WALL MOUNTED TYPE

Sound level

WALL MOUNTED 43/ 37dB(A) Below features only apply to FAY71L.

Drastic size reduction


Improved airflow modes realise comfortable air distribution across the entire room

TYPE Auto-swing 5-level air direction setting Auto-air direction control


High Low
FAY71L
Reduced size (by 22% in volume,
32% in installation area)makes

FAY installation possible in a very limited


FAY71LVE 10° 10° 10°

Sound level space. Conventional model


The air direction is set automatically
(FAY71FAVE)

45/ 41dB(A)
to the memorised position of the
-70 mm
Auto-s wing S ettable to 5 previous air direction.
from 10° to 70° 70° different levels 70° (Initial setting is 10° for cooling 70°
-200 mm
Cooling only FAY71LVE / FAY100FAVE High Low
FAY100FA 290 mm
between 10° to 70° and 70° for heating.)

Heat pump FAY71LVE / FAY100FAVE Comfort even on the far side of the room
1,050 mm
To carry air to the far side of long rooms, extra-
high airflow adds 10% more fan speed the "high"
Made more compact, FAY100FAVE Sophisticated extension design setting. Air discharge strength is selected from the
remote controller.
stylish, and quieter Accessory required for indoor unit (option) Compact and stylish design that does
not detract from the decor of the room.
Wired LCD remote controller Wireless LCD remote controller Two selectable temperature-sensors Easier to install and service
A s ignal rec eiver mus t be
added to the indoor unit.
Flap is closed when not operating Both indoor unit and wired remote
Signal receiver unit
(Installed type)
controller (option) contain temperature- Maintenance possible from
Easier to install and service
Cooling only
sensors. Temperature sensing can be the front of the unit
BRC7E619 Light weight set at the unit or, to further improve All maintenance tasks can be carried
Heat pump comfort level, closer to the target area out via front access. During service
BRC7EA618 FAY71L Reduced weight by 8kg greatly
at the wired remote control. work, attachment and detachment of
BRC1C61 Cooling only facilitates installation. *Temperature-sensor on indoor unit must be used
BRC7C611W when the air c onditioner is c ontrolled from another parts is easier.
Heat pump
Conventional New model room.
Note: R emote c ontroller c able not BRC7C610W FAY100F
(FAY71FAVE) (FAY71LVE) **Wireles s remote c ontroller does not have a Low gas pressure detection
Wireles s remote c ontroller and s ignal 21 Kg 13 Kg
Programme "Dry" Insufficient gas charging is normally
inc luded. C ables must be
proc ured loc ally. rec eiver unit are s old as a s et.
Drain pump kit is available as option. Dehumidification is microprocessor hard to detect. During post-installation
Installs onto side of unit.
controlled to prevent abrupt and trials and regular inspection procedures,
Height of drain up
uncomfortable changes in air temperature. the refrigerant level is monitored by
microprocessor to maintain proper gas
1,000 mm Switchable fan speed: High/Low pressure.

Indoor unit
Drain-pump kit
(Available to be installed onto right side.)

Drain enclosure can


be used on either
left and right side.
Drain pan and air filter can be kept
clean by mould-proof polystyrene
Removable and washable grille
DIII-NET connection is standard
specification. Adapter is not required.

Features (Features are explained on P. 37–38.)


Mould
Feature Comfort prevention Work & Servicing Control features Others

Draft prevention func tion

Drain pump mec hanis m


High fan s peed mode

C entral remote c ontrol


S elf-diagnos is func tion
S witc hable fan s peed

E mergenc y operation

C ontrol by 2 remote

C ontrol by 1 remote
Auto-c ooling/heating
temperature-s ens ors

Year-round c ooling

E xternal c ommand
Low gas pres s ure
treatment for filter
Programme "Dry"

Pre c harged for

Interloc k c ontrol
Mould res is tant
Two s elec table

Mould-proofing
Timer s elec tor

up to 30 m

c hange-over
Auto-res tart
Auto s wing

applic able

Filter s ign
drain pan

c ontrollers
detec tion
Hot s tart

c ontroller
Upward

c ontrol

PE fin
Model
Cooling only *1 *2 *4 *4

Heat pump *1 *3 *4 *4

*1Applic able when wired remote c ontroller is us ed


*2Applic able to R 71LU/R 100LU outdoor units (for temp. down to – 15°C ) (An option is required.)
*3Applic able to R Y71LU/R Y100LU outdoor units (for temp. down to – 5°C )
*4Applic able to R (Y)71LU/100LU outdoor units
Guide Line up Outdoor units Remote controllers Standard specifications Options Outer dimension drawings
23 P. 3–4, 7–8 P. 33–34 P. 35–36 P. 41, 51 P. 58 P. 62, 63 24
FLOOR STANDING TYPE
Sound level

