INSTRUMENT REGN.NO.

DATE OF INSPECTION
DRAWING / DOCUMENT NO.
PSER
HANGER DETAILS
Note : Initial cold values shall be taken before hydraulic test and hot values shall be taken at near full parameters.

Hanger Completion of Design Values Actual reading of hangers (mm)


supporting structure
(Yes / No) Elevation of
Tag.No. Type Rating Cold Hot Pipe C.L. (M) Cold Remarks Hot Remarks
MS H01 VLH SA-08-160 Yes 97 180 11520 97
MS H02 VLH SH-10-160 Yes 66 96 8500 66
MS H03 CLH 1152 Yes 30 73 4500 30
MS H04 VLH SH-10-080 Yes 52 61 4500 52
MS H05 RIGID SUPPORT NA Yes NA NA NA NA
MS H06 VLH SH-10-160 Yes 42 77 4500 42
MS H07 CLH 1153 Yes 60 129 4500 60
MS H08 CLH 1152 Yes 30 107 4500 30
MS H09 VLH CH-09-160 Yes 80 115 10550 80
MS H11 VLH SH-09-160 Yes 180 88 22200 118
MS H12 VLH SH-09-160 Yes 115 130 22200 115
MS H14 VLH SA-10-080 Yes 27 10 36000 27
MS H15 VLH SA-10-160 Yes 35 69 34900 35
MS H16 CLH 1152 Yes 45 90 38000 45
MS H18 CLH 1152 Yes 75 30 52000 75
MS H19 CLH 1162 Yes 120 42 55500 120
MS H20 CLH 1152 Yes 75 17 55500 75
MS H21 VLH SA-10-160 Yes 111 82 55500 111
MS H22 RIGID SUPPORT NA Yes NA NA NA NA
MS H23 VLH SH-08-080 Yes 57 67 59650 57
MS H24 VLH SH-09-080 Yes 60 63 59650 60
MS H25 VLH SH-09-080 Yes 60 61 59000 60
MS H26 VLH SH-08-080 Yes 57 62 59000 57
MS H27 RIGID SUPPORT NA Yes NA NA NA NA
MS H28 VLH SH-10-080 Yes 56 38 55500 56
MS H29 VLH SH-09-160 Yes 100 65 55500 100
MS H30 CLH 1162 Yes 105 49 55500 105

NAME SIGNATURE / DATE FQP NO.: QPE:STD:250:PP:71


PROJECT INSPECTED BY REV. NO.: R00
UNIT NO. CLEARED BY LOG SHEET NO.: L-02
RATING CUSTOMER PAGE 1 OF 1
WI:QLY:03-F11/R0
INSTRUMENT REGN.NO.

DATE OF INSPECTION

PSER DRAWING / DOCUMENT NO.

HANGER DETAILS
Note : Initial cold values shall be taken before hydraulic test and hot values shall be taken at near full parameters.

Hanger Completion of supporting Design Values Actual reading of hangers (mm)


structure
(Yes / No) Elevation of
Tag.No. Type Rating Cold Hot Pipe C.L. (M) Cold Remarks Hot Remarks

MS H31 CLH 1152 Yes 90 45 52000 90


MS H33 CLH 1152 Yes 15 60 38000 15
MS H34 CLH 1162 Yes 30 104 31540 30
MS H35 CLH 1162 Yes 45 87 31540 45
MS H36 VLH SH-10-080 Yes 39 52 31540 39
MS H37 RIGID SUPPORT NA Yes NA NA NA NA
MS H38 VLH SH-09-080 Yes 61 66 31540 61
MS H39 VLH SH-08-080 Yes 62 60 31540 62
MS H40 RIGID SUPPORT NA Yes NA NA NA NA
MS H41 VLH SH-09-160 Yes 113 126 22200 113
MS H42 VLH SH-09-080 Yes 68 39 22200 68
MS H43 RIGID SUPPORT NA Yes NA NA NA NA
MS H44 VLH SH-08-160 Yes 81 160 10500 81
MS H45 CLH 1153 Yes 45 160 45000 30
MS H47 CLH 1162 Yes 30 88 4500 30
MS H48 CLH 1162 Yes 30 87 4500 30
MS H49 VLH SH-10-160 Yes 47 82 8500 47
MS H50 VLH SA-08-080 Yes 40 61 11220 40
MS H51 VLH SH-11-080 Yes 37 38 12725 37
MS H52 VLH SA-06-160 Yes 101 75 12725 101

NAME SIGNATURE / DATE FQP NO.: QPE:STD:250:PP:71


PROJECT INSPECTED BY REV. NO.: R00
UNIT NO. CLEARED BY LOG SHEET NO.: L-02
RATING CUSTOMER PAGE 1 OF 1
WI:QLY:03-F11/R0
INSTRUMENT REGN.NO.

DATE OF INSPECTION
PSER
DRAWING / DOCUMENT NO.

HANGER DETAILS
Note : Initial cold values shall be taken before hydraulic test and hot values shall be taken at near full parameters.

