January - March 2003

Issued by : EBG - Electrical Systems & Equipment, LARSEN & TOUBRO LIMITED, Powai Works, Mumbai 400 072

L&T switchboards
tested for
ASTA certification

L&T switchboards have been sec. and IP54 degree of protection The TTA testing included testing
tested for ASTA certification for in addition to other tests like of incoming circuit, outgoing
compliance with the requirements dielectric properties, temperature circuits, earthing circuits in
of Type Tested Assembly (TTA) rise, clearance & creepage addition to the horizontal and
& Partially Type Tested Assembly distance verification, mechanical
(PTTA) as per IEC 60439. The vertical busbars.
operations, effectiveness of
tests were carried out at British protective circuit etc.
Short-Circuit Testing Station Additionally, PTTA tests were
Limited in U.K. successfully conducted on Power
Similarly, type TQ Motor Control
Control Centre type TF and Motor
The certification of type TF Power Centre has also been certified as
TTA for 80kA short time withstand Control Centre type TQ
Control Centre (for TTA) switchboards for 100kA for 1 sec.
included testing of switchboard at for 1 sec. and IP54 degree of
protection. short time withstand test.
80kA short time withstand for 1

Visit us at www.LNTEBG.com
FEATURE

Type-Tested Assemblies of
Low-Voltage Switchgear & Controlgear
- Mr. B.N. Mistry & Mr. C.D. Mehta
Switchgear Design & Product Development

Reliability of a power distribution be experienced by the same significantly influence the


system is very important switchboard and still it has to performance, from the typical
particularly in case of modern continue to perform satisfactorily assembly verified to be in
process industries wherein the with respect to electrical as well accordance with the standard.
cost of interruption is very high. as mechanical operations.
This is more important in severe Partially type-tested low-voltage
operating conditions (similar to Hence, it is required that the same switchgear and controlgear
tropical conditions prevailing in switchboard undergoes all the assembly (PTTA)
India) where heat, dust, humidity abnormal and normal operating
A low voltage switchgear and
and vermin are prevalent. This conditions to ensure its
controlgear assembly, containing
increases the responsibility of the performance during its intended
both type tested and non–type–
designers and manufacturers of life.
tested arrangements, provided the
such systems in delivering
latter are derived from (e.g. by
products, which are totally reliable The design of quality
calculation) type tested
and safe to work on; products switchboards that will protect the
arrangements which have
which also have the right control integrity of the supply can be
complied with the relevant tests.
and protection devices. achieved by compliance to the
standard for design, construction
Type tests
Low Voltage switchboards form an and testing of switchboards viz.
important link in such power IEC 60439-1 / IS 8623-1. Low These tests are intended to verify
distribution system which mainly voltage switchgear and control compliance with the requirements
consists of drives / motors gear assemblies – Part1: Type- laid down in the standard and are
operating at Low Voltage. Hence, tested and Partially type-tested carried out on a sample of such
it becomes essential to build assemblies. an assembly. Type tests include
highest reliability in LV the following:
switchboards. IEC60439, provides two
fundamental approaches for ➽ Verification of temperature
The quality and reliability built in checking the product performance rise limits
the switchboards can be verified, i.e. Type-tested Assembly and ➽ Verification of the dielectric
to a large extent, by carrying out Partially Type-tested Assembly. properties
type tests. Testing as a means of ➽ Verification of the short-circuit
proving the product performance To understand the requirements, withstand strength
is increasingly becoming an issue let us look at some of the § of busbars & Incoming
of prime importance worldwide. definitions used in the standard. circuit
§ of outgoing circuits
Conventionally, each of these tests Type-tested low-voltage ➽ Verification of the
is carried out on separate switchgear and controlgear effectiveness of the
specimen. These tests are an assembly (TTA) protective circuit
essential requirement but may § verification of effective
not be entirely sufficient. This is A low voltage switchgear and
connection
mainly because in a practical controlgear assembly conforming
§ verification of short-circuit
situation, abnormalities such as to an established type or system
withstand
short circuits or similar faults may without deviations likely to
➽ Verification of clearance and
creepage distances absence of any valid technical Successful type testing to the
➽ Verification of mechanical / practical reasons, generally requirements of TTA is one of the
operation laboratories insist on biggest challenges. Electrical
➽ Verification of the degree of conducting all the tests on the industry, worldwide, has
protection same switchboard). recognised the need of
compliance to the standard as an
➽ The incoming as well as the
Routine tests assurance of satisfactory field
outgoing circuits undergo
performance. In order to ensure
These tests are intended to detect temperature rise test and short-
the reliability of the power
faults in materials and circuit test. It means that all
distribution system, both Power
workmanship. They are carried components in the power circuit
Control Centre and Motor Control
out on every new assembly. like switchgear (ACBs,
Centre should conform to the
Routine tests include the Contactors, Relays etc),
requirements of TTA.
following:- incoming & outgoing contacts,
link work, are also subjected to
➽ Inspection of the assembly Conclusion
these tests, in addition to the
including the wiring / checking The main issue in switchboard
busbar system.
of the schemes design and manufacture is in
➽ Dielectric test ➽ Continuity between the understanding the applicable
➽ Checking of the protective accessible metal parts of standards and adhering to them.
measures and electrical enclosure and earthing circuit
continuity of the protective has to be ensured. Correctly engineered protective
circuits. systems in a "standard compliant"
➽ The earthing circuit is also
switchboard provide the customer
tested for short time withstand a safe and reliable power
For certifying a switchboard as
test. distribution system. Switchboards,
TTA, it is mandatory that all the
requirements as per IEC 60439 ➽ All the drawout feeders are a link between the source
are complied with for all the seven tested for 50 nos. of insertion upstream and the load
type tests, in addition to the routine and withdrawing operations downstream, should offer the
tests. All the tests have to be (racking in and out). highest levels of safety, reliability
carried out on the same design of and ultimately, performance.
the switchboard. Conformance to TTA ensures the
following :- Type testing is increasingly
It should be noted that the term ➽ Satisfactory performance in becoming the key criterion in the
‘Type Tested’ is different than the normal and abnormal field of electrical distribution to
term ‘TTA’. The term ‘Type Tested conditions. assess the reliability and
Switchboards’, which is widely performance of the product. The
➽ Compliance with the safety international standard for design,
used, only means that different
requirements stipulated in the construction and testing of low
designs / switchboards have been
standard. voltage switchgear and
subjected to different type tests
(may be at different times). ➽ All the switchgear, power controlgear assemblies, IEC
Whereas the term ”Type Tested contact assemblies, 60439, provides two fundamental
Assembly” means that the same connecting links etc. are approaches in this respect - Type
design is subjected to all the capable of withstanding / Tested Assembly and Partially
above mentioned type tests clearing the fault. Type Tested Assembly.
simultaneously.
However, any switchboard may Although PTTA may be useful to
The TTA testing is much more not be able to fulfill these assess the performance of a
severe as it involves the requirements unless it is designed particular design / product aspect
following:- and manufactured to meet these e.g. short-circuit, temperature rise
➽ All the tests are to be conducted requirements. This is not an easy in a switchboard; the overall
on same switchboard (though task as it is clear from the fact guarantee of the switchboard
standard permits testing on that very few manufacturers, performance, during normal and
different identical panels, in worldwide, have TTA certified abnormal conditions, can be
switchboards. derived only through TTA.
M-line Contactors

