61936-1 © IEC:2002 – 53 –
Table 1 – Minimum clearances in air – Voltage range I (1 kV < U m ≤ 245 kV)
Rated short-
Nominal Highest duration power- Rated lightning Minimum phase-to-earth
voltage of voltage for impulse withstand and phase-to-phase
frequency withstand
system equipment voltage a clearance, N c
Voltage voltage
range
U n U m 1,2/50 µs Indoor Outdoor
r.m.s. r.m.s. r.m.s. (peak value) installations installations
kV kV kV kV mm mm
20 60 120
3 3,6 10
40 60 120
40 60 120
6 7,2 20
60 90 120
60 90 150
10 12 28 75 120 150
95 160 160
75 120 160
15 17,5 38
95 160 160
95 160
20 24 50 125 220
145 270
145 270
30 36 70
170 320
I 45 52 95 250 480
b If values are considered insufficient to prove that the required phase-to-phase withstand voltages are met,
additional phase-to-phase withstand tests are needed.
c For rod-structure.
61936-1 © I
IEE C : 2 002 – 55 –
Table 2 – Minimum clearances in air – Voltage range II ( U m > 245 kV)
voltage voltage
Voltage Phase-to-
Phase-to-
range Ro d
Rod phase Conductor
earth 250/ Conductor Rod
Un – 250/ –
U 1 2/50 2 500
U
n 250/
U m 1,2/50 µ s 2 500 µs – –
r.m.s. structure 2 500 µs conductor
r.m.s. (peak value) (peak structure conductor
N (peak parallel
value)
value)
kV kV kV kV mm kV
Search document
mm
1 600
850/950 750 1 900 1 125 2 300 2 600
1 700 b
275 300
1 800
700
70 0
76 5
765
(800) c
Continue
1 800/1 950 1 425
for Free5 600
4 200 2 423 7 200 9 0 00
1 950/2 100 1 550 4 900 6 400 2 480 7 600 9 4 00
a The rated lightning impulse is applicable phase-to-phase
phase-to-phase and phase-to-earth.
b Minimum clearance required for upper value of rated lightning impulse withstand voltage.
c The introduction of U = 550 kV (instead of 525 kV); 800 kV (instead of 765 kV); 1 200 kV, of a value between
m
765 kV and 1 200 kV, and of the associated rated withstand voltages, is under consideration.
ELECTRICAL CLEARANCES
The clearances are mainly maintained to ensure satisfactory performance in service
and ensure supply of personal inspection, operation and maintenance. Types of clearances are
Earth clearance
Phase clearance
Section clearance
Ground clearance
Bay clearance or Bay width
Earth Clearance
The electrical clearance is defined as “The minimum distance required between live
parts and earth material”.
Phase Clearance
The difference between two or more live parts at difference potential then it is called
Section Clearance
Upload your documents to download.
This safety clearance to conductor is defined as “The clearance having minimum
difference between on unscreened live conductor and to the limits of a working clearance
OR
whenever the separation is related to the safety of operating personal.
As per the standards “This is the minimum clearance from any point where a men may be
required to stand to the nearest outdoor conductor in air”.
ai r”.
Related titles
GENERAL CLEARANCE:
(KV) (m.m) PHASE (m.m.)
12 60 90 90 2600 Search document
Page 24 of 178
TNA Transformer datasheet- IEC Documents HV Portable Tester L&T salzer price td_334_1.en
flatpack-va-… list.pdf
Table-3
Ground Clearance
VOLTAGE RATING MINIMUM CLEARAN
(kV) TO GROUND(mm)
400 8000
You're Reading a Preview
230 5500
132 4600
Upload your documents to download.
110 4600
OR
66 4600
Become
33 a Scribd member for full access.
3650Your
first 30 days are free.
22 3650
11 3650
Continue for Free Table-4
400 27
230 16
132
Search document
11
110 9 5 TO 1
Reward Your Curiosity
TNA Transformer
Everything datasheet-
you want to read. IEC Documents HV Portable Tester L&T salzer price td_334_1.en
flatpack-va-… list.pdf
Anytime. Anywhere. Any device.
Related Interests
Power (Physics)
TNA Transformer datasheet-flatpack- IEC Documents HV Portable Tester L&T salzer price
va-limiter.pdf list.pdf
More From
Related titlesSethu Raman
Search document
TNA Transformer datasheet- IEC Documents HV Portable Tester L&T salzer price td_334_1.en
flatpack-va-… list.pdf
Rockwell DEV_NUMB Relay Setting CYMGRD 6-3 Oct
Automation - Schneider 2006 (2)
UPLOADED BY UPLOADED BY UPLOADED BY UPLOADED BY
robertspiteri Lanz Valdez Sethu Raman Sethu Raman
RME Closed Door KABELINDO NYY SVL Selection Pns Construction GIS-Tech detail.pdf
Part 1 --- PEC[1] MATERIALS
ABOUT SUPPORT
Press Accessibility
Contact Us Publishers
Join today
Invite Friends
Gi s
LEGAL
Terms
Related titles
Privacy
Copyright
Search document
Copyright © 2020 Scribd Inc. . Browse Books . Site Directory . Site Language: English
TNA Transformer datasheet- IEC Documents HV Portable Tester L&T salzer price td_334_1.en
flatpack-va-… list.pdf
Related titles