Professional Documents
Culture Documents
Hybrid Project Training
Hybrid Project Training
1 System Introduction
2 Controller
5 O&M
System Introduction
The hybrid power supply system converts the mains / DG into a stable -48VDC
through the rectifier module, and the module outputs -48VDC to supply the load
and charge the battery at the same time;
The hybrid power supply system converts the DC power generated by the solar
battery pack into a stable -48VDC through the PV module, and the module outputs
-48VDC to power the load and charge the battery at the same time;
Mains, DG, PV,and battery complement supply power ; unified management
through platform and controller to achieve PV priority power supply and provide
stable and reliable -48VDC for the load;
When the battery pack supplies power to the load, when the battery voltage
drops to LVD1, the Controller issues an instruction to cut off the power supply of
the primary load circuit; when the battery voltage drops to LVD2, the Controller
issues an instruction. Cut off the power supply of the secondary load circuit;
Intelligent devices such as controllers, combiners, and energy meters, as well
as door sensors, smoke, flood, temperature, and humidity are uploaded to RMS
center through FSU.
3
System wiring diagram
4
Structure drawing
5
System Configuration
Item Configuration
Input branches Mains*1+DG*1 Manual ,CB 125/3P
6
AC Input
Socket
Earth
Mains DG SPD Meter
Mains:U、V、W、N;
DG:U、V、W、N;
SPD:Class B+C,The green terminal is a dry node in SPD state, and 4 sets of
dry nodes are connected in seriesEnergy
Meter:Current detection:CT(curremt transformer),Factory connected;
voltage detection: U, V, W, N; can detect voltage, current, active power,
reactive power, active power, reactive power of each phase; total
voltage, current, power, power consumption;
Communication : 485 to FSU (IBSU-4E).
7
AC input Basic diagram
8
PV Input
CB SPD *2 *3
*6
SPD:Class C,The green terminal is a dry node in the SPD state, and the
PV input SPD dry nodes are connected in series;
9
AC input Basic diagram
P
V
10
DCDB
电池合路器(电池共用管理器)
Notes:
Switch connector Battery connector RS485
q The wiring from the combiner to the switching power
supply and the FSU is connected at the factory;
q The combiner has been debugged at the factory;
q It is necessary to connect the battery to the combiner at
the site. Only the negative battery wire is connected, and the
positive battery wire is connected to the Positive of the
cabinet.
12
● Independently set the boost and floating charge voltage
value of each battery pack ;
● Independently set the charging and discharging current
coefficient of each battery pack;
● Independently set the relevant technical parameters of
each battery pack;
● Real-time measure the operating parameters like SOC /
SOH / DOD of each battery pack;
● Dynamically store the operating data of a certain number
of equipment and battery packs;;
● Support battery packs of different periods, capacities, and
brands;
● Support the sharing of lead-acid battery pack, lithium
battery pack and echelon battery pack;
● Support lithium battery / echelon battery priority discharge,
lead-acid battery backup option;
● Support over-voltage, under-voltage, over-current, over-
temperature cut-off protection for lithium battery / echelon
battery cells;
● RS485 Northbound Interface southbound interface
connected to echelon battery;
Schematic diagram of battery connection
● Connect FSU and monitoring center for two-way data
communication through northbound communication;
13
Power Switch and Monitoring Unit
14
Controller
Monitoring uint
Composition:
q Controller;
q DC power board, shunt detection board, dry contact
board;
q LVD control board;
15
Controller function, interface
Detect system battery status, fault status, AC power supply status, module status and DC output
information
Parameters, battery parameters, system parameters, energy saving parameters, environmental
parameters
System control, module control, dry contact control, sub-cabinet configuration
Control the failure alarm records in the running state
Perform system configuration operations before leaving the factory according to the technical
requirements of the order, please do not operate
a.Detection and control of each unit(Such as: AC power distribution status, rectifier status, battery status, DC
shunt status are all detected or controlled by the controller).
b.It can be connected with the monitoring center to realize four remote functions (with intelligent
communication port (RS232 / RS485, network port, etc.),
Realize telemetry, remote signaling, remote control and remote adjustment functions with the monitoring
center, and upload the power supply running status to the tower monitoring center in real time)
c.Support dry contact alarm output, simple and convenient.
FSU(IBSU-4E)
North
bound
on/off Com Port AI DI
interface
Wiring diagram
Construction tools
19
Common construction materials
21
Secondary transportation, unpacking inspection, installation location
4.4. For data inspection, check the inventory data against the equipment data list, and check the accuracy and
completeness of the data.
4.5. Processing of unpacking inspection results
a. Start by checking the project preparation form and fill in the inspection results in the form.
b. The results of the abnormal inspection should be attached with photos and necessary textual
explanations.
c. Prepare a written report for the abnormal situation of inspection and send it to the relevant
department for processing through the feedback channel.
