Per Lineup (if Different) provide the following information. Check all that apply.
1. Service Voltage and Neutral (if required): ___480_ Voltage __60____HZ (x ) Neutral Bus
6. If Main CB also Specify if Req:( x )Long Time ( x )Short Time ( x )Instantaneous ( x )GF ( x )SE
Rated
8. Specify Main Metering if required: ( x ) PQM II ( ) PL2000 ( ) Analog Voltmeter & Ammeter
11. Vertical Bus Rating: ( ) 300A ( x ) 600A ( ) 850A (Requires 1200A Main Bus or Higher)
12. Ground Bus Rating: (x ) 300A ( ) 600A ( ) Vertical Ground Bus ( ) Unit / Load GND Lug
13. Enclosure Type: ( ) NEMA 1G ( ) NEMA 1HG ( ) UL TYPE 12 ( ) NEMA 2 ( x ) NEMA 3R NWI
14. Enclosure Options: ( x ) Vertical Bus Shutters (x ) Section Space Heaters ( ) Rodent Barriers
( ) Bottom Plates ( x ) Structural Floor Sills ( ) Rear Main Bus Barriers
15. Unit Options: ( x ) Standard wire ( ) SIS Wire for ( ) Control ( ) Power
Wiremarkers for (x ) Control ( ) Power ( x ) Standard Wiremarkers ( ) Heat Shrunk
Wire Termination ( ) Standard ( x ) Ring ( ) Spade for ( x ) Control ( )Power
17. Feeders: Frame Amp Size ______20A/3P_________ Trip Amps________ QTY ___1____
Frame Amp Size _______60A/2P________ Trip Amps________ QTY ___1____
Frame Amp Size _______________ Trip Amps________ QTY _______
Frame Amp Size _______________ Trip Amps________ QTY _______
Frame Amp Size _______________ Trip Amps________ QTY _______
Frame Amp Size _______________ Trip Amps________ QTY _______
19. Starter Disconnect Options: ( ) Fused switch (x ) Mag Only CB ( ) Thermal Mag CB
( ) CB or Fused Switch Aux Contacts ( ) CB Shunt Trip ( ) CB Bell Alarm
20. Starter Control Options: ( ) FV Lights ( ) XFMR Lights ( x ) LED ( x ) P-T-T ( x ) Run Lt ( x ) Stop
Lt ( x ) Start PB ( x ) Stop PB ( x ) HOA Switch ( x ) ETM (x ) Coil Suppressors ( ) Ammeter
( ) Current Transducer Relays will be our STD C2000 ( x )Control QTY _9__ (x ) Timers QTY
_4__
21. Starter Motor Protection Type (For Starters other than VFD’s and SSS which will use their
internal electronic OL): ( ) Bimetallic OL ( ) Ambient Bimetallic OL
( ) STD Electronic CR324X OL ( ) MM200 ( x ) MM300 ( ) Ground Fault
22. Communications (If Req): ( ) Modbus RS485 ( ) Devicenet ( x ) Ethernet TCP/IP ( ) Profibus
23. Starters: Types are FVNR, FVR, RVAT, 2S2W, 2S1W (2 Speeds Specify VT, CT or CH)
24. VFD’s & SSS’s: VFD (Specify CT, VT, LF, ISO and/or BP) SSS (Specify HD if req’d and ISO and/or BP)
25. Special Options: ( ) FOB ( ) Export Box ( ) Extended Warranty ____ Yrs
( ) Customer Witness Test and/or Inspection.
Nomenclature