Download as pdf or txt
Download as pdf or txt
You are on page 1of 31

1.1 Electrical Networks and Protections 1.

1 Electrical Networks and Protections


Introduction : electrical networks Introduction : electrical networks
and protection systems and protection systems
APPS APPS

Olivier Richardot Olivier Richardot


Issue A Issue A
Last modification : april 2011 Last modification : april 2011

Summary
y Summary
y

What is an electrical network? What is an electrical network?


Network architecture and components Network architecture and components
El t i l ffaults
Electrical lt and
d th
their
i consequences El t i l ffaults
Electrical lt and
d th
their
i consequences
Role and constitution of a protection system Role and constitution of a protection system
Required qualities of a protection system
y Required qualities of a protection system
y
The main protection’s families The main protection’s families

Schneider Electric - Energy Automation – Technical Institute 2 Schneider Electric - Energy Automation – Technical Institute 2
What is an electrical network? What is an electrical network?
Network architecture and components Network architecture and components
Electrical faults and their consequences Electrical faults and their consequences
Role and constitution of a protection system Role and constitution of a protection system
Required qualities of a protection system Required qualities of a protection system
The main protection’s families The main protection’s families

Schneider Electric - Energy Automation – Technical Institute 3 Schneider Electric - Energy Automation – Technical Institute 3

What is an electrical network ? What is an electrical network ?

Electrical network carry electricity from production centers to consumers Electrical network carry electricity from production centers to consumers

Schneider Electric - Energy Automation – Technical Institute 4 Schneider Electric - Energy Automation – Technical Institute 4
Electrical networks hierarchyy Electrical networks hierarchyy

Transmission and interconnection Transmission and interconnection


400 kV – 225 kV – 150 kV 400 kV – 225 kV – 150 kV

Repartition Repartition
90 kV – 63 kV 90 kV – 63 kV

Distribution
Di t ib ti Distribution
Di t ib ti
20 kV – 15 kV – 6 kV 20 kV – 15 kV – 6 kV
230-400 V 230-400 V

Schneider Electric - Energy Automation – Technical Institute 5 Schneider Electric - Energy Automation – Technical Institute 5

Standard voltage
g levels Standard voltage
g levels

NF C18
C18-510
510 Un IEC 60038 NF C18
C18-510
510 Un IEC 60038

EHV EHV
HTB 230 kV HTB 230 kV
HV HV
50 kV 50 kV
35 kV 35 kV
HTA HTA
MV MV

BTB
1 kV BTB
1 kV
500 V 500 V
BTA BTA
LV LV
50 V 50 V
TBT TBT
Schneider Electric - Energy Automation – Technical Institute 6 Schneider Electric - Energy Automation – Technical Institute 6
French network French network

Schneider Electric - Energy Automation – Technical Institute 7 Schneider Electric - Energy Automation – Technical Institute 7

Electrical networks protection


p Electrical networks protection
p

● Why do we need to protect transmission and distribution networks? ● Why do we need to protect transmission and distribution networks?
● Structures costs and strategic aspect of product « electricity » ● Structures costs and strategic aspect of product « electricity »
● Availability,
Availability continuity
continuity, quality of service ● Availability,
Availability continuity
continuity, quality of service
● Profitability and materials life duration ● Profitability and materials life duration

● Why do we need to protect industrial networks? ● Why do we need to protect industrial networks?
● Workmen
Workmen’s
s safety ● Workmen
Workmen’s
s safety
●Potential differences between earth points → risks of electric shock or ●Potential differences between earth points → risks of electric shock or
electrocution electrocution
● Materials protection ● Materials protection
●Flashover arcs → risks of fire or explosion ●Flashover arcs → risks of fire or explosion
●Overloads → risks of damage or destruction ●Overloads → risks of damage or destruction
● Operation
O ti continuity
ti it ● Operation
O ti continuity
ti it

Schneider Electric - Energy Automation – Technical Institute 8 Schneider Electric - Energy Automation – Technical Institute 8
Short-circuit on a 225 kV cable Short-circuit on a 225 kV cable

Schneider Electric - Energy Automation – Technical Institute 9 Schneider Electric - Energy Automation – Technical Institute 9

What is an electrical network? What is an electrical network?


