Fig. 2. PLC-based control system configuration [2]. Fig. 3. Flow chart of governor control program [2].
In section II, the system development and Each implemented functions of the governor
configuration of governor and operation control are control part can be described as in the following
described. In section III, field test and results are
details below.
a) Speed Control Function
The speed control function is shown as a diagram
in Fig. 4. The speed control function composes of
implemented main sub-function blocks for instance
Set Point, Ramp Rate, Dead Band, PID, and
Limiter. The maximum limit of speed set point is
100% while minimum limit depending on the field
circuit breaker (41) status. The set point can be
Fig. 5. Function block diagram of guide vane position control
obtained by SCADA with enable signal pulse. The
for the turbine [2].
demand signal from SCADA is then passed the
ramp rate that assigning the rising or decreasing c) Runner Vane Control Function
rate of signal. The guide vane position demand or In this function, the desired position of runner
speed control signal is then result of difference blade is obtained by the computation of relationship
value (error) from the speed set point and speed between the guide vane position and head water
feedback that passing PID function block. level in reservoir. The runner vane control function
is shown as a diagram in Fig. 6. The function is
consisted of Relation, Limiter, Set Point, Selector,
Summing, Dead Band and Gain Valve. The runner
vane control has three mode; auto, manual, and
runner stop.