Professional Documents
Culture Documents
Long-Term Performance of Partially Silicone Rubber Coated Porcelain Long-Rod Insulators
Long-Term Performance of Partially Silicone Rubber Coated Porcelain Long-Rod Insulators
Long-Term Performance of Partially Silicone Rubber Coated Porcelain Long-Rod Insulators
I N our investigations of the effect of core diameter of polymer voltage was confirmed compared with the same long rod
insulators on their contamination flashover voltages, we insulator without any coating on its trunks [2], [3]. The silicone
found that transmission line insulators with very small core rubber coated surfaces were pre-conditioned to get a uniform
diameters have 30-50% higher flashover voltages compared contamination layer as is the case of hydrophobic polymer
with larger core diameter insulators like line-post and station insulators [4]. Due to pre-conditioning, the surface
post insulators, and bushing shells despite all the specimens hydrophobicity was reduced and surface resistances were not
having the same housing material and the same or similar shed so high compared with the dried trunk surface of transmission
configurations [1]. Such better performance of a transmission line polymer insulators. Although we also evaluated the
line insulator can be attributed to its large ratio of shed to core performance of the specimen after one week of rest time
diameter which is 4 to 5. Due to such a large ratio, the leakage expecting the recovery of hydrophobicity, any significant
current density on trunks is 4 or 5 times higher than that at the improvement wasn’t obtained.
shed tips resulting in extremely high surface resistances on Considering the actual field conditions of silicone rubber
trunks. So the voltage applied to the whole insulator gets polymer insulator surfaces, we developed a new contamination
divided and allotted to these individual trunks. Such an method by spraying dry salt and Tonoko powders on to the
improved voltage distribution along the transmission line insulator surfaces. Then we could get a significant
polymer insulator results in higher contamination flashover improvement of 35-45% in the flashover voltage [5]. We could
voltages. also confirm significant improvement in the flashover voltage
In the case of porcelain long rod insulators, ratios of shed to by the salt fog test method [6].
core diameter are only 2~3. So the difference in the surface In the next stage of our investigation, we evaluated the
resistance is not so significantly large between the trunk and comparative contamination flashover voltages among the
shed portions and can be easily masked by other factors such as porcelain long rod insulators with silicone rubber coating only
the non-uniform distribution of fog density along the insulator on all the shed surfaces, only on the trunk surfaces and whole
and the difference in wetting degree between the upper- and the insulator surface [7]. Higher flashover voltages were
under-shed surfaces. So superior contamination flashover obtained, for the specimen with silicone rubber coating on all
voltage performance, as is the case of transmission line the shed surfaces compared with the specimen coated on all the
A10 2
trunk surfaces. This can be attributed to the longer leakage or TABLE 2 SEQUENCE AND CONDITIONS OF ACCELERATED AGEING TEST
longer dry arcing distance along the individual shed surfaces Time, h
Stress Test Conditions
compared with that along the trunk surfaces. 3 6 9 12 15 18 21
Based on the successful test results of porcelain long rod Voltage AC 160kV(Line to Ground)
insulators with partial silicone rubber coating, we evaluated Salinity : 6.0 mS/cm
Salt Fog
also the performance of a porcelain bushing shell with silicone Input Rate:0.5 l/h/m3
rubber coating on all the trunks by salt fog test method [8]. Steam Fog Input Rate:0.1 kg/h/m3
8m
an accelerated ageing test and by an outdoor exposure test Wall Bushing
under the test voltage of 160kV for the system voltage of Nozzles for Salt Fog
275kV on full scale [9]. In this paper we present the Nozzles for Steam Fog
investigation results of long-term performance of these
insulators. Plan
10 m
TABLE 1 SPECIMEN DETAILS
UV Lamps
Leakage
RTV SiR No. of Specimen Insulator Strings
Kind of Test Shed Shape Distance,
Coating at Units
mm Nozzles for Steam Fog
Nozzles for Salt Fog
2 4280
Trunks
3 6420 Elevation
Accelerated Whole Fig. 1 Accelerated ageing test arrangement
2 4280
Ageing Surface
40mm
Under 5.7 m 5.7 m
2 4280
40mm Sheds
Nozzles for Salt Fog
Outdoor
Trunks 3 6420
Exposure Bushing
6.3 m Specimen
unit coated with silicone rubber and aged by the accelerated This shows that if silicone rubber coating is applied only to all
ageing test or outdoor exposure test is installed vertically in the the trunk surfaces, the applied voltage to the whole insulator
fog chamber as shown in Fig. 2 after cleaning the surface by tap string can be divided and allotted to these portions and ageing
water. Test voltage V0 is applied and then salt fog is directly deterioration is accelerated by the partial discharges
sprayed over the specimen as shown in Fig. 2. Based on the test concentrated around these portions if the string is too short for
procedure shown in Fig. 3, after confirming withstand during the partial discharges to occur.