Network architecture and components Network architecture and components
Electrical faults and their consequences Electrical faults and their consequences
Role and constitution of a protection system Role and constitution of a protection system
Required qualities of a protection system Required qualities of a protection system
The main protection’s families The main protection’s families

Schneider Electric - Energy Automation – Technical Institute 10 Schneider Electric - Energy Automation – Technical Institute 10
Meshed grids: transmission and Meshed grids: transmission and
repartition repartition
Mesh, or loop Mesh, or loop

B Tie-connection B Tie-connection
C C

A A

D D
E E

G G

H H

F F

Close tie-connection Close tie-connection


Schneider Electric - Energy Automation – Technical Institute 11 Schneider Electric - Energy Automation – Technical Institute 11

Meshed grids: transmission and Meshed grids: transmission and


repartition repartition

Schneider Electric - Energy Automation – Technical Institute 12 Schneider Electric - Energy Automation – Technical Institute 12
Radial g
grids: distribution Radial g
grids: distribution
Overhead distribution networks: Overhead distribution networks:
● Rural zones MV
● Rural zones MV
● Low load concentration source
NO ● Low load concentration source
NO

● Low implementation cost simple


i l spur liline ● Low implementation cost simple
i l spur liline

Underground distribution networks: NO NO NO Underground distribution networks: NO NO NO


MV WC MV WC
● Urban or mixed zones source BC ● Urban or mixed zones source BC
NO NO
● High load concentration double spur line ● High load concentration double spur line

● High continuity of service ● High continuity of service

MV
main ring MV MV
main ring MV
source source source source
NO NO

Schneider Electric - Energy Automation – Technical Institute 13 Schneider Electric - Energy Automation – Technical Institute 13

Electric p
power p
plants Electric p
power p
plants

● Component of the network which provides electric power to the network ● Component of the network which provides electric power to the network
● Alternators moved by different primary energy sources ● Alternators moved by different primary energy sources
● Predominantly centralized production, distributed generation being ● Predominantly centralized production, distributed generation being
more and more important with market deregulation more and more important with market deregulation

G G

Schneider Electric - Energy Automation – Technical Institute 14 Schneider Electric - Energy Automation – Technical Institute 14
Sources: statistic data (France)
( ) Sources: statistic data (France)
( )

● data from French Utility RTE at end of 2009 ● data from French Utility RTE at end of 2009

thermal nuclear 63.1 GW thermal nuclear 63.1 GW

thermal classic 26.1 GW thermal classic 26.1 GW

hydraulic 25.4 GW hydraulic 25.4 GW

wind-power 4.6 GW wind-power 4.6 GW

other renewables 1 2 GW
1.2 other renewables 1 2 GW
1.2

Schneider Electric - Energy Automation – Technical Institute 15 Schneider Electric - Energy Automation – Technical Institute 15

Cruas-Meysse
y nuclear plant
p ((France)) Cruas-Meysse
y nuclear plant
p ((France))

Schneider Electric - Energy Automation – Technical Institute 16 Schneider Electric - Energy Automation – Technical Institute 16
Transmission lines Transmission lines

● Component of the network dedicated to electric energy transmission ● Component of the network dedicated to electric energy transmission
from a node to an other from a node to an other
● Three-phase lines made of one to four wire per phase, eventually ● Three-phase lines made of one to four wire per phase, eventually
added
dd d up withith an earth
th wire
i added
dd d up withith an earth
th wire
i
● Transit power linked to permanent maximal admissible current, and to ● Transit power linked to permanent maximal admissible current, and to
static stability
y limit static stabilityy limit

Schneider Electric - Energy Automation – Technical Institute 17 Schneider Electric - Energy Automation – Technical Institute 17

Lines: statistic data (France)


( ) Lines: statistic data (France)
( )