FLOOR STANDING
TYPE
41/ 35
High Low
FVY71LA
dB(A)
Quiet operation

Indoor unit High Low


dB(A)
Lightweight
Easier to install and service

71LA 41 35 The unit can be easily transported and


100LA 46 40 installed.

FVY
Note : Anec hoic c hamber c onvers ion value,
meas ured ac c ording to J IS parameters and
125LA 49 43 Weight
Indoor unit Conventional
New model
FVY-F
Auto-swing delivers comfort to every corner of the room 71 class 45 kg 39 kg
Cooling only FVY71LAVE–125LAVE FVY units have swinging louver spreads comfortable airflow. Any uncomfortable 100 class 63 kg 46 kg
Heat pump FVY71LAVE–125LAVE sensation of sudden change is avoided by a slow cycle of 2 to 3 full swings per 125 class 67 kg 47 kg
minute.
Auto-swing Manual setting of vertical airflow louvers Long-life filter lasts about 1 year *
The floor-standing Maintenance not required
configuration means
*For dust concentration of 0.15 mg/m3
LCD control panel is standard
Filter exchange interval

the FVY is easy to install


Annual
and maintain. 2 weeks
Conventional Long-life filter

It can also be installed


filter

Vertical airflow adjustment is possible when

under high ceilings. Note: This remote controller has a temperature-


sensor.
(changing between cooling and heating or) to
match interior spaces and partitions. Low gas pressure detection
Insufficient gas charging is normally
A good choice for spaces with Programme "Dry" hard to detect. During post-installation
ceilings so high that heating by Dehumidification is microprocessor con- trials and regular inspection procedures,
ceiling-mounted units is inefficient. trolled to prevent abrupt and uncomfort- the refrigerant level is monitored by
Note: For optimal installation, space factors should be able changes in air temperature. microprocessor to maintain proper gas
accurately calculated.
pressure.
Switchable fan speed: High/Low

Easy-to-operate, handy LCD control panel


The LCD displays text, numbers and graphics to indicate the temperature setting,
timer setting, auto-swing, fan speed, and more. Furthermore, the LCD panel can
be detached and used as a remote controller, so air conditioning can be controlled
from another room or from the cash register.
(Remote controller cable not included. Cables must be procured locally.)

Two selectable temperature-sensors


Temperature-sensors on both indoor unit and wired remote controller.
Temperature sensing can be set closer to the target area to further improve
comfort level.
*Temperature-sensor on indoor unit must be used when the air c onditioner is c ontrolled from another room.
**Wireles s remote c ontroller does not have a temperature-s ens or.

Features (Features are explained on P. 37–38.)


Mould
Feature Comfort prevention Work & Servicing Control features Others

C entral remote c ontrol


S elf-diagnos is func tion
S witc hable fan s peed

E mergenc y operation

C ontrol by 2 remote

C ontrol by 1 remote
Auto-c ooling/heating
temperature-s ens ors
Year-round c ooling

E xternal c ommand
Low gas pres s ure
treatment for filter
Programme "Dry"

Pre c harged for

Interloc k c ontrol
Mould res is tant
Two s elec table

Timer s elec tor

Long-life filter
up to 30 m

c hange-over
Auto-res tart
Auto s wing

applic able

Filter s ign

c ontrollers
detec tion
Hot s tart

c ontroller

c ontrol

PE fin
Model
Cooling only *1 *3 *3

Heat pump *2 *3 *3

*1Applic able to R 71LU– R 125LU outdoor units (for temp. down to – 15°C ) (An option is required.)
*2Applic able to R Y71LU– R Y125LU outdoor units (for temp. down to – 5°C )
Guide Existing
Line up models: Outdoor units
units: Remote controllers
controllers: Standard specifications
specifications: Options Outer dimension drawings
Options: drawings: *3Applic able to R (Y)71LU– 125LU outdoor units
25 P.33–4,
P. ~ 4 7–8 P.25
P. 33–34
~ 26 P.27
P. 35–36
~ 28 P.34
P. 42, 52 P.36
P. 58~ 37 P.
P.38
63~ 45 26
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Sound level

