Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 2

TEST REPORT FOR AUXILIARY RELAY

PLANT NAME DATE


PANEL NAME PANEL NO
RELAY MAKE AUX VOLT
OPERATING VOLTAGE

PICK UP TEST:

PICK UP VOLTS
RELAY MODEL NO RELAY SERIAL NO
LH MID RH

Remarks: Tested & found ok.

TEST REPORT FOR FEEDER PROTECTION RELAY TYPE: 7SJ62


PLANT NAME MSDS#5 DATE 15.11.2016
PANEL NAME (TR-15 LV-2 BOARD) NET FEEDER (NGT) PANEL NO 504
RELAY MODEL NO AUX VOLT
RELAY SERIAL NO RELAY MAKE
OPERATING
VOLTAGE
SERVICE SETTING:

Secondary Injection Test:

EARTH O/C

Set Current (A) Operating Current (A) Set Time (sec) Operating Time (sec)
3.0 3.0 0.60 0.60
PHASE O/C:
I>:
Set Current (A) Operating Current (A) Set Time (sec) Operating Time (sec)
20.0 20.0 0.15 0.15

Remarks: Tested & found ok.

You might also like