EN6150 enclosure
Quick settings
guide-Rev01
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
1 Email: Contact@elec-engineer.net - +213556898238/+213782276734
ENSURE THAT AT LIST 03 RECTIFIERS ARE
INSTALLED
Date(s): 16/12/2015 Toutes les précautions et mesures de sécurité ont été prises en compte lors de cette opération
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.net
2 - +213556898238/+213782276734
Entry Pin code «1 »
Admin level password is «640275 »
Date(s): 16/12/2015 Toutes les précautions et mesures de sécurité ont été prises en compte lors de cette opération
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.net
3 - +213556898238/+213782276734
Wrong Battery Vfloating voltage
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.com
4 - +213556898238/+213782276734
Battery capacity Setting:
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.com
5 - +213556898238/+213782276734
Battery Charging current
0,1xC10
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.com
6 - +213556898238/+213782276734
LVD1 Threshold
Should be
enabled and
setted at 45V
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.com
7 - +213556898238/+213782276734
LVD2 Threshold
Should be
enabled and
setted at 43V
2000
Cycles
Numbers
LVD2 related to Battery
disconnection should be enabled
and setted as above
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.com
8 - +213556898238/+213782276734
Compensation
voltage per Set
should be setted at:
96mv/C° Starting
from 20C°
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.com
9 - +213556898238/+213782276734
Equalization
operation should be
Setted at:
VEQU=56,4V
Period depend on
batteries status
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.com
10 - +213556898238/+213782276734
Environnement
settings should not
be Changed
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.com
11 - +213556898238/+213782276734
Ensure that the rectifier output voltage (system
voltage) is not less than 54,5v
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.com
12 - +213556898238/+213782276734
(1-7PL)
Priority Loads
CB’s
merci
Date(s): 16/12/2015
All the values and adjustments proposed in this document are derived from the equipment manufacturer's datasheet
Carried out by GEOCOM : Aouili Ahmed
Email: Contact@elec-engineer.com
15 - +213556898238/+213782276734