● Transmission and repartition grid (data from RTE at end of 2009) ● Transmission and repartition grid (data from RTE at end of 2009)
270 kV CC 4 underground connections: 117 km (FA2000) 270 kV CC 4 underground connections: 117 km (FA2000)

400 kV overhead:
h d 21 279 k
km underground:
d d 3 km
k 400 kV overhead:
h d 21 279 k
km underground:
d d 3 km
k

225 kV overhead: 25 568 km underground: 970 km 225 kV overhead: 25 568 km underground: 970 km

150 kV overhead: 1 061 km underground: 2 km 150 kV overhead: 1 061 km underground: 2 km

90 kV overhead: 14 963 km underground: 499 km 90 kV overhead: 14 963 km underground: 499 km

63 kV overhead: 33 656 km underground : 2 135 km 63 kV overhead: 33 656 km underground : 2 135 km

● Distribution grid (data from French distrib. Utility ERDF at end of 2009) ● Distribution grid (data from French distrib. Utility ERDF at end of 2009)
HTA overhead: 363 600 km underground : 235 650 km HTA overhead: 363 600 km underground : 235 650 km

BT overhead: 426 800 km underground : 248 500 km BT overhead: 426 800 km underground : 248 500 km
Schneider Electric - Energy Automation – Technical Institute 18 Schneider Electric - Energy Automation – Technical Institute 18
France-Spain
p 400 kV interconnection France-Spain
p 400 kV interconnection

Schneider Electric - Energy Automation – Technical Institute 19 Schneider Electric - Energy Automation – Technical Institute 19

Substations Substations

● Component of the network allowing control,


control dispatching and ● Component of the network allowing control,
control dispatching and
transmission of electric energy on different voltage levels transmission of electric energy on different voltage levels
● Bus-bars to which are connected spans (or cubicles), lines and ● Bus-bars to which are connected spans (or cubicles), lines and
t
transformers
f t
transformers
f
● Presence of break and disconnect devices allowing separation of ● Presence of break and disconnect devices allowing separation of
different network sections different network sections

Schneider Electric - Energy Automation – Technical Institute 20 Schneider Electric - Energy Automation – Technical Institute 20
Substations: main components
p Substations: main components
p

feeder measurementt feeder measurementt


circuit-breaker circuit-breaker
transformers transformers

bus-bar bus-bar

li and
line d ground
d li and
line d ground
d
disconnect switch disconnect switch

selector selector
disconnect disconnect
protection; switch protection; switch
control-command control-command
Schneider Electric - Energy Automation – Technical Institute 21 Schneider Electric - Energy Automation – Technical Institute 21

Substations: main components


p Substations: main components
p

bus-bar longitudinal CB bus-bar longitudinal CB


VT “Bus-Tie” VT “Bus-Tie”

LGS CB LGS CB

CT CT

bus-bar
bus bar bus-bar
bus bar
voltage voltage
control control

switch bus-bar isolator switch switch bus-bar isolator switch


bus-bar bus-bar
selector selector

CVT CVT

bus coupler bus coupler


Schneider Electric - Energy Automation – Technical Institute 22 Schneider Electric - Energy Automation – Technical Institute 22
Substations: statistic data (France)
( ) Substations: statistic data (France)
( )

● HV substations (data from RTE at end of 2009) ● HV substations (data from RTE at end of 2009)
270 kV CC 2 HVDC stations (FA2000) 270 kV CC 2 HVDC stations (FA2000)

400 kV 142 substations


b t ti 400 kV 142 substations
b t ti

225 kV 536 substations 225 kV 536 substations

150 kV 27 substations 150 kV 27 substations

90 kV 516 substations 90 kV 516 substations

63 kV 1291 substations 63 kV 1291 substations

● MV substations (data from French distrib. Utility ERDF at end of 2009) ● MV substations (data from French distrib. Utility ERDF at end of 2009)
Public MV distribution HV/MV 2 200 substations Public MV distribution HV/MV 2 200 substations

Public LV distribution MV/LV 734 000 substations Public LV distribution MV/LV 734 000 substations
Schneider Electric - Energy Automation – Technical Institute 23 Schneider Electric - Energy Automation – Technical Institute 23