DUCT CONNECTION
MIDDLE STATIC PRESSURE TYPE 39 dB(A)
High
FDYM03FA
Freedom of layout
The duct system allows the efficient location of discharge outlets
Quiet operation

Indoor unit High


dB(A) (220V)
LOW
(220V) in accordance with the room layout FDMG71A 42 38

FDMG/FDYM
FDMG100A 44 36
FDMG100A Middle static pressure type is available in a larger than standard space
FDMG125A 45 37
FDMG140A 46 36
Duct connection is simpler with standard rear intake chambers FDMG180A 47 37
Cooling only FDMG71AV1–180AV1
FDYM03FA 39
FDYM03FAV1–06FAV1 FDYM04FA 39
Heat pump FDYM03FAV1–06FAV1 Compact, 295 mm high design makes installation possible where the FDYM05FA 44
ceiling space is limited (For FDYM) FDYM06FA 46
FDYM03FA Note : Anec hoic c hamber c onvers ion value,

Unit can be mounted Ordinary duct


(procured locally)
Air conditioner Ordinary duct
(procured locally)
meas ured ac c ording to J IS parameters and

in the ceiling and air can be


295 mm
Accessory required for indoor unit (option)
305 mm or more
Switchable fan speed: High/Low
For FDYM
delivered freely by duct. Wired LCD remote controller Wireless LCD remote controller Air blow Air intake

Programme "Dry"
Dehumidification is microprocessor
controlled to prevent abrupt and un-
comfortable changes in air temperature.
Signal receiver unit
(Separate type)
BRC1C61 Cooling only
Wireles s remote
Note: R emote c ontroller c able not BRC4C64 c ontroller and Low gas pressure detection
inc luded. C ables must be Heat pump s ignal rec eiver unit
proc ured loc ally. BRC4C62 are s old as a s et. Insufficient gas charging is normally
Supports simultaneous running of the twin and hard to detect. During post-installation
For FDMG
triple multi operations. trials and regular inspection procedures,
Digital remote controller Remote controller Twin Multi Operation Triple Multi Operation
the refrigerant level is monitored by
microprocessor to maintain proper gas
pressure.
KRC47-2A KRC47-1A
KRC47-4A
See pages 31–32 for details of the Multi Series.

Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
When air conditioning two rooms Door-installed Wall-installed
Under-door cutout
simultaneously, the air discharged into each ventilation grille ventilation grille

room must be circulated back to the air


conditioner. To achieve this, a ventilation
Ventilates air through
duct should be installed for each room or one Partitioning wall
the partitioning wall.
of the indicated ventilation grilles should be (S ee right)

installed on the partitioning wall or under the Ventilation grille Ventilation grille Under-door c utout

door between the rooms. Note: The under-door cutout method should be used only when there is a small volume of airflow.

Features (Features are explained on P. 37–38.)


Feature Comfort Work & Servicing Control features Others

G roup c ontrol by 1 remote


S elf-diagnos is func tion
S witc hable fan s peed

E mergenc y operation

C ontrol by 2 remote
Automatic c ool/heat

Twin and triple multi

Adjus table external


Year-round c ooling

E xternal c ommand
Low gas pres s ure
Programme "Dry"

Pre c harged for

Interloc k c ontrol
C entral remote

s tatic pres s ure


Timer s elec tor
c hange -over

up to 30 m

Auto-res tart
applic able

c ontrollers
detec tion
Hot s tart

c ontroller

operation
c ontrol

c ontrol

PE fin
Model
Cooling FDMG
only FDYM *1 *3 *3

Heat pump *2 *3 *3

*1Applic able to R 71LU– R 140LU outdoor units (for temp. down to – 15°C ) (An option is required.)
Guide Line up Outdoor units Remote controllers Standard specifications Options Outer dimension drawings *2Applic able to R Y71LU– R Y140LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C )
P. 3–10 P. 33–34 P. 35–36 P. 43, 48, 53, 56 P. 59 P. 64, 65 *3Applic able to R (Y)71LU– 140LU outdoor units
27 28
Sound level
DUCT CONNECTION Sound level
DUCT CONNECTION
LOW STATIC PRESSURE TYPE
38 dB(A)
HIGH STATIC PRESSURE TYPE 51 High
dB(A)

