Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

July-September 2002

Issued by : EBG - Electrical Systems & Equipment, LARSEN & TOUBRO LIMITED, Powai Works, Mumbai 400 072

Prospect / Retrospect

Industrial processes are ease of operation and and certain energy is let through
progressively becoming monitoring. the circuit. If the let through
sophisticated and the cost of energy is higher than the
downtime is increasing. With a Selection of control components withstand capacity of
large number of induction and provision of adequate downstream equipment, it can
motors in use, to control the protection is a very important cause damage to the
downtime, their protection aspect. The need for more downstream equipment. Thus,
system plays an important role. precise protection is achieving proper co-ordination
Hence, designing a effective necessitated by another factor. means matching the
motor supply circuit and This has led users to size cables characteristics of the SCPD and
ensuring its safety under all economically. the downstream equipment
opereating conditions has including cables to ensure that
paramount importance. When a short circuit occurs, the the let-through energy and peak
Short Circuit Protective Devices cut-off current do not rise above
There is a trend towards (SCPD) take a finite time to the levels that the downstream
installing motor starters in Motor interrupt the fault. During this circuit can withstand.
Control Centers (MCCs) for time, the current rises rapidly

Visit us at www.LNTEBG.com
FEATURE

Considerations for Short Circuit Protection to Starters


- Mr. D. Chatterjee
Switchgear Product Engineering

Protection of motor and associated under short-circuit conditions, the limits the peak fault current, thereby
power circuit, including cables, contactor or starter shall cause no minimising the let-through energy.
requires proper consideration for danger to persons or installations and
different abnormlities. In the event of shall be suitable for further use. Light The factors to be considered while
an overload, the equipment is contact welding is accepted. Type 2 selecting a fuse are :
protected by an overload relay with co-ordination has a major advantage. n The fuse should not blow during
certain time delay. But, in case of a After the fault is cleared, the user starting of the motor.
short circuit, the current needs to be needs just to reset the breaker or n The fuse should blow at a current
interrupted quickly for restricting the replace the blown fuse and check for lower than the breaking capacity
let-through energy and consequent contact welding. of contactor selected.
damage to the downstream equipment. n The fuse should blow at a current
This needs proper co-ordination among Type 1 co-ordination is cheaper during at which overload relay, contactor
the Short Circuit Protective Device installation but Type 2 proves to be and cables are capable to handle
(SCPD) and downstream equipment. economical in the long run. the let-through energy.

