Professional Documents
Culture Documents
Public Comment No. 24-NFPA 409-2014 (Section No. 5.2.1) : Related Item
Public Comment No. 24-NFPA 409-2014 (Section No. 5.2.1) : Related Item
Public Comment No. 24-NFPA 409-2014 (Section No. 5.2.1) : Related Item
5.2.1 *
Where aircraft storage and servicing areas are subdivided into separate fire areas, the separation shall be
by a fire wall barrier having not less than a 3 2 -hour fire resistance rating. Any openings in such fire walls
barriers communicating directly between two aircraft storage and servicing areas shall be provided with a
listed 3 2 -hour fire door or 3 2 -hour shutter actuated from both sides of the wall. Where areas are of
different heights, the tallest wall shall have a fire resistance rating of not less than 3 than 2 hours.
NFPA's Building Code Development Committee (BCDC) supports Committee Input #29. A fire barrier of 2 hour
rating is an adequate separation. Fire wall are over kill. To provide the structural protection necessary for a fire
wall would be nearly impossible considering the clear span trusses being utilized in these facilities.
Related Item
Committee Input No. 29-NFPA 409-2013 [Section No. 5.2.1]
3 of 35 6/24/2014 9:07 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Public Comment No. 27-NFPA 409-2014 [ Section No. 5.9.6 [Excluding any
Sub-Sections] ]
Because entry of fuel, oil, and water into landing gear pits is inevitable, drainage , an active flooring system
, or pumping facilities shall be provided.
An active flooring system is an alternative to drainage or pumping system to contain flammable liquid in landing
gear pits, so guidance should be given in the code.
Related Item
Public Input No. 45-NFPA 409-2013 [New Section after 6.2.7.10]
4 of 35 6/24/2014 9:07 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
5.9.6.4 ....Where active flooring systems are used they shall be designed, installed, and maintained
in accordance to the manufacturer’s instructions and be listed for the purpose.
Where active flooring systems are used they shall be designed, installed, and maintained in accordance to the
manufacturer’s instructions and be listed for the purpose.
Related Item
Public Input No. 45-NFPA 409-2013 [New Section after 6.2.7.10]
5 of 35 6/24/2014 9:07 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
5.11.2.1
In aircraft storage and servicing areas of hangars, floor trench drainage in accordance with 5.11.2.2
through 5.11.2.12 or a approved active flooring system in accordance with 5.11.2.2 through 5.11.2.12 and the
manufacturer's instructions shall be provided.
6 of 35 6/24/2014 9:07 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6.1.1
The protection of aircraft storage and servicing areas for Group I hangars shall be in accordance wtih any
one of the following:
(1) See text from 2011 edition
(2) See text from 2011 edition
(3) See text from 2011 edition
6.1.2
Group I aircraft hangar storage and service areas housing unfueled aircraft shall be provided with
protection in accordance with 6.1.1 or with automatic sprinkler protection as specified in Chapter 12.
Where the provisions of Chapter 12 are used, no provisions of Chapter 6 are required.
There are two changes being proposed here. The first is to return section 6.1.1 with its three subsections to the
text of the 2011 edition. No First Revision was recorded to delete existing section 6.1.1 and its subsections, but
they do not appear in the first draft language on the website.
Second, the additional sentence has been suggested to clear up the protection requirements for unfueled aircraft.
There is a great deal of confusion in the field as to whether the committee intends to also require the provisions of
Chapter 6 when the user has chosen to protect an hangar for unfueled aircraft in accordance with Chapter 12. Of
particular concern is section 6.2.10.8.2, which requires an extra fire pump. Some AHJ's are enforcing this section
for hangars designed for unfueled aircraft that are protected in accordance with Chapter 12 even though Chapter
12 does not have similar language. Explicit instructions not to use Chapter 6 if Chapter 12 is followed would be
extremely helpful to the users of NFPA 409.
Related Item
Public Input No. 47-NFPA 409-2013 [Section No. 6.1.1]
7 of 35 6/24/2014 9:07 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6.1.7
Foam solution piping shall be permitted to be black steel meeting the requirements of NFPA 13.
The NFPA-11 Technical Committee respectfully requests the NFPA-409 Technical Committee reconsider the
decision to permit the use of black steel pipe for foam solution lines used in foam systems that are dry and/or open
to atmosphere. This will allow for alignment of the discharge piping requirements of foam systems between the
two standards.
NFPA-409 only requires operational flow testing of foam systems every 5 years. In the case of AFFF deluge
sprinkler systems that testing is typically done by discharging through a test header with no flow through the
sprinkler discharge piping network. As such there is no easy way to flush corrosion debris that may have formed
in the foam solution piping since installation. In fact, there is no follow up water discharge testing for aircraft
hangar AFFF deluge sprinkler systems that determines whether sprinkler piping and/or deluge sprinklers may be
obstructed. High expansion foam systems are typically discharged with water through the foam generators to
confirm proper operation of the water motor that drives the fan.