400 kV substation 400 kV substation

Schneider Electric - Energy Automation – Technical Institute 24 Schneider Electric - Energy Automation – Technical Institute 24
What is an electrical network? What is an electrical network?
Network architecture and components Network architecture and components
Electrical faults and their Electrical faults and their
consequences consequences
Role and constitution of a protection system Role and constitution of a protection system
Required qualities of a protection system Required qualities of a protection system
Th main
The i protection’s
t ti ’ families
f ili Th main
The i protection’s
t ti ’ families
f ili

Schneider Electric - Energy Automation – Technical Institute 25 Schneider Electric - Energy Automation – Technical Institute 25

Short-circuits Short-circuits

Short-circuits that may appear on the networks are of different kinds... Short-circuits that may appear on the networks are of different kinds...

1-phase-to- 2-phase-(to- 3-phase-(to- 1-phase-to- 2-phase-(to- 3-phase-(to-


ground ground) ground) ground ground) ground)

Schneider Electric - Energy Automation – Technical Institute 26 Schneider Electric - Energy Automation – Technical Institute 26
Short-circuits Short-circuits

... and can have various origins. ... and can have various origins.

i t
internal
l external
t l i t
internal
l external
t l
● maneuver over voltages ● lightning shocks ● maneuver over voltages ● lightning shocks
● isolators deterioration ● ice, snow, dust ● isolators deterioration ● ice, snow, dust
● resonance, ferroresonance ● branches, animals ● resonance, ferroresonance ● branches, animals
● broke conductors ● excavation engines ● broke conductors ● excavation engines
● ... ● vehicle collisions ● ... ● vehicle collisions
● ... ● ...

Schneider Electric - Energy Automation – Technical Institute 27 Schneider Electric - Energy Automation – Technical Institute 27

Short-circuits: examples of risky Short-circuits: examples of risky


sit ations
situations sit ations
situations

Schneider Electric - Energy Automation – Technical Institute 28 Schneider Electric - Energy Automation – Technical Institute 28
Short-circuits: statistic data (France)
( ) Short-circuits: statistic data (France)
( )

● data from ‘Techniques de l’Ingénieur’ ● data from ‘Techniques de l’Ingénieur’


transmission & interconnection 15.2 faults per 100 km per year transmission & interconnection 15.2 faults per 100 km per year
mono 83 % mono 83 %
poly 17 % poly 17 %

repartition 37.5 faults per 100 km per year repartition 37.5 faults per 100 km per year
mono 68 % mono 68 %
poly 32 % poly 32 %

distribution (MV) 150 faults per 100 km per year distribution (MV) 150 faults per 100 km per year
mono 64 % mono 64 %
poly 36 % poly 36 %
Schneider Electric - Energy Automation – Technical Institute 29 Schneider Electric - Energy Automation – Technical Institute 29

Schneider Electric - Energy Automation – Technical Institute 30 Schneider Electric - Energy Automation – Technical Institute 30
Other electric faults Other electric faults

● Sustained overloads ● Sustained overloads


isolator deterioration (over-heating) that may lead to perforation isolator deterioration (over-heating) that may lead to perforation

● Over voltages ● Over voltages


straight-front transient, origin from atmosphere straight-front transient, origin from atmosphere
transient maneuver regime transient maneuver regime
industrial frequency industrial frequency
arcing arcing

● Unbalances ● Unbalances
rupture of a conductor rupture of a conductor
unbalanced load unbalanced load
vibrations over-heating
vibrations, over heating of rotating machines vibrations over-heating
vibrations, over heating of rotating machines

Schneider Electric - Energy Automation – Technical Institute 31 Schneider Electric - Energy Automation – Technical Institute 31

Consequences:
q voltage
g dips
p Consequences:
q voltage
g dips
p

A short-circuit has as a major consequence to impose to healthy A short-circuit has as a major consequence to impose to healthy
elements a lower voltage than the minimal admissible voltage in normal elements a lower voltage than the minimal admissible voltage in normal
operation operation