TYPE OF CO-ORDINATION SHORT CIRCUIT PROTECTIVE * MCCBs


IEC 60947-4-1 and IS13947 (Part4/ DEVICES (SCPDs): Introduction of current limiting
Section1) define two types of co- MCCBs has resulted in a major
ordination: * Fuses breakthrough in the reduction of let-
* Type 1 Fuses are traditionally used as through energy in the system even
* Type 2 SCPDs because of their low initial at higher fault level. The current
capital cost and capability to limiting MCCBs allow use of lower
Type 1 co-ordination requires that, interrupt faults faster. Fuses have size contactors and cables
under short-circuit conditions, the excellent current limiting compared to conventional MCCBs
contactor or the starter shall cause characteristics and can be applied resulting in cost efficient system.
no danger to persons or installations safely on systems having high fault In the event of a fault,these MCCBs
and may not be suitable for further levels. Fuse is able to restrict let- operate quickly, much before the
service without repair and/or through energy at high fault levels. short circuit current reaches its
replacement of parts. In a starter At high current, the fuse element peak value.
configured with Type 1 co-ordination, melts (pre-arcing period) followed
one can check all the starter by arcing which persists until the The factors to be considered while
components after a fault and replace resistance across the fuse builds selecting an MCCB are:
them if necessary. But this works out up to reduce the current to zero n The thermal rating of MCCB should
to be expensive as well as time (arcing period). Both these actions be greater than or equal to the
consuming. take place very quickly. The motor full load current.
combination of high-speed n The breaking capacity of the MCCB
Type 2 co-ordination requires that operation and high arc resistance should be greater than or equal to
the prospective fault current at its
installation point.
n The magnetic threshold setting of
the MCCB should not result in
nuisance tripping during starting of
the motor.
n Use a current limiting MCCB with
only magnetic protection (without
thermal protection) and a suitable
thermal overload relay with
matching motor characteristics.
n The thermal characteristics of
MCCB (if provided) should be such
that it falls above the overload relay
characteristics up to the magnetic not available from a single time of this changeover, there is arcing
threshold of the MCCB. manufacturer. For e.g. if the fuse/ when the star contacts open. If delta
n The contactor should be able to MCCB manufacturer does not make contactor closes during this arcing
break currents up to the magnetic relays or contactors one has to depend period, there will be short-circuit.
threshold of the MCCB. on other makes to offer complete Hence, there is a intentional time
n The starter should be able to protection system. It is likely that the delay between opening of star
withstand let-through energy of the relay or the contactor undergoes some contactor and closing of delta
MCCB. design changes, which can affect the contactor. But during this period, there
selection combination with the fuse/ is no voltage across the motor (since
Magnetic Threshold Determination: MCCB. Thus it is very important that both star and delta contactors are
all protective equipments open). Since there is no driving torque
Typical motor starting current = 6In are available from a single to the motor, its speed starts reducing.
Maximum peak = 6In x 2.2 = 13.2In source to offer proper co- When the delta contactor closes, full
Magnetic threshold = Imag ordination. line voltage appears across the motor
Minimum value = 0.8 x Imag and it speeds up with a jerk. This kind
Peak value = 1.414 x 0.8 x Imag
* MCCBs: of star-delta staring is called as open
Therefore, for proper operation:
1.414 x 0.8 x Imag > 13.2In In current limiting MCCBs, transition. To avoid such jerks, close
Imag > 11.8In the magnetising current is transition star-delta starters are
i.e. Imag ~ 12In 12 times the nominal preferred.
(Tolerance in characteristics to be considered separately.) current. But in star-delta
starters, the current may In close transition, the changeover
For example, in star-delta starters, at shoot up to 18 times during changeover to delta is with three resistors in
starting, the starting current is reduced from star to delta. So the nominal circuit. These resistors do not allow
to 1/3rd of that with DOL starters. But, rating of the MCCB chosen should be the motor to see full line voltage as
at the instant of switching from star to 1.5 times or above the line current of well as prevent break in supply to the
delta, a high current peak I p is motor. motor, thus giving continuous driving
experienced. torque to the motor. The voltage
* CONTACTORS: coming across the motor with resistors
It may shoot up to 18 times the normal The contactor should be able to is more than that in star and less than
current depending on motor conditions. break any current upto the that in delta. This prevents jerks during
magnetic transition giving smooth changeover to
Ip = [(240 (Voltage at star) ± 415 (Voltage at delta) ] x 12In (at starting) threshold of the motor.
the MCCB. It
415
(Not for more than 2 cycles and +/- according to phase difference)
should carry Resistance calculations for close
Ip = 18In (approx.) the full load transition star-delta starters:
c u r r e n t Resistance, R = 0.4 x V2
continuously Resistance wattage,
However, this changeover takes place for the utilization category specified. (Continuous i.e. 12 starts/hr)
in a very short period of time. So, it Wr = V2
doesn’t affect the selection of the back * RELAYS: 1200 R
up fuse. However, MCCBs being peak The relay range is selected where,
sensing devices may cause nuisance according to the phase current as V = Line voltage in volts,
trip during the changeover between star the relays are connected in phase Ic = Current in amps. (in delta
to delta, if it is not properly selected. circuit. Another important factor is condition).
that the relay used should be able
SELECTION OF EQUIPMENT to withstand the let-through energy For example :
The only way to ensure Type 2 co- of the respective MCCB. Hence, in kW Rating = 150 kW
ordination, is to carry out exhaustive some cases, CT operated relays Voltage = 415 V
tests of the particular fuse & relay and are provided even in case of small Line Current = 275 A
MCCB & relay combinations with the motors. Phase Current = 159 A
contactors. While individual protection
devices may perform to a given set of CLOSE TRANSITION FOR STAR- R = 0.4 X V = 0.4 X 415 = 0.6 Ohms
characteristics, their behaviour in DELTA STARTERS: Ic 275
combination affects the way the circuit In normal star-delta schemes, first the
reacts to a fault. Selection of motor is started in star connection. Wr = V2 = (415)2 = 289.43W
equipment becomes very important When it reaches a certain speed, the 1200R 1200 x 0.6
here. Sometimes all the devices are connection is changed to delta. At the
Close transition star-delta schematic

For further details on this subject, please contact:


EBG - Electrical Systems & Equipment, Larsen & Toubro Limited, Saki-Vihar Road, P.O. Box 8901, Powai, Mumbai 400 072
Fax: 022-858 1024 * E-mail: kotnisnd@Intebg.com

Printed by Printania Offset Pvt. Ltd.,D 20/21, Shalimar Industrial Estate, Matunga (East), Mumbai 400 019. Tel.: 407 7996/
8866/4540 Fax : 402 4703 Email: pds6@bol.net.in Edited by Henry A. Karkada for Larsen & Toubro Limited, from L&T
House, Narottam Morarji Marg, Ballard Estate, Mumbai 400 001, The views expressed in this magazine are not necessarily
ABCI those of the management of Larsen & Toubro Limited. The contents of this magazine should not be reproduced without the
written permission of the Editor. Not for sale-only for circulation among the customers. Associate Editors: Sharmila Banerjee.
Member Editorial Coordinators : R. S. Mahajan, Neelam D. Kotnis, EBG-ESE, Powai .

You might also like