Based upon experience of members of the NFPA-11 Technical Committee that service and test deluge sprinkler
and high expansion foam systems it is clear that internal pipe scale and corrosion can cause systems failures due
to obstruction of the piping and discharge outlets. Foam solution piping in aircraft hangar systems is subject to
wide temperature and humidity fluctuations that create condensation that promotes internal corrosion of black
steel pipe over time. This problem is more pronounced in hangars located in high humidity areas near the coasts
and islands where the air can contain salt. Water remaining in the system piping from system commissioning tests
will also cause corrosion over time. In some aircraft hangars corrosion of black steel foam solution sprinkler piping
has been severe enough to warrant replacement due to leaks and concern about pipe integrity.
A series nine of photos (attached) illustrate the problems discovered in black steel foam solution piping as the
systems were being inspected and tested. Not all of the pictures directly relate to aircraft hangar system foam
solution piping but they indicate the same problems that can be experienced in aircraft hangar foam systems.
A technical article by FM Global and published in Sprinkler Age magazine (February 2013, Vol 32/02, page 22)
states that bare black steel pipe is not suitable for dry or pre-action systems due to high volume of corrosion that
can obstruct piping and sprinklers. The article also concludes that galvanized pipe may not eliminate corrosion but
it is the best option and has served the industry well.
Based on the field problems experienced with dry and/or deluge type foam systems installed with black steel foam
solution piping the NFPA-11 Technical Committee urges the use of galvanized pipe for aircraft hangar foam
systems where the internal foam solution pipe surfaces are exposed to atmosphere.
8 of 35 6/24/2014 9:07 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6.1.7
Foam solution piping shall be permitted to be black steel meeting be any ferrous material meeting the
requirements of NFPA 13.
NFPA's Building Code Development Committee (BCDC) believes NFPA 13 addresses the type of ferrous piping
materials that are allowed. Black steel is a ferrous material, and ferrous materials should be referenced to NFPA
13. This revision simplifies the intent of the provision.
Related Item
First Revision No. 13-NFPA 409-2013 [New Section after 6.1.1]
9 of 35 6/24/2014 9:07 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6.1.7
Foam solution piping shall be permitted to be black steel meeting the requirements of NFPA 13.
No technical data or information was presented by the NFPA 409 Technical Committee to substantiate the use of
black steel pipe for foam solution (99%, 98%, 97%, or 94% water) in place of galvanized pipe. This new Section
6.1.7 would supersede the requirements of NFPA 11 and/or NFPA 16. NFPA 11 is in the current Fall 2014 revision
cycle, with Section 4.7 - Piping (SR # 12) being completely revised, including differentiating the piping
requirements between foam concentrate and foam solution. If adopted, this Second Draft Revision of NFPA 11
(which passed ballot by the Technical Committee) will also allow for the usage of black steel pipe when the
discharge devices are closed to the atmosphere.
To substantiate the usage of galvanized pipe, even for indoor systems (e.g. aircraft hangars), Steel Pipe Material
Corrosion, an article authored by Paul Su and David Fuller of FM Global in Sprinkler Age (February 2013, Vol.
32/02, p22), concludes that “bare/black steel should not be used in a dry or pre-action system due to the high
volume of corrosion
products that can obstruct piping and sprinklers”. It also concludes “galvanized pipe does not eliminate corrosion
but is the best option and has served the industry well.” Below is a hyperlink to Sprinkler Age, February 2013 for
review of the article by Technical Committee members. (Hyperlink to Sprinkler Age, February 2013:
http://digital.turn-page.com/i/109066).
Related Item
First Revision No. 13-NFPA 409-2013 [New Section after 6.1.1]
10 of 35 6/24/2014 9:07 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6.2.7.10
Controllers for foam concentrate pumps shall be as follows:
(1) For electric-drive foam concentrate pumps greater than 22.4kW (30 horsepower) , a listed
full-service
This public comment is to reject FR No. 16 and return to language of previous edition. Limited service controllers
are specifically designed for small horsepower motors. The reliability of limited service controllers is improved
because NFPA 20 requires the same type of circuit breaker in a limited service controller as in a full service
controller. The option of controller type should be left to the design professional utilizing the requirements of NFPA
20.
Related Item
First Revision No. 16-NFPA 409-2013 [Section No. 6.2.7.10]
11 of 35 6/24/2014 9:07 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
NFPA's Building Code Development Committee (BCDC) is opposed to this First Revision and supports Committee
Input #40. This First Revision would require two fire pumps which is overkill. There is no substantial evidence that
this redundancy is necessary due to reliability problems with fire pumps. We agree that NFPA 20 takes
considerable care in ensuring fire pump reliability.
Related Item
First Revision No. 41-NFPA 409-2013 [Section No. 6.2.10.8.2]
Committee Input No. 40-NFPA 409-2013 [Section No. 6.2.10.8.2]
12 of 35 6/24/2014 9:07 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Public Comment No. 19-NFPA 409-2014 [ Sections 6.2.11.4, 6.2.11.5, 6.2.11.6, 6.2.11.7 ]
13 of 35 6/24/2014 9:07 AM