Driving torque proportional to squared voltage Driving torque proportional to squared voltage
AsM  slowing down and risk of stalling AsM  slowing down and risk of stalling

Disturbance of P and Q flows Disturbance of P and Q flows


G  risk of loss of synchronism G  risk of loss of synchronism

Schneider Electric - Energy Automation – Technical Institute 32 Schneider Electric - Energy Automation – Technical Institute 32
Consequences
q g
: overvoltages Consequences
q g
: overvoltages

● A one-phase-to-ground fault with ● A one-phase-to-ground fault with


isolated or impedant neutral leads isolated or impedant neutral leads
to a voltage rise on healthy phases to a voltage rise on healthy phases

● Opening a circuit (with self) on a ● Opening a circuit (with self) on a


short-circuit current generates a short-circuit current generates a
temporary overvoltage  temporary overvoltage 

Schneider Electric - Energy Automation – Technical Institute 33 Schneider Electric - Energy Automation – Technical Institute 33

q
Consequences: g
contact voltages q
Consequences: g
contact voltages

● Fault between phase(s) and grounded metallic mass(es) ● Fault between phase(s) and grounded metallic mass(es)

difference off potentials


diff i l between
b metallic ( ) and
lli mass(es) d ground
dddue difference off potentials
diff i l between
b metallic ( ) and
lli mass(es) d ground
dddue
to current flow through resistances to current flow through resistances

Uc Uc

Uc Uc

Schneider Electric - Energy Automation – Technical Institute 34 Schneider Electric - Energy Automation – Technical Institute 34
What is an electrical network? What is an electrical network?
Network architecture and components Network architecture and components
Electrical faults and their consequences Electrical faults and their consequences
Role and constitution of a protection Role and constitution of a protection
system system
Required qualities of a protection system Required qualities of a protection system
Th main
The i protection’s
t ti ’ families
f ili Th main
The i protection’s
t ti ’ families
f ili

Schneider Electric - Energy Automation – Technical Institute 35 Schneider Electric - Energy Automation – Technical Institute 35

Role of a p
protection system
y Role of a p
protection system
y

The role of a protection system is to: The role of a protection system is to:
● detect and clear quickly any electric fault on the network ● detect and clear quickly any electric fault on the network
● separate faulty part of the network only ● separate faulty part of the network only
● signal any abnormal operation condition ● signal any abnormal operation condition
● limit operation interruptions and electric fault consequences ● limit operation interruptions and electric fault consequences
● optimize the network operation ● optimize the network operation

Schneider Electric - Energy Automation – Technical Institute 36 Schneider Electric - Energy Automation – Technical Institute 36
Constitution Constitution

Protection is realized by de-energizing the faulty element, according to Protection is realized by de-energizing the faulty element, according to
voltage level and installation power voltage level and installation power

fuses contactors circuit breakers fuses contactors circuit breakers

Schneider Electric - Energy Automation – Technical Institute 37 Schneider Electric - Energy Automation – Technical Institute 37

Protection principle
p p Protection principle
p p

The protection relay is a continuous network electric state monitoring The protection relay is a continuous network electric state monitoring
device, which controls breaking systems via « break » (NC), or device, which controls breaking systems via « break » (NC), or
« make » (NO) switches « make » (NO) switches
ure

ure
nd

nd
comman

comman
measu

protect. signaling control- measu protect. signaling control-


relay command relay command

Schneider Electric - Energy Automation – Technical Institute 38 Schneider Electric - Energy Automation – Technical Institute 38
Monitored values Monitored values
I current relays
y I current relays
y

U voltage relays U voltage relays

P, Q power relays P, Q power relays

Z impedance relays Z impedance relays

f frequency relays f frequency relays

Schneider Electric - Energy Automation – Technical Institute 39 Schneider Electric - Energy Automation – Technical Institute 39

