Professional Documents
Culture Documents
385.06.11 Vir Sistem D.O.O. - Epc155, CL2, Mar2ra
385.06.11 Vir Sistem D.O.O. - Epc155, CL2, Mar2ra
Prezzo
ITEM DESCRIZIONE Totale (€)
Unitario (€)
1.1 Linear Heat Detector 6,80 --,00
Linear heat detector, composed of two steel conductors, with an external diameter of
0,8mm, independent and individually surrounded in an heat sensing polymer.
Conductors are twisted in a way to guarantee that between them will always be present
the mechanical strength necessary for a suitable intervention.
All that is wrapped with a protective tape. The outer sheath is completed with an external
vinyl jacket which increase the mechanical stability and offer resistance to chemical and
environmental agents.
- Two poles thermosensible cable with EPC external coating.
- External diameter: ± 4mm
- Intervention temperature: 88°C (190°F)
- Installation temperature: -40÷66°C
- Certification: UL and FM as linear heat detector
- External cable sheath: PVC based, red coloured
- Marking at regular intervals of 1mt indicating nominal features of the cable and
UL, FM certification markings.
Cod: EPC190
Q.ty: ---- 6
1.2 Cable fixing clip. 0,50 ---,00
Sensor cable fixing clip, model CL2. Clip has two “pass thru” openings able to support sensor
cable and further steel rope.
Clip is made of polypropylene, and it is supplied with nut washer and bolt.
Cod: CL2
Q.ty: ----
CAVI TERMOSENSIBILI UL/FM – RIVELATORI TERMICI STAGNI, ATEX, UL/FM – APPLICAZIONI PER SISTEMI ANTINCENDIO 1
Prezzo
ITEM DESCRIZIONE Totale (€)
Unitario (€)
2.1 MAR2 Panel, Rack 19” version, suitable to manage up to 32 detection zones. 4.000,00 ---,00
Power supply: 220Vac via a 220Vac / 24Vac transformer that shall be placed on the internal
plate of the cabinet and has to be connected to Power Supply card.
The power supply card acts as battery charger, if backup batteries are connected.
LCD display signalling of the alarm point with indication of the distance in metres or feets
(selectable).
Cod: MAR2_RACK
Q.ty: 1
2.2 Line start box, complete with terminals, and PG9 cable glands for L.H.D. cable, and resistors. 180,00 ---,00
Material of the boxes GRP (glass reinforced polyester) .Protection degree IP65.
Cod: BRT0.IL
Q.ty: ----
2.3 End Of Line box, complete with terminals, and PG9 cable glands for L.H.D. cable, and 180,00 ---,00
resistors. Material of the boxes GRP (glass reinforced polyester) .Protection degree IP65.
Cod: BRT0.FL
Q.ty: ---
2.4 Test boxes, complete with terminals, and PG9 cable glands for L.H.D. cable, and key switch to 225,00 ---,00
simulate the intervention of cable. Functionally those boxes are not necessary, but the
insertion of those items along one branch of sensor cable (or i.e. each 300mt of cable) is a
good practice for maintenance and alarm simulation purposes. Material of the boxes GRP
(glass reinforced polyester) .Protection degree IP65.
Cod: BRT0.TS
Q.ty: ---
2.5 Intermediate boxes, complete with terminals, and PG9 cable glands for connection between 180,00 ---,00
L.H.D. cable, and key switch boxes. Material of the boxes GRP (glass reinforced polyester).
Protection degree IP65.
Cod: BRT0.T
Q.ty: ---
General Condition:
We remain at your disposal for any further information, or clarification you need. Best regards
Davide BARILLA’