FDBG/FDYB FD( Y)
LOW
FDY06KA
FDYB50KA
(220V)

FDYB50KA FDY06KA
Cooling only FDBG25AVE–71AVE Cooling only FD03KY1–20KY1
Heat pump FDYB35KAVE–71KAVE Accessory required for indoor unit (option)
Heat pump FDY06KAY1–20KAY1 Accessory required for indoor unit (option)
Cooling only Cooling only
Digital remote controller Remote controller Remote controller

KRC47-2A KRC47-1A KRC47-3A


KRC47-4A Heat pump
Heat pump Wired LCD remote controller Wireless LCD remote controller
Wired LCD remote controller Wireless LCD remote controller

Signal receiver unit


Signal receiver unit BRC1C61 (Separate type)
BRC1C61 (Separate type) Wireles s remote
Wireles s remote Note: R emote c ontroller c able not c ontroller and
Note: R emote c ontroller c able not c ontroller and inc luded. C ables must be BRC4C62 s ignal rec eiver unit
inc luded. C ables must be BRC4C62 s ignal rec eiver unit proc ured loc ally. are s old as a s et.
proc ured loc ally. are s old as a s et.

Ideal for quiet, beautiful living spaces Recommended for spacious and large-volume areas because of its flexible installation
Suitable for condominiums and apartments, houses and hotels Suitable for large stores, factories, and other large areas, and for use with housing
ducts in homes
Quiet operation Compact
dB(A)
Small, lightweight, and easy-to-install outdoor unit. Quiet operation Central control
Indoor unit High Low
FDBG60AVE 42 39
Many options are available for use with large-scale and
Durable advanced-function centrally controlled systems
Note : Anechoic chamber conversion value,
measured according to J IS parameters and criteria. Highly durable outdoor unit has PE fins for improved
resistance to salt corrosion and atmospheric pollution.
Durable S uc tion c hamber
To achieve increased durability by improved resistance [Duc t c onnec tion]
Air filter Features (Features are explained on P. 37–38.)
to salt corrosion and atmospheric pollution, coated PE Guide
To prevent increased operation sound, avoid installing the air suction grille Feature Comfort Work & Servicing Control features Others
fins (with special acryl pretreatment) are used for the

G roup c ontrol by 1 remote


directly below the suction chamber. Line up
heat exchanger of the outdoor unit. P. 3–4, 7–8

S elf-diagnos is func tion


E mergenc y operation

C ontrol by 2 remote
Automatic c ool/heat
Outdoor units

Adjus table external


Year-round c ooling

E xternal c ommand
Low gas pres s ure
Triple Multi Operation Double twin Multi Operation
P. 33–34

Pre c harged for

Interloc k c ontrol
Supports

C entral remote

s tatic pres s ure


Timer s elec tor
c hange -over
Remote controllers

up to 30 m
simultaneous

Auto-res tart
P. 35–36

applic able

c ontrollers
detec tion
Hot s tart

c ontroller
running of the Standard specifications

c ontrol

c ontrol

PE fin
triple and double Model P. 44, 45, 53
twin multi Options
Cooling only *3
P. 59
operations. Heat pump *4 *1 *2 *2 *4 *3 Outer dimension drawings
See pages 31–32 for details of the Multi Series.
*1Applic able to R Y140LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. downP.
to 65–67
– 0°C )
Features (Features are explained on P. 37–38.) *2Applic able to R (Y)140LU outdoor units
*3R equired to c hange the pulley
Feature Comfort Work & Servicing Control features Others *4FDY06-10 only
G roup c ontrol by 1 remote
S elf-diagnos is func tion

Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
S witc hable fan s peed

E mergenc y operation

Triple and double twin


C ontrol by 2 remote
Automatic c ool/heat

Adjus table external


Year-round c ooling

E xternal c ommand
Low gas pres s ure
Programme "Dry"

When air conditioning two rooms


Pre c harged for

Interloc k c ontrol

Door-installed Wall-installed
C entral remote

s tatic pres s ure


Timer s elec tor

Under-door cutout
c hange -over

multi operation

simultaneously, the air discharged into each ventilation grille ventilation grille
up to 30 m

Auto-res tart

room must be circulated back to the air


applic able

c ontrollers
detec tion
Hot s tart

c ontroller

conditioner. To achieve this, a ventilation


c ontrol

c ontrol

PE fin

Ventilates air through


Model duct should be installed for each room or one Partitioning wall
the partitioning wall.
of the indicate ventilation grilles should be (S ee right)
Cooling only * Applic able to R Y71LU outdoor units (for temp. down to – 5°C )
1

and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C ) installed on the partitioning wall or under the Ventilation grille Ventilation grille Under-door c utout
Heat pump *1 *2 *2 *2Applic able to R Y71LU outdoor units door between the rooms. Note: The under-door cutout method should be used only when there is a small volume of airflow.

