START-UP CHECKLIST

UNIT : .................. Document No. : SLK-KTG1-OPR-CL-TBN-004


SYSTEM : TURBINE LUBE OIL SYSTEM START-UP PERIOD : ............ / ........... / .................

NO EQUIPMENT RECOMMENDED Check ( √ ) REMARKS

OIL EXHAUSTER FAN


1 Make sure there’s no maintenance works at gas exhaust Fan No LOTO

2 Make sure power source is ready and rackin position and switch to remote Power On

Make sure main oil tank level is normal from local or


Highgest Level
3 DCS monitor (normal 1520 mm , highest 1720 mm ,
(1720 mm)
lowest 1320 mm trip 1270 mm )

4 Manual Valve Outlet Oil Extractor Fan Must be Open

Visual inspection after fan running


- Any leakage of oil No any leakage
5
- Abnormal sound Normal sound
- Any vibration to line or fan Normal vibration

AC OIL PUMP
make sure no loto and
1 Make sure there’s no maintenance works at AC Oil Pump area
tag out at DCS
Make sure power source is ready and rackin position and switch to
2
remote
3 Make sure three way valve is open (oil inlet and outltet Must be Open

Pressure 0.6 Mpa


4 Make sure cooling water system operates normally
and temperature 32 C )

make sure oil temp normal 21 C ready to start

pressure main oil tank


5 Make Sure oil pressure tank is vacuum (local indication )
- 0.001 Mpa

Visual inspection after Pump running


- Any leakage of oil at oil line No any leakage
6
- Abnormal sound Normal sound
- Any vibration to line or pump Normal vibration

DC OIL PUMP

1 make sure three way valve is open (oil inlet and outltet ) Must be Open

Visual inspection after Pump running


- Any leakage of oil No any leakage
2
- Abnormal sound Normal sound
- Any vibration to line or pump Normal vibration

JACKING OIL PUMP

1 Make sure there’s no maintenance work at Jacking Oil Pump area

2 Make sure source power is ready Power On

Pressure Inlet 0,03 Mpa


3 Make sure AC oil pump operates normally
(Local indicator)

Check Pressure before


4 Make sure JOP strainer in clean condition and operates normally
and after filter

5 All Inlet Manual Valves Must be Open

6 All Outlet Manual Valves Must be Open

7 Oil leaking Must be no leak

TURNING GEAR

Must be Circulating
1 AC Oil Pump
(check oil sigh glass)

Must be on Operation
2 Oil Extractor Fan (Check main oil tank
pressure)

3 Jacking Oil Pump Must be Run

4 Lubricating Pressure Sufficient (0,18 MPa)


NO EQUIPMENT RECOMMENDED Check ( √ ) REMARKS

5 Turbine Shaft Rotation Must be Stop

6 Manual Valve for Oil Supply to Turning Gear Must be Open

7 Switch Control Must be "LOCAL"

Checked by : Approved by :

Turbine Operator DCS Operator Shift Leader