Protection elements Protection elements

Schneider Electric - Energy Automation – Technical Institute 40 Schneider Electric - Energy Automation – Technical Institute 40
What is an electrical network? What is an electrical network?
Network architecture and components Network architecture and components
Electrical faults and their consequences Electrical faults and their consequences
R l and
Role d constitution
tit ti off a protection
t ti system
t R l and
Role d constitution
tit ti off a protection
t ti system
t
Required qualities of a protection Required qualities of a protection
system system
Th main
The i protection’s
t ti ’ families
f ili Th main
The i protection’s
t ti ’ families
f ili

Schneider Electric - Energy Automation – Technical Institute 41 Schneider Electric - Energy Automation – Technical Institute 41

Essential qualities
q Essential qualities
q

RELIABILITY FASTNESS RELIABILITY FASTNESS

protection protection
system
t system
t

SELECTIVITY ROBUSTNESS SELECTIVITY ROBUSTNESS


Schneider Electric - Energy Automation – Technical Institute 42 Schneider Electric - Energy Automation – Technical Institute 42
Selectivity
y Selectivityy

Selectivity consists into separating the malfunctioning element from healthy Selectivity consists into separating the malfunctioning element from healthy
network to de-energize it, and only this one network to de-energize it, and only this one

● Necessary for operation and electric energy supply continuity ● Necessary for operation and electric energy supply continuity

● Optimization of electric network operation ● Optimization of electric network operation

● Tripping of the fault clearing necessary CB alone ● Tripping of the fault clearing necessary CB alone

SELECTIVITY SELECTIVITY
Schneider Electric - Energy Automation – Technical Institute 43 Schneider Electric - Energy Automation – Technical Institute 43

Selectivity
y Selectivityy

Four tools to ensure selectivity of a protection system: Four tools to ensure selectivity of a protection system:

● Use of protections sensitive only to faults occurring inside the ● Use of protections sensitive only to faults occurring inside the
protected section protected section
selectivity by differential protection selectivity by differential protection

● Use of protections with spread time-delays to ● Use of protections with spread time-delays to
let the protection which is the closest from let the protection which is the closest from
fault clear the fault fault clear the fault
time-grading selectivity time-grading selectivity

SELECTIVITY SELECTIVITY
Schneider Electric - Energy Automation – Technical Institute 44 Schneider Electric - Energy Automation – Technical Institute 44
Selectivity
y Selectivityy

Four tools to ensure selectivity of a protection system: Four tools to ensure selectivity of a protection system:

● Use of protections with spread thresholds adjusted to discriminate the ● Use of protections with spread thresholds adjusted to discriminate the
faults located out of the protected section faults located out of the protected section
current-grading selectivity current-grading selectivity

● Use of information sharing between relays to ● Use of information sharing between relays to
let the only concerned protections clear the let the only concerned protections clear the
fault fault
logic selectivity logic selectivity

SELECTIVITY SELECTIVITY
Schneider Electric - Energy Automation – Technical Institute 45 Schneider Electric - Energy Automation – Technical Institute 45

Fastness Fastness

Fatness consists into separating the malfunctioning Fatness consists into separating the malfunctioning
element from healthy network to de-energize it, within element from healthy network to de-energize it, within
FASTNESS FASTNESS
a delay compatible with various security constraints a delay compatible with various security constraints

● Necessary for workmen and materials safety ● Necessary for workmen and materials safety

● Safeguard of production units stability ● Safeguard of production units stability

● Reduction of costs due to deteriorations or destructions caused by a fault ● Reduction of costs due to deteriorations or destructions caused by a fault

● Continuity of operation, cost of unsupplied energy ● Continuity of operation, cost of unsupplied energy

● Respect of selectivity ● Respect of selectivity

Schneider Electric - Energy Automation – Technical Institute 46 Schneider Electric - Energy Automation – Technical Institute 46
Reliability
y Reliabilityy

Reliability consists into surely separating the Reliability consists into surely separating the
malfunctioning element from healthy network malfunctioning element from healthy network
RELIABILITY RELIABILITY
to de-energize it to de-energize it

● Necessary for workmen and materials safety ● Necessary for workmen and materials safety

● Reduction of costs due to deteriorations or destructions caused by a fault ● Reduction of costs due to deteriorations or destructions caused by a fault