Guide Line up Outdoor units Remote controllers Standard specifications Options Outer dimension drawings
P. 3–10 P. 33–34 P. 35–36 P. 42, 52, 56 P. 59 P. 64
29 30
Simultaneous operation system
MULTI SERIES

Simultaneous operation system Remote controllers for the Multi Series

MULTI SERIES INDOOR UNIT Wired LCD remote controller Wireless LCD remote controller
Twin, Triple, and Double Twin Multi-Operation (Option) (Option)
CEILING MOUNTED Cooling only BRC7C613W
CASSETTE TYPE Heat pump BRC7C612W
Cooling only BRC7EA66

Simultaneously operates
CEILING SUSPENDED TYPE Heat pump BRC7E63W
BRC1C61
DUCT CONNECTION Heat pump BRC4C62

2 to 4 indoor units using LOW STATIC PRESSURE TYPE


DUCT CONNECTION Cooling only BRC4C64

a single outdoor unit.


MIDDLE STATIC PRESSURE TYPE Heat pump BRC4C62

A single remote controller Connect the wired remote controller Install the signal receiver unit (part
In large interior spaces a single indoor unit In a single-floor restaurant, for example, positioning 4 units at controls simultaneous to turn an indoor unit into the master of the optional wireless remote
may not be able to provide uniform comfort. strategic locations realises comfortable airflow that reaches operation of multiple indoor units. unit. controller) to turn an indoor unit into
every inch of the room. the master unit.
Installation of 2 to 4 units, can provide an Note: This type of system does not allow individual control or independent operation of indoor
effective solution. units. It is not the best choice for large rooms with partitions.

Supports Two selectable Wired remote controller has a Because the wireless remote
Installing multiple units is economical and realises comfort temperature-sensor functions. temperature-sensor. Depending on
the installation conditions, select
controller does not have a
temperature-sensor, select the
Lower cost of installation than for individual pair type Note: Selectable temperature sensing is available and set the temperature-sensor of a temperature-sensor of the indoor
with ceiling-mounted cassette and ceiling- selected indoor unit or the temperature- master unit.
Reduced installation space for outdoor units suspended models, but not with middle static-
sensor of the remote controller.
pressure models.
Enhanced comfort from distributed indoor units
Note: An indoor unit's temperature-sensor must
be used when the air conditioners
Indoor units include ceiling mounted cassette type, ceiling suspended type, and duct connection middle and low static pressure type. are controlled from another room.

Double Twin Multi operation


4 indoor units can be run simultaneously Improved comfort level and space-saving Piping Guideline
for outdoor unit installation
with a single outdoor unit. Before New Twin Multi Operation Triple Multi Operation Double Twin Multi Operation
5 HP x 2 units 10 HP double twin multi operation

Sub
Sub unit Sub
Sub unit Sub unit Sub
unit Main unit Main L3 unit Main
unit unit unit
Dead zone

Dead zone

L1 L4
L1 L2 L5
Branch L2 Branch L3 L1 L6
piping kit piping kit
Branch
piping kit
Remote Remote L2 Remote
Main pipe controller Main pipe controller Main pipe controller
L L L
Branch piping kit
Branch piping kit Required about 40% less installation space
for outdoor unit Outdoor unit Outdoor unit Outdoor unit
Branch piping kit
Before New
R(Y)125KU x 2 units R(Y)200KU or R(Y)250KU x 1 unit