Efficiency meets aesthetics and All these five ratings are available ✔ Easy access to mounting holes
performance combines with in single frame size of sleek 45mm (even after directly mounting
elegance in the new M-line range width. overload relay).
of Power Contactors recently
launched by L&T. Salient features of M-line ✔ Front ON/OFF mechanical
contactors (MNX 9 to MNX 32) : indication.
M-line range of Contactors are
✔ Compact construction ensures
designed and manufactured to ✔ Ease of contact inspection and
complete safety.
meet international standards. replacement.
They meet the precise requirement ✔ Highest aesthetic standard.
✔ Coil with four terminals (two on
of all switching applications,
each side) to facilitate ease of
surpassing the conventional levels ✔ Conform to standards
termination.
of performance and set a distinct § IEC 60947–4-1
new benchmark. ✔ Common coil for entire range § BS EN 60947–4–1
from 9A to 32A. § IS 13947-4-1
Starting from 9A AC3 duty this
range will be available up to 550A ✔ Snap fit construction for ease
of coil replacement. Accessories available with the
AC3 Duty. Presently, the following
range are :
contactors are available : ✔ Finger proofing of terminals.
Contactor AC3 Rating ✔ Contactor lockable in off ✔ 2 and 4 Pole Auxiliary Contact
condition. Blocks
MNX9 9A
MNX12 12A ✔ Alpha-numeric terminal ✔ Surge Suppressor.
MNX18 18A marking.
MNX25 25A ✔ Add on Pneumatic Timer
✔ Direct mounting of Overload
MNX32 32A
Relay & Pneumatic Relay ✔ Mechanical Interlock Kit

For further details on this subject, please contact:


EBG - Electrical Systems & Equipment, Larsen & Toubro Limited, Saki-Vihar Road, P.O. Box 8901, Powai, Mumbai 400 072
Fax: 022-2858 1024 * E-mail: kotnisnd@Intebg.com

Printed by Printania Offset Pvt. Ltd.,D 20/21, Shalimar Industrial Estate, Matunga (East), Mumbai 400 019. Tel.: 2407 7996/
8866/4540 Fax : 2402 4703 Email: pds6@bol.net.in. The views expressed in this magazine are not necessarily those of the
management of Larsen & Toubro Limited. The contents of this magazine should not be reproduced without the written
ABCI permission of the Editor. Not for sale-only for circulation among the customers. Associate Editors: Sharmila Banerjee.
Editorial Coordinators : R. S. Mahajan, Neelam D. Kotnis, EBG-ESE, Powai .
Member

You might also like