● Capability to ensure protection function’s operation without failure at any time ● Capability to ensure protection function’s operation without failure at any time

Schneider Electric - Energy Automation – Technical Institute 47 Schneider Electric - Energy Automation – Technical Institute 47

Reliability
y Reliabilityy

The tools to ensure protection system’s The tools to ensure protection system’s
reliability: reliability:
RELIABILITY RELIABILITY

● Redundant system to compensate possible material failures ● Redundant system to compensate possible material failures

● Self-control and supervision functions ● Self-control and supervision functions

● Adequate sensitivity to operate properly in circumstances where faults are ● Adequate sensitivity to operate properly in circumstances where faults are
difficult to detect difficult to detect

● Good robustness to disturbances due to the system’s environment ● Good robustness to disturbances due to the system’s environment

Schneider Electric - Energy Automation – Technical Institute 48 Schneider Electric - Energy Automation – Technical Institute 48
Robustness Robustness

Robustness consists into not separating an healthy element from the Robustness consists into not separating an healthy element from the
network in case of a disturbance which is not an abnormal operation for network in case of a disturbance which is not an abnormal operation for
the protected section the protected section

● Necessary for operation electric energy supply continuity ● Necessary for operation electric energy supply continuity

● Non-deterioration of electric network operation ● Non-deterioration of electric network operation

● Absence of unexpected trips ● Absence of unexpected trips

ROBUSTNESS ROBUSTNESS
Schneider Electric - Energy Automation – Technical Institute 49 Schneider Electric - Energy Automation – Technical Institute 49

Robustness Robustness

The tools to ensure protection system’s robustness: The tools to ensure protection system’s robustness:

● A redundant
d d t system
t permits
it to
t adjust
dj t settings’
tti ’ sensitivity
iti it th
through
h the
th use off ● A redundant
d d t system
t permits
it to
t adjust
dj t settings’
tti ’ sensitivity
iti it th
through
h the
th use off
complementary functions complementary functions

● A system which is independent from network’s configuration is not disturbed by ● A system which is independent from network’s configuration is not disturbed by
external operation constraints external operation constraints

● A coordinated system is indifferent to abnormal operations that doesn’t concern ● A coordinated system is indifferent to abnormal operations that doesn’t concern
the protected section the protected section

each protection function has each protection function has


it own specific
its ifi role
l it own specific
its ifi role
l
ROBUSTNESS ROBUSTNESS
Schneider Electric - Energy Automation – Technical Institute 50 Schneider Electric - Energy Automation – Technical Institute 50
What is an electrical network? What is an electrical network?
Network architecture and components Network architecture and components
Electrical faults and their consequences Electrical faults and their consequences
R l and
Role d constitution
tit ti off a protection
t ti system
t R l and
Role d constitution
tit ti off a protection
t ti system
t
Required qualities of a protection system Required qualities of a protection system
The main protection’s families The main protection’s families

Schneider Electric - Energy Automation – Technical Institute 51 Schneider Electric - Energy Automation – Technical Institute 51

Classification BACKUP
Classification BACKUP
PROTECTIONS PROTECTIONS
fault clearance in case fault clearance in case
MAIN PROTECTIONS of mal operation of MAIN PROTECTIONS of mal operation of
selective and fast fault clearance main protections selective and fast fault clearance main protections

selectivity by selectivity by selectivity by selectivity by


current-grading backup by time current-grading backup by time
measurement information measurement information
selectivity delayed action selectivity delayed action
principle sharing principle sharing

overcurrent overcurrent
distance distance
differential overcurrent CB fail differential overcurrent CB fail
logic logic
voltage voltage
Schneider Electric - Energy Automation – Technical Institute 52 Schneider Electric - Energy Automation – Technical Institute 52
Overcurrent Overcurrent

Fuses Fuses
● Basic protection against short-circuits ● Basic protection against short-circuits
● Direct breaking action with the help of short-circuit current energy ● Direct breaking action with the help of short-circuit current energy
● MV applications: motors and transformers  1MW ● MV applications: motors and transformers  1MW