4 indoor units distribute comfortable airflow 300 mm 500 mm


Simultaneous operation system Twin Multi Operation Triple Multi Operation Double Twin Multi Operation
throughout the room. Max. piping length L Max. (L1, L2) 50 m L Max. (L1, L2, L3) 50 m L Max. (L1, L2) Max. (L3, L4, L5, L6) 50 m
Simultaneous operation of four indoor units Max. branch piping length Max. (L1, L2)*1 20 m Max. (L1, L2 , L3) 20 m Max. (L1, L2) Max. (L3, L4, L5, L6) 20 m
can be controlled from a single remote controller. 1000 mm
300 mm
Max. branch pipe length difference Max. (L1, L2) Min. (L1, L2)*2 10 m Max. (L1, L2, L3) Min. (L1, L2, L3) 10 m (L2 L6) (L1 L3) 10 m
L2 L1 10 m
Requires a single refrigerant piping system. L4 L3 10 m
L6 L5 10 m
In case of L1 L2, L3 L4, L5 L6

Max. level difference between outdoor unit and indoor units 30 m 30 m 30 m


Triple Multi operation Twin Multi operation Max. level difference between indoor units 0.5 m 0.5 m 0.5 m
*1 Max. (L1, L2) means maximum length out of L1 and L2.
*2 Min. (L1, L2) means minimum length out of L1 and L2.

Refrigerant piping uses terminal branching to facilitate installation.


(Branch piping kits are sold separately. Please use the model indicated on page 59)
Branch piping kit
Branch piping kit

Guide Line up Outdoor units Remote controllers Standard specifications Options Outer dimension drawings (For Twin Multi) (For Triple Multi) (For Double Twin Multi)
31 P. 5–6, 9–10 P. 33–34 P. 35–36 P. 46–48, 54–56 P. 57–59 P. 60–74 32
OUTDOOR UNIT

P o w e r fu l Ins ta lla tion a nd ma intena nc e


Compact unit provides Uses "Receiver" Pre charged for up to 30 metres
Flexible design
OUTDOOR UNIT quiet operation.
to enhance refrigerant control
(Applies to R(Y)71LU–140LU)
If refrigerant piping length does not
exceed 30 m, there is no need for on- for large room
Instead of the using an accumulator to ab- site gas charging.
sorb excess refrigerant, Daikin outdoor
units have a receiver in the piping located
(Applies to R(Y)71LU–140LU)
or multi-use
away from the compressor. By preventing Allowed refrigerant pipe length and
level difference
the return of liquid to the compressor, the
Pre charged Max. length Max. level
receiver enhances reliability. *1 difference
R25J 10 m 25 m 15 m
Defrost control delivers powerful RY35F 10 m 20 m 15 m
heating in extremely cold climates R35J 10 m 25 m 15 m
(Applies to RY71LU–140LU) (Heat pump only) RY50GA 10 m 30 m 15 m
R50G
To optimise heating performance, by RY60GA 5m 30 m 15 m
R60G
monitoring the difference in air temperature RY71LU 30 m 50 m 30 m
R71LU (Equivalent length 70 m)
in the indoor/outdoor heat exchanger and RY100LU 50 m
30 m 30 m
the intake air temperature, the system R100LU (Equivalent length 70 m)
RY125LU 50 m
accurately adjusts to provide the best R125LU
30 m (Equivalent length 70 m) 30 m

R(Y)71LU R(Y)100LU R(Y)125LU R(Y)140LU operating parameters. RY140LU 30 m 50 m


(Equivalent length 70 m) 30 m Piping can be drawn out from three
R140LU
This enables defrost mode to be initiated RG71A directions - front, left side, or below.
RA140A 50 m
and so minimise indoor declines in RG180A
5m (Equivalent length 70 m) 30 m

Q u ie t O pe r a t io n temperature caused by frost. For example, if


the outdoor airtemperature falls to -1.5°C,
R100FU
R125FU
5m 50 m
(Equivalent length 70 m) 30 m 200 and 250 class models can
the integrated heating capacity is raised
Note: Additional refrigerant charging is required if the
1

refrigerant pipe is longer than the length.


be combined for centralised,
Fitted with wide inlet fan Fitted with Super Aero Grille Equipped with scroll compressor about 20%. horizontal-series installation
(Applies to R(Y)71LU–140LU) (Applies to R(Y)71LU–140LU)
for quiet operation Integral heating capacity and temperature difference Common width and depth make
Fully shaped aerodynamic propellers To suppress turbulence and achieve (Applies to R(Y)125LU and 140LU) (actual measurement when outdoor temperature is -1.5°C) 4-direction piping offers series installation easy.
°C
are designed to push air with a large quiet operation, the curved ribs of the Smooth running, minimal vibration, 25
Defrost begins
greater layout freedom
R(Y)200KU R(Y)200KU R(Y)250KU
wing surface, providing both high grille are optimised to meet the low operating sound. 20
in this area (Applies to R(Y)71LU–140LU)
Integral heating
blow volume and quiet operation with outflow of air. Piping can be run from the front, 690 mm

Defrost and hot start


capacity
15
turbulence. bottom, right or rear surface 1280 mm 1280 mm 1280 mm

integral capacity
according to how the unit is installed.