5. Determine the installation location
5.1. The installation position of the equipment conforms to the requirements of the equipment layout design
drawings of the station. It is strictly forbidden to change the installation position of the equipment.
Equipment installation position error ≤10mm.
5.2. After the calibration of the installation location of the equipment, the accuracy of the location of the
design drawings should be checked. If there is a deviation, the design department should be contacted
for correction.
22
Rack fixing
1. Rack fixing
1.1. Fix the cabinet after the installation position is determined. The
size of the cabinet installation holes is shown in Figure 4-2. During
installation, first measure and mark the drilling position on the
ground (equipment base). Hole, install M12 * 95 expansion bolts;
remove the access panel in the cabinet and the baffle at the rear of
the cabinet, and then fix the cabinet at the designed installation
position.
Claim:
a. The vertical error of the equipment does not exceed 0.1% of the
height of the equipment. The front of the equipment is arranged
straight and should be in a straight line. The deviation per meter is
≤3mm, and the deviation of the entire column is ≤15mm.
b. Keep the drill bit vertical to the ground when drilling, and the
drilling depth should be greater than the length of the expansion tube
of the expansion bolt 20mm to ensure that the expansion tube of the
expansion bolt can fully contact the wall of the installation hole.
c. When installing the expansion bolt, the nut should be tightened to
fix the expansion tube of the expansion bolt, and then a nut should
be screwed in, so as not to expose the bolt: (as shown in Figure 4-1).
d. The bolts are installed in the order of flat washer, spring yellow
washer and nut.
23
Main circuit connection
W
AC input
V
U
N
+
PV input --
To the nearest PE
ground point
Working earth
Battery 2 +
Battery 1+
Battery 2-
Battery1-
24
Controller connection
25
FSU
North
bound
on/off Com Port AI DI
interface
q COM port:DKD51 controller, combiner, energy meter; wiring has been completed.
q AI:The temperature and humidity sensor of the power cabinet, the wiring has been
completed
q DI:The wiring of the flood and smoke senser in the power cabinet has been completed at
the factory; the battery cabinet's flood and smoke senser shall be connected on site
q The WEB system configuration has been configured at the factory and no operation is
required on site;
q Upload communication:Depends on the background platform system.
FSU connection with power cabinet
27
FSU connection with battery cabinet
28
Parameter Setting
When the system is operating for the first time, the system time of the
monitoring unit needs to be set to the local time, otherwise it will affect the
energy measurement ,set the controller parameters according to the on-site
battery manufacturer information, otherwise it will affect the battery
management and accelerate the aging of the battery. The parameter names are
shown in the table below.
Parameter Name Setting Range
DG Parameter DC Parameter
29
Power on Test
(1) Choose a time with good lighting conditions for debugging. Turn on the PV input MCB and observe whether the module
is turned on normally.
(2) Use a multimeter to measure the positive and negative bus voltages, and slowly increase to the default float voltage value,
and turn off the photovoltaic input.
(3) Turn on the DH input MCB, and set the DG switch to on in the system control settings through the controller parameter
settings. Start the DG and observe whether the module is normally power on. Use a multimeter to measure the positive and
negative bus voltage values. to the default value of float charge voltage, set the DG switch to off, turn off the DG input, omit
this step when DG is not available.
(4) When there is mains in the system, turn on the AC input MCB and observe whether the rectifier module is normally
power on. Use a multimeter to measure the positive and negative bus voltage values. Slowly increase to the default float
voltage value and close the mains input.
(5) Observe whether the system parameters are abnormal through the LCD screen, and set the system working parameters
according to the correct operation method and steps.
(6) After confirming that the system is working properly and that the measured parameters meet the requirements, close
the photovoltaic input and AC input switches, connect the load, turn on the system, close the battery fuse, and the system
enters the normal working state.
(7) Turn on the FSU switch, observe the status of the FSU indicator, and wait for 2 minutes to log in to the monitoring
platform.
(8) After starting, the system must be closely monitored for 20 minutes, pay attention to the monitoring information
provided by the system, and the alarms should be processed in time. If the situation is serious or the system needs to be
shut down for testing, the shutdown sequence is as follows:
1) Disconnect the load and battery; 2) Disconnect the photovoltaic input and AC input switches;
30
Switching power supply
Shunt Contactor
Socket
Earth Mains DG SPD Meter
Ø “SPD failure”alarm
Alarm condition:AC SPD fault alarm is displayed in the controller;;
Ø“LVD1 、LVD2(BLVD)”Alarm
Alarm condition:“When the "system protection mode" is the "LVD" mode, the primary DC contactor
is opened.
Ø“Fuse”Alarm:
Alarm condition:When the voltage difference between the upper end of the battery fuse and
the negative is greater than 0.5V;
Ø“Module communication”Alarm
Alarm condition: the communication between the rectifier (including photovoltaic
module) and the controller fails;
42
43