● simplicity ● simplicity
● low cost ● low cost
● quick fault clearance ● quick fault clearance

● no selectivity ● no selectivity
● lack of flexibility ● lack of flexibility
AsM AsM

Schneider Electric - Energy Automation – Technical Institute 53 Schneider Electric - Energy Automation – Technical Institute 53

Overcurrent Overcurrent

Max of I relays Max of I relays


● Local I measurement ● Local I measurement
● Trip criterion elaboration on current analysis ● Trip criterion elaboration on current analysis
● Selectivity by time, current, logic information ● Selectivity by time, current, logic information
● Directional protection (with local U measurement) if several sources ● Directional protection (with local U measurement) if several sources

● main protection in: ● main protection in:


distribution distribution
industry industry

● backup protection in transmission ● backup protection in transmission

I> I>
Schneider Electric - Energy Automation – Technical Institute 54 Schneider Electric - Energy Automation – Technical Institute 54
Differential Differential

● Local and remote I measurement ● Local and remote I measurement


● Trip criterion elaboration on incoming and outgoing currents analysis ● Trip criterion elaboration on incoming and outgoing currents analysis
● Intrinsic
I i i selectivity
l i i bby time
i andd measurement principle
i i l ● Intrinsic
I i i selectivity
l i i bby time
i andd measurement principle
i i l

Id > Id >

Schneider Electric - Energy Automation – Technical Institute 55 Schneider Electric - Energy Automation – Technical Institute 55

Distance Distance

● Local I and U measurement ● Local I and U measurement


● Trip criterion elaboration on impedance analysis computed by the relay ● Trip criterion elaboration on impedance analysis computed by the relay
● Z = U/ I provides
id an image
i off the
h lload d and
d permits
i didistance evaluation
l i ● Z = U/ I provides
id an image
i off the
h lload d and
d permits
i didistance evaluation
l i
from the fault location in case of short-circuit from the fault location in case of short-circuit
● Selectivity
y byy time,, impedance,
p , logic
g information ● Selectivityy by
y time,, impedance,
p , logic
g information
● Tele-action schemes for a fast fault clearance ● Tele-action schemes for a fast fault clearance

Z< Z< Z< Z<


Schneider Electric - Energy Automation – Technical Institute 56 Schneider Electric - Energy Automation – Technical Institute 56
Voltage
g and Frequency
q y Voltage
g and Frequency
q y

● Local U and F measurement ● Local U and F measurement


● Trip criterion elaboration on voltage and/or frequency analysis ● Trip criterion elaboration on voltage and/or frequency analysis
● Selectivity
S l i i b by time
i compulsory
l as voltage
l andd ffrequency are ● Selectivity
S l i i b by time
i compulsory
l as voltage
l andd ffrequency are
« extended » values (therefore no possible discrimination of faulty « extended » values (therefore no possible discrimination of faulty
element) element)
● Generally used as backup protections ● Generally used as backup protections

U, F U, F
Schneider Electric - Energy Automation – Technical Institute 57 Schneider Electric - Energy Automation – Technical Institute 57

Improve
p yyour knowledge
g ... Improve
p yyour knowledge
g ...

Techniques de l’Ingénieur Techniques de l’Ingénieur

RTE : Mémento de la sûreté du système électrique, RTE : Mémento de la sûreté du système électrique,
édition 2004 édition 2004

Guide de l’ingénierie
g électrique
q Guide de l’ingénierie
g électrique
q

Anyy available
a a ab e pprotection
otect o app
application
cat o gu
guide
de Any
y available
a a ab e pprotection
otect o app
application
cat o gu
guide
de

Schneider Electric - Energy Automation – Technical Institute 58 Schneider Electric - Energy Automation – Technical Institute 58
Revision Comment Author Date Revision Comment Author Date

A Creation from french issue C2 O. RICHARDOT Mar 2011 A Creation from french issue C2 O. RICHARDOT Mar 2011

Schneider Electric - Energy Automation – Technical Institute 59 Schneider Electric - Energy Automation – Technical Institute 59

You might also like