Max. point of
10

Difference between Allowed refrigerant pipe length and


5 indoor heat exchange level difference
temperature and intake
air temperature ( T) Facilitates pump down Pre charged Max. length Max. level
0
0 10 20 30 40 50 60 70 80 (Refrigerant recovery function) *1
50 m
difference

Elapses operation time (min.) R(Y)200KU 5m (Equivalent length 70 m) 30 m


A pump-down switch is provided to 50 m
R(Y)250KU 5m 30 m
Defrost operation complete Defrost monitoring start make it easier to collect refrigerant if (Equivalent length 70 m)

(heating operation restart) (monitors to maximum point) Note: 1Additional refrigerant charging is required if the
the unit is to be moved or layout refrigerant pipe is longer than the length.

modified.
Suited for year-round cooling Also adapts to year-round cooling
Wide inlet fan applications Low gas level detection function RY200KU and250KU can adapt up to 0°C.
(Applies to R(Y)71LU–140LU) Operation sound dB(A) Cooling is efficient even in winter when (Applies to R(Y)71LU–140LU) (Heat pump only)

Heat pump indoor temperatures are higher than those Effective gas monitoring reduces the RU08/10K models are available
Sound level (cool/heating)
Outdoor unit outside, such as in underground public spaces labor required for operation, in two type depending on
C o m pa c t RY71LU 48/49 or offices with many computers. maintenance, and repairs. installation conditions
• Heat pump/RY71–140LU: possible up to -5°C
Slim and low-profile design outdoor units RY100LU 49/52 • Cooling only/R71–140LU: possible up to -15°C RU08/10KU models are factory
• The year-round cooling kit is required as option.
(Applies to R(Y)71LU–140LU)
RY125LU 49/52 shipped with refrigerant charged for
Compactly designed outdoor unit 5 m of piping.
The design curved Super Aero RY140LU 54/56
with interior layout optimised for the RU08/10K models are factory
Grille restricts the spread of Cooling only shipped with no refrigerant charged.
smooth airflow. exhaust gas and fits in the same Outdoor unit
Sound level
space as conventional outdoor
units. R71LU 48
Reduced weight
(Applies to R(Y)71LU-125LU) R100LU 49 D u r a bilit y
The light weight makes delivery and R125LU 49
installation easier. Heat exchange fins provided with anti-corrosion treatment (Applies to all outdoor units)
R140LU 54
To achieve increased durability by Construction
conventional New Note : Anec hoic c hamber c onvers ion value,
improved resistance to salt corrosion
50 meas ured ac c ording to J IS parameters and Non-treated fin Aluminium

108 kg 89 kg 500
and atmospheric pollution, coated PE
fins (with special acryl pretreatment) PE fin Hydrophilic film
RY100KUV1 RY100LUV1 Aluminium
(mm) are used for the heat exchanger of the C orrosion resistant
ac rylic resin
outdoor unit.
33 34
LCD REMOTE CONTROLLER
Easy-to-read LCD remote
LCD REMOTE controller allows various system L C D pa n e l s h o w s o pe r a t in g s t a t u s in le t t e r s , n u m be r s , a n d m o t io n .
Airflow / swing display Displays auto-swing operating status and setting position of air discharge angle.

CONTROLLERS control configurations and can (Not available for ceiling mounted built-in type and duct connection type )
Preset temperature / operation mode display Displays preset room temperature and operating status (fan, dry, cool).

Necessary optional accessory control multiple indoor units. Programming time display Operation start and stop time can be set for individual timers up to 72 hours. The liquid crystal display also shows
when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.
Remote controller options are shown on the page introducing each indoor unit model. Self-diagnosis function Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.

Wired LCD remote controller S im ple s y s t e m pr o v id e s a d iv e r s e a s s o r t m e n t o f c o n t r o l m o d e s .


