Professional Documents
Culture Documents
Transmission Line Insulation Design at High Altitude
Transmission Line Insulation Design at High Altitude
E 0
.0 A
D^ 5 CENTER
2.9 L...03 OUTSIDE\
Za8- w
2.7 UI)
25 0
UA.
0 5 10 15 20 25 0.1
LINE LENGTH, km
Fig. 4. Altitude Profile of Dillon-Blue Ri ver Line 0.05
1.8 2.2 2.6 32 34
Showing Approximation By Eight
Constant-Altitude Sections. STRI KE DISTANCE, m
Fig. 6A. Required V-String Strike 'Distances For
Switching Surges, Dillon-Blue River Line,
Z.4 .120
With Resistor, Without Arrester.
---Average of Two Outside
SSFOR
.832 and One Center Phase
2.2
NO RESISTOR--.573
E 2o WITH RESISTOR- 27
.W 1 ~~~~~~~~114
1.8 .619
1.6
1.4
'.4
12 SOUTHEAST WATERTON
I.0
100 200 300
LINE LENGTH, km
resi stors.
O 5 \
The strike distance selection procedure for an
I STRING
-
IVI design should result in strike distances for the
5 NESC I-strings and for the center phase V-string so that
16 INSULATORS the average of the center phase SSFOR and the two
0 outside phase SSFOR's equals the design criterion.
0
For a design SSFOR of 1.0 with pre-insertion resistors
but without line entrance arresters, the curves of
WI
o
Figure 6A (solid curve for center phase) and Figure 7B
0
18
are entered at a SSFOR of 1.0 resulting in strike
'
0.5 -
distances of 2.69 m for the center phase and 2.55 m
-j
LU. for the outside phase for an 18-insulator I-string.
The minimum insulator string length for the V-string
is 1.05 times the strike distance. Therefore, the
_ minimum center phase string length is 2.82 m, which is
0.1 20
equivalent to 19 insulators. To meet NESC
requirements [4], the strike distance for the
0.05 I-strings must be increased to 2.76 m. At this strike
1.8 2.2 2.6 5O 3.4 distance, using 18 insulators, the SSFOR from Figure
STRIKE DISTANCE, m 7B is 0.8. To achieve a total SSFOR for the line of
Fig. 7B. Required I-String Strike Distances 1.0, the center-phase SSFOR can be as high as
[3-2(0.8)] = 1.4. For this SSFOR, the center phase
For Switching Surges, Dillon-Blue River V-string strike distance is 2.62 m, and 19 insulators
Line, Outside Phases. Average of Inward are still required.
and Outward Swing With Resistor, Without Similar calculations can be performed for the
Arrester. case in which line entrance arresters and no pre-
insertion resistors are used. From Figures 7C and 6B,
and neglecting NESC requirements, the minimum I-string
10 and center phase V-string strike distances are 2.46 m
W
10
-
\)\ I- STRINGS
IS INSULATORS
and 2.60 m, respectively. Nineteen insulators would
still be required for the center phase. Using an
G \A
|\ I-string strike distance of 2.76 m to meet the NESC
AVERAGE requirements results in an SSFOR of 0.11 for the
8
outside phases, thus permitting an SSFOR of 2.78 for
the center phase V-string. From Figure 6B, a center
phase strike distance of 2.53 m is obtained, and the
w
O.S
number of insulators is reduced to 18.
-
SWING IN Table III presents the results for various
SWING OUT
combinations of pre-insertion resistors and/or line
entrance arresters using this methodology. For either
NESC
line, use of either pre-insertion resistors or
0
arresters alone results in almost the same
0.1 strike distance and insulator requirements. For
either line the use of both pre-insertion resistors
2.0 2.2 2A 2.6 2. 3.0 and arresters results in the smallest values of
required strike distance.
STRIKE DISTANCE,m
Al 1 IVI
Desi gn V-Strings I ~ Vv
Line Arrester Resister Criterion S, m Ins S, m Ins S, m Ins
Southeast- No Yes SSFOR 2.25 16 2.23 16 2.34 17
Waterton No Yes NESC 2.25 16 2.61* 16 2.23 16
Yes No SSFOR 2.26 16 2.21 16 2.34 17
Yes No NESC 2.26 16 2.65* 16 2.26 16
Yes Yes SSFOR 1 .95 16 1.96 16 2.02 16
Yes Yes NESC 1.95 16 2.35* 16 1.95 16
Lightning 2.34 16 2.34 16 2.34 16
Dillon-Blue River No Yes SSFOR 2.56 18 2.55 18 2.69 19
No Yes NESC 2.56 18 2.76* 18 2.62 19
Yes No SSFOR 2.52 18 2.46 18 2.60 19
Yes No NESC 2.52 18 2. 76* 18 2.53 18
Yes Yes SSFOR 2.07 18 2.07 18 2.13 18
Yes Yes NESC 2.07 18 2.38* 18 1.99 18
Li ghtni ng 2.63 18 2.63 18 2.63 18
* NESC Requirement
strike distance increases to 2.13 m. With arresters center to the outside phases. Coupling factors to
located at station entrances, the SSFOR for the the center and outside phases are 40% and 20%,
center phase, the outside phases, and the total line respectively. Therefore, the approximate strike
are presented in Table IV. The SSFOR for a distance requirement for the center phase is 75% of
16-insulator V-string in the center phase is 2.63 m or 1.97 m. Thus the strike distance *of 2.13 m
presented for comparison purposes. All strike with 18 insulators meets all requirements.
distances exceed the NESC requirements. The values In conclusion, uprating of this line requires
of Table IV show that to achieve the stated SSFOR the use of pre-insertion resistors in the breakers,
design criterion of 1.0, a breaker resistor is and the center phase bundle should be in a hori-
required and the conductor bundle should be in the zontal configuration.
horizontal position.