30 minutes under the test voltage V0, test voltage is increased Hydrophobicity measurement results after 400 cycles of the
by 10% and flashover or withstand during 5minutes is accelerated ageing test of 3 long-rod insulator units of string
confirmed. If no flashover, the test voltage is increased by under the same voltage application are shown in Fig. 6. A
another 10%. Repeating this procedure, the first flashover drastic improvement can be seen in the hydrophobicity on the
voltage FOV1 is obtained. Then, 80% of FOV1 is applied to the trunk surfaces compared with the case of 2 units of string. In
same specimen for 5 minutes to confirm flashover or withstand. our visual observation, any severe discharge activities were not
If no flashover, the same test procedure is repeated to get the observed.
next flashover voltage FOV2. Thus repeating the procedure, Surface observation results of SiR coated trunk surfaces after
five flashover voltage values shall be obtained and the average 400 cycles of accelerated ageing tests of 2 units and 3 units of
value is compared. strings are shown in Fig. 7. In the case of 3 units of string,
FOV5 crazing is seen only on the energized side unit and the number
5min
FOV2
of trunks with crazing in this unit is less than that in the case of
5min 5min
5min 5min
2 units of string. Any erosion or crazing is not observed on the
remaining two units.
Applied Voltage, kV
1.3V0 5min V4
5min FOV1 V4≒0.8FOV4
1.2V0 V1 V ≒0.8FOV
5min 1 1
1.1V0 F.O ●: Coated on Whole Surface (Measured on Trunk Surface)
5min ○: Coated on Whole Surface (Measured on Under-shed Surface)
F.O. F.O.
30min ■: Coated on Under-shed Surface
Hydrophobicity Level Acc. to STRI Criteria
Time 5
Fig. 3 Contamination Test Procedure 4
3
Hydrophobic
7
with whole surface coating and under-shed surface coating is
HC1~2, no significant reduction in hydrophobicity. Slight 6
Hydrophilic
3
surfaces of the energized side unit. Any erosion and surface 2
degradation wasn’t observed on the other specimen. Specimen: SiR Coating on Trunks
1
Surface hydrophobicity on the specimens coated with SiR on
trunks was significantly reduced after 400 cycles of accelerated
Ground Energized Ground Energized
ageing test as shown in Fig. 5. Significant reduction in End Middle End End Middle End
hydrophobicity can be seen on almost all the trunks of both Ground Side Unit Energized Side Unit
units.
Concentrated partial discharges are observed at the trunks. Fig. 5 Hydrophobicity on Trunks of 2 Units of String after 400 Cycles
A10 4
Center Unit
coated trunk surfaces, specimens of the 3 units of string have
significantly higher contamination flashover voltages
compared with the specimens of 2 units of string.
22
V. CONCLUSION
Energized End Unit
REFERENCES 110
[1] B. K. Gautam, S. Matsumura, K. Sakanishi, R. Matsuoka and M. Ito, Ground End (3 Unit)
“Effect of Core Diameter of Cylindrical Polymer Insulators on
Contamination Flashover Voltage – Part I”, IEEJ Trans. on Electrical and
Average Flashover Voltage, kV/unit
Electronic Engg., Vol. 1, No. 3, pp. 298-305, Sept. 2006. 100 New Specimen
[2] B. K. Gautam, S. Matsumura, S. Matsushita, T. Hashimoto, K. Sakanishi
and R. Matsuoka, “Investigation of Contamination Flashover Voltage of a
Porcelain Long Rod Insulator with Silicone Rubber Coating on the Ground End (2 Unit)
Trunks”, Proceedings of the 8th ICPADM, Paper No. M-2, pp. 591-594, 90
Bali, Indonesia, June 26-30, 2006.
[3] K. Yamada, T. Yamazaki, C. Saka, B. K. Gautam, K. Sakanishi, R. Energized End (3 Unit)
Matsuoka and K. Kondo, “Improvement of Contamination Flashover
Performance of Long Rod Porcelain Insulators – Part 2”, IEEJ Tokai
Branch Joint Conference, paper No. o-062, Gifu, Japan, September 28-29, 80
2006 (in Japanese). : Ground End
[4] K. Naito, K. Izumi, K. Takasu and R. Matsuoka, “Performance of : Center Energized End (2 Unit)
Composite Insulators under Poluuted Conditions”, CIGRE Session Paper : Energized End
No. 33-301, 1996. 70
1 2 3 4 5 6 7
[5] M. Suzuki, J. Aoyama, K. Yamada, A. Hayashi, C. Saka, K. Sakanishi and
Hydrophobic Hydrophilic
R. Matsuoka, “Improvement of Contamination Flashover Voltage Hydrohobicity Class
Performance of a Porcelain Long-rod Insulator”, IEEJ Tokai Branch
Conference, Paper No. O-013, 2008 (in Japanese) Fig. 8 Contamination Flashover Voltage Test Results