Water Demand and Sprinkler Design
Water Demand and Sprinkler Design
Type MV
The TYCO Type MV Nozzles are open (non-automatic) directional spray nozzles designed for use in wate
The MV Nozzles are effective in covering exposed vertical, horizontal, curved, and irregular shaped surf
an external fire and possible structural damage or spread of fire to the protected equipment.
In some applications, depending on water design density requirements, the Type MV Nozzles may also
They are external deflector-type nozzles that discharge a uniformly filled cone of medium velocity wate
Type MV-R
The Tyco andMV-R
Type MV-TReverse
(Type MV-R
ActionReverse Action
and Type MV-Tand Type
Tank TopMV-T Tank
Nozzles areTop Open
open Nozzles Medium
(non-automatic) Ven
spray
protection of vessels
They are external or structuresnozzles
deflector-type containing highly flammable
that discharge liquids,
against the gasesof
direction andthesolids having
orifice in a flashpoi
determined areanozzles are effective in covering exposed vertical, horizontal, curved, and irregular shap
MV-R and MV-T
heat from an external fire and possible structural damage or spread of fire to the protected equipment
They also MV-R
The Type promote vaporAction
Reverse dilution and dispersion.
Nozzle, designed specifically to protect spherical vessels and bulk storag
angle conical spray pattern.
1. Brass
zzles designed for use in water spray fixed systems for fire protection applications. 2. Pressure range at inlet of nozzle 1
ed, and irregular shaped surfaces in a cooling spray to prevent excessive absorption of heat from 3. Axial distance from the nozzle tip
tected equipment.
e Type MV Nozzles may also be used for fire control or extinguishment.
one of medium velocity water droplets. Area Coverage is based on
orifice types (eg.,
MV10,12,15,18,19,21,25,26)- 2
to 3.5m2
p Open
open Nozzles Medium
(non-automatic) Velocity)
spray nozzles designed for use in water spray fixed systems for fire 1. Brass
es and solids having flashpoints of 66°C
on of the orifice in a uniformly filled (150°F)
spray and
pattern of below.
medium velocity water droplets over a pre-
al, curved, and irregular shaped surfaces in a cooling spray to prevent excessive absorption of
to the protected equipment.
erical vessels and bulk storage tanks, can be installed at any angle and discharges a 118° reverse
ure will result in a decrease in coverage area since the spray patterns tend to draw inwards at higher pressures
metal is using
area is covered for each nozzle
ge pressure of each nozzle is 1.4 to 4.1 bar
stance from nozzle tip is 0.6 meter or les
spray angles of 65 to 140C
diamter and K-factor will get from Table-A
ngles are 65,80,95,110,125,140,160,180
erage is based on
es (eg.,
15,18,19,21,25,26)- 2
S.No. Name Material Area covered in m2 Pressure range in bar
1 Type D3 PROTECTOSPRAY Bronze 2.5 1.4 to 4.1
2 Type MV Brass 2 to 3.5 1.4 to 4.1
3 Type MV-R and MV-T Brass 1.75 1.4 to 4.1
Axial Distance in m Orifice dia in mm K-Factor (lpm/bar^1/2)
< 0.65 5.16 to 12.7 17.3 to 103.7
< 0.65 5.15 to 12.6 17.3 to 100.8
0.75 5.15 to 12.6 17.3 to 100.8
Spray Angles Type of Orientation
658,095,110,125,140,000,000 Upright
9,095,110,125,140,160 Pendent
No Upright
Note
As per layout
No. of rings 7
No. of nozzles 77
No. of nozzles in First ring 21
No. of nozzles in Second ring 17
No. of nozzles in Third ring 15
No. of nozzles in Fourth ring 11
No. of nozzles in Fifth ring 7
No. of nozzles in Sixth ring 5
No. of nozzles in Seventh ring 1
Case-1
1 Axial Distance from Nozzle Deflector to Tank Roof 0.7 m
Radial Distance from Nozzle Centrelne (Coverage) 1.675 m
Surface area coverage of each Nozzle 8.81 m2
Total Tank surface area 1351.4 m2
Tank surface area for each riser 675.70 m2
No. of Nozzles required as per coverage area of each nozzle 77 nos
4 As per Layout
Total no. of rings 7 nos
Total no. of nozzles 77 nos
No. of nozzles on 1st rong 21 nos
No. of nozzles on 2nd rong 17 nos
No. of nozzles on 3rd rong 15 nos
No. of nozzles on 4th rong 11 nos
No. of nozzles on 5th rong 7 nos
No. of nozzles on 6th rong 5 nos
No. of nozzles on 7th rong 1 nos
Wet crude storage tank
Case-1 Case-2
Tank half of diamter 20.6 m
R Run down distance 2 R
Effluent Tank
Case-1
Tank half of diamter 14.5 m
R Run down distance 2.25
Note: Recommended operating pressure range is between 1.4 and 3.5 kg/cm2.g
Water Demand & Spray Nozzle Calculation for 200 KL
Horizontal Tank
Note: Recommended operating pressure range is between 1.4 and 3.5 kg/cm2.g
L 16200 16.2
D 4000 4
203.5757
m3