Hanger Completion of Design Values Actual reading of hangers (mm)


supporting structure
(Yes / No) Elevation of
Tag.No. Type Rating Cold Hot Pipe C.L. (M) Cold Remarks Hot Remarks
HRH- H01 VLH SS-11-080 Yes 57 65 59108 57
HRH- H02 VLH SH-11-080 Yes 45 64 59108 45
HRH- H03 RIGID SUPPORT NA NA NA NA NA
HRH- H04 VLH SH-11-080 Yes 58 19 59108 58
HRH- H05 RIGID SUPPORT NA NA NA NA NA
HRH- H06 CLH 1162 Yes 50 78 46500 50
HRH- H07 CLH 1165 Yes 75 165 39800 75
HRH- H08 VLH SH-10-160 Yes 86 122 37000 86
HRH- H09 CLH 1162 Yes 90 54 36900 90
HRH- ZR2 RIGID SUPPORT NA NA NA NA NA
HRH- H10 CLH 1162 Yes 120 37 36900 120
HRH- H11 CLH 1162 Yes 105 49 34000 105
HRH- H12 RIGID SUPPORT NA NA NA NA NA
HRH- H13 VLH SH-11-080 Yes 26 11 22200 26
HRH- H15 CLH 1162 Yes 30 97 8500 30
HRH- H16 CLH 1163 Yes 45 132 4667 45
HRH- H17 CLH 1172 Yes 30 77 4500 30
HRH- H19 VLH SH-11-080 Yes 29 35 4500 29
HRH- H22 VLH SS-10-080 Yes 59 39 15870 59
HRH- H23 VLH SS-09-080 Yes 42 31 15890 42
HRH- H24 VLH SS-10-080 Yes 57 38 15890 57
HRH- H26 VLH SH-11-160 Yes 50 88 4500 50
HRH- H27 CLH 1163 Yes 45 124 4500 45
HRH- H28 CLH 1162 Yes 30 97 8500 30
HRH- H30 VLH SH-11-080 Yes 25 11 22258 25

NAME SIGNATURE / DATE FQP NO.: QPE:STD:250:PP:71

PROJECT INSPECTED BY REV. NO.: R00

UNIT NO. CLEARED BY LOG SHEET NO.: L-02

RATING CUSTOMER PAGE 1 OF 1


WI:QLY:03-F11/R0
INSTRUMENT REGN.NO.

DATE OF INSPECTION
PSER
DRAWING / DOCUMENT NO.

HANGER DETAILS
Note : Initial cold values shall be taken before hydraulic test and hot values shall be taken at near full parameters.

Hanger Completion of Design Values Actual reading of hangers (mm)


supporting structure
Tag.No. Type Rating (Yes / No) Cold Hot Elevation of Pipe C.L. (M) Cold Hot Remarks
HRH- H31 VLH SH-10-160 Yes 112 130 22258 112

HRH- H35 VLH SH-11-160 Yes 96 132 28500 96

HRH- H36 CLH 1173 Yes 75 165 28500 75

HRH- H37 CLH 1173 Yes 45 186 28500 45

HRH- H38 CLH 1164 Yes 45 222 28500 45

HRH- H39 CLH 1163 Yes 30 142 38000 30

HRH- H40 CLH 1162 Yes 45 197 46000 45

HRH- H42 VLH SH-11-080 Yes 39 22 58000 39

HRH- H44 VLH SH-11-080 Yes 36 52 59000 36

HRH- H45 VLH SS-11-080 Yes 55 59 59000 55

HRH- H46 VLH SH-10-160 Yes 70 98 7900 70

HRH- H48 VLH SH-10-080 Yes 47 52 7900 47

HRH- H49 VLH SH-10-160 Yes 39 69 7900 39

NAME SIGNATURE / DATE FQP NO.: QPE:STD:250:PP:71

PROJECT INSPECTED BY REV. NO.: R00

UNIT NO. CLEARED BY LOG SHEET NO.: L-02

RATING CUSTOMER PAGE 1 OF 1

WI:QLY:03-F11/R0
INSTRUMENT REGN.NO.

DATE OF INSPECTION
PSER
DRAWING / DOCUMENT NO.

HANGER DETAILS
Note : Initial cold values shall be taken before hydraulic test and hot values shall be taken at near full parameters.

Hanger Completion of Design Values Actual reading of hangers (mm)


supporting structure
Tag.No. Type Rating (Yes / No) Cold Hot Elevation of Pipe C.L. (M) Cold Remarks Hot Remarks
CRH- H01 VLH SH-10-160 Yes 46 66 9500 46
CRH- H02 VLH SH-08-160 Yes 56 80 8110 56
CRH- H03 VLH SH-12-160 Yes 47 73 4500 47
CRH- H04 VLH SH-11-080 Yes 47 55 4500 47
CRH- H06 VLH SH-10-080 Yes 36 53 4500 36
CRH- H07 VLH SH-10-160 Yes 56 85 4500 56
CRH- H09 VLH SH-09-160 Yes 91 64 18200 91
CRH- H10 VLH SH-10-160 Yes 47 23 22140 47
CRH- H11 VLH SH-10-080 Yes 29 40 22200 29
CRH- H13 VLH SH-10-080 Yes 31 20 32850 31
CRH- H14 VLH SH-10-080 Yes 28 20 32850 28
CRH- H16 VLH SH-10-080 Yes 50 59 35600 50
CRH- H18 VLH SH-08-080 Yes 27 29 37800 27
CRH- H19 VLH SH-08-160 Yes 71 97 37850 71
CRH- H20 VLH SH-07-160 Yes 66 97 40000 66
CRH- H22 VLH SH-07-160 Yes 126 94 53000 126
CRH- H23 VLH SH-09-160 Yes 99 67 56000 99
CRH- H25 VLH SA-09-160 Yes 107 123 58780 107
CRH- H26 VLH SA-09-080 Yes 27 44 58760 27
CRH- H28 VLH SH-09-160 Yes 100 66 56000 100
CRH- H29 VLH SH-07-160 Yes 124 92 53000 124
CRH- H31 VLH SH-07-160 Yes 66 93 40000 66
CRH- H32 VLH SH-08-160 Yes 68 90 37850 68
CRH- H33 VLH SH-08-080 Yes 41 38 37800 41
CHR- H34 VLH SH-04-080 Yes 35 39 24700 35
CRH- H39 VLH SH-06-080 Yes 26 28 35500 26