Frame Amp Size _______________ Trip Amps________ QTY _______

18. Starter Control Power: ( x ) CPT ( ) Separate Source ( ) Line to Line

19. Starter Disconnect Options: ( ) Fused switch (x ) Mag Only CB ( ) Thermal Mag CB
( ) CB or Fused Switch Aux Contacts ( ) CB Shunt Trip ( ) CB Bell Alarm

20. Starter Control Options: ( ) FV Lights ( ) XFMR Lights ( x ) LED ( x ) P-T-T ( x ) Run Lt ( x ) Stop
Lt ( x ) Start PB ( x ) Stop PB ( x ) HOA Switch ( x ) ETM (x ) Coil Suppressors ( ) Ammeter
( ) Current Transducer Relays will be our STD C2000 ( x )Control QTY _9__ (x ) Timers QTY
_4__

21. Starter Motor Protection Type (For Starters other than VFD’s and SSS which will use their
internal electronic OL): ( ) Bimetallic OL ( ) Ambient Bimetallic OL
( ) STD Electronic CR324X OL ( ) MM200 ( x ) MM300 ( ) Ground Fault

a. Equivalent to Eaton MP3000

22. Communications (If Req): ( ) Modbus RS485 ( ) Devicenet ( x ) Ethernet TCP/IP ( ) Profibus

23. Starters: Types are FVNR, FVR, RVAT, 2S2W, 2S1W (2 Speeds Specify VT, CT or CH)

Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______


Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______
Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______
Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______
Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______
Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______
Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______
Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______
Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______
Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______
Type ____________ ( ) CT ( ) VT ( ) CH HP _______ QTY ______

24. VFD’s & SSS’s: VFD (Specify CT, VT, LF, ISO and/or BP) SSS (Specify HD if req’d and ISO and/or BP)

Type _RVSS___ ( ) ISO ( x ) BP ( ) CT ( ) VT ( ) HD ( ) LF HP _250____ QTY _1____


Type ________ ( ) ISO ( ) BP ( ) CT ( ) VT ( ) HD ( ) LF HP _____ QTY _____
Type ________ ( ) ISO ( ) BP ( ) CT ( ) VT ( ) HD ( ) LF HP _____ QTY _____
Type ________ ( ) ISO ( ) BP ( ) CT ( ) VT ( ) HD ( ) LF HP _____ QTY _____
Type ________ ( ) ISO ( ) BP ( ) CT ( ) VT ( ) HD ( ) LF HP _____ QTY _____
Type ________ ( ) ISO ( ) BP ( ) CT ( ) VT ( ) HD ( ) LF HP _____ QTY _____
Type ________ ( ) ISO ( ) BP ( ) CT ( ) VT ( ) HD ( ) LF HP _____ QTY _____
Type ________ ( ) ISO ( ) BP ( ) CT ( ) VT ( ) HD ( ) LF HP _____ QTY _____
Type ________ ( ) ISO ( ) BP ( ) CT ( ) VT ( ) HD ( ) LF HP _____ QTY _____
Type ________ ( ) ISO ( ) BP ( ) CT ( ) VT ( ) HD ( ) LF HP _____ QTY _____

25. Special Options: ( ) FOB ( ) Export Box ( ) Extended Warranty ____ Yrs
( ) Customer Witness Test and/or Inspection.

Nomenclature

MLO = Main Lugs Only


CB = Circuit Breaker
Swbd = Switchboard
XFMR = Transformer
Req = Required GF
= Ground Fault SE =
Service Entrance FV =
Full Voltage P-T-T
= Push To Test Lt =
Light ISO =
Line Isolation Contactor
BP = Bypass Contactor
VT = Variable Torque
CT = Constant Torque
CH = Constant Horsepower
HD = Heavy Duty Rated
HP = Horsepower
QTY = Quantity