Purchaser NEA Rs Infra Project STR DGN of TT "Da (0 Deg.) " With Htls Conductor (WZ 4) 132KV D/C Transmission Line From Kusaha To Biratnagar

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

RS INFRA PURCHASER STR DGN OF TT "DA(0 DEG.

)" WITH HTLS 132KV D/C Transmission Line


PROJECT NEA CONDUCTOR (WZ 4) From Kusaha To Biratnagar

DESIGN OF STUB & CLEAT


DESCRIPTION UNIT NOTATIONS VALUES SKETCH

Ult. Tension with OLF = 1.1 Kg T 51,935

Size of Stub mm HT L 110x110x10


Yield Strength Kg/Sqcm Fy 3569
Flange width of stub cm fs 11
Thickness of stub cm ts 1.0
Surface length of Stub cm S 40
Embedded Stub length cm L 30
Bond strength between Galv. Stub &
Concrete Kg/Sqcm B 12
Bond strength of Stub Kg Fb=SxLxB 14,364 STUB

Size of Cleat mm HT L90x90x8


Yield Strength Kg/Sqcm F'y 3569 CLEAT
Compr.Strength of Concrete. Kg/Sqcm f'c 205
Thickness of Cleat cm tc 0.8
Flange width of Cleat cm fc 9.00
Length of Inner Cleat mm ln 150
Length of Outer Cleat mm lo 150

Bearing Capacity of Single cleat


P = n*f'c*l*(fc-tc) Kg P 50,430
Quantity of Inner Cleat/Stub no n 2
Quantity of Outer Cleat/Stub no n 2
Bearing strength of Cleats Kg Sb 1,00,860
Shear strength of bolt N/sqmm 310
Connection Size mm 16
Bolts Qty per Stub no 4 Typ. Detailing
Shear plane S/S=1, D/S=2 2
For Shear Kg Sh 50,850
Cleat Bearing Kg Br 53,248
Strength of Cleat (Fmin) Kg F=Min.(Sb,Sh,Br) 50,850
> 50% OF "T"
Total strength of Stub & Cleat Kg Fb 65,214
> 51,935 Safe

Notes: 1. Quality of bolts used are of Grade 5.6


2. Allowable Compressive Strength of Concrete (M20) : 205 Kg/sqcm
3. This stub cleat arrangement shall be applicable for concrete foundations only.

RS/NEA/132KV/STR-DGN/DA/01 Page 54

You might also like