W ir e d r e m o t e c o n t r o lle r h a s bu ilt -in Control pattern Wired remote controller Wireless remote controller
Easier to read because LCD screen is larger. t e m pe r a t u r e -s e n s o r (Applies to wired remote controllers)
Enables temperature sensing closer to target
For easier operation, louver switches, which are frequently
used, have been made larger. area for improved comfort. (When using remote Control by 1
(Basic system)
Oil-resistant plastic casing. control from another room, temperature-sensor remote controller
Only 17 mm thick. Can be installed either recessed or Non-polar, double-c ore S ignal rec eiver unit ins talled
exposed.
in indoor unit's air inlet must be selected.) (max. wiring length 500 m) on indoor unit
Note: The indoor unit’s temperature-sensor is specified at the time of
Indoor units applicable for the remote controller shipment. Temperature sensing with the wired remote controller is not
available with the ceiling mounted cassette corner, ceiling-mounted For control from 2 C ontrol by 1 wireles s remote
CEILING MOUNTED CASSETTE TYPE c ontroller and 1 wired remote
CEILING SUSPENDED TYPE
built-in, and duct connection type. Control by 2 locations such as in c ontroller (S ee note 1)
CEILING SUSPENDED CASSETTE TYPE remote controllers room and control room, S ignal rec eiver unit ins talled
CEILING MOUNTED CASSETTE CORNER TYPE C onnec ts 2 wired
exits, etc. on indoor unit
WALL MOUNTED TYPE BRC1C61 N o n -po la r , do u ble -c o r e c o n n e c t io n remote c ontrollers
CEILING MOUNTED BUILT-IN TYPE*1
DUCT CONNECTION LOW STATIC PRESSURE TYPE *2 s pe c ific a t io n s s im plify w ir in g
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
DUCT CONNECTION HIGH STATIC PRESSURE TYPE *2 Non-polar, double-core remote controller For simultaneous
*1. When the auto-swing function is not available, the message, wire prevents wiring mistakes. signal Group control control of up to 16
BRC1C61 THIS FUNCTION IS NOT AVAILABLE is displayed when indoor units.
the wind direction adjustment button is pressed. receiver unit (or decoration panel) of Automatic addres s s etting func tion Automatic addres s s etting func tion
S ignal rec eiver unit ins talled
*2. Applicable to only heat pump type. wireless type is also easy to connect. on 1 indoor unit

Operation and surveillance is


F a c ilit a t e s m a in t e n a n c e a n d r e pa ir
Wired LCD remote controller with weekly schedule timer Control by
carried out using the contact (C ommand from outs ide) (C ommand from outs ide)
All initial settings can be set from the remote signal from the operation
external command control box in the building
Remote control is equipped with weekly timer function. controller. After interior construction is surveillance (security) room. Optional wiring adaptor for Optional wiring adaptor for
complete, ceiling mounted units can be elec tric al appendic es is nec es s ary elec tric al appendic es is nec es s ary
24-hour clock function (1-hour backup for power failures)
Programming function for each day of week. remotely set without having to use stepladder
C entral remote c ontroller (option) C entral remote c ontroller (option)
Scheduling possible of start/stop and temperature limit (5 access for manual setting.
settings/day) Setting contents: High ceiling use, air direction, filter type,
Programming can be enabled or disabled. Centralised control of
address for centralised control (group control address is Centralised remote up to 64 indoor groups
Copy function for programmed schedules.
set automatically). control from remote location
Indoor units applicable for the remote controller
Remote controller is equipped with model name up to 1 kilometer away.
CEILING MOUNTED CASSETTE TYPE
CEILING SUSPENDED TYPE and failure display functions. This facilitates Optional S kyAir s eries interfac e Optional S kyAir s eries interfac e
adaptor required. *1
CEILING SUSPENDED CASSETTE TYPE service in the unlikely event of a malfunction. adaptor required. *1
CEILING MOUNTED CASSETTE CORNER TYPE
WALL MOUNTED TYPE BRC1D61
CEILING MOUNTED BUILT-IN TYPE*1 S k y A ir s h a r e s c o m m o n c o n t r o l w it h HR V HR V
DUCT CONNECTION LOW STATIC PRESSURE TYPE *2 H R V (h e a t r e c la im v e n t ila t io n ) a n d Link by remote
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
DUCT CONNECTION HIGH STATIC PRESSURE TYPE *2 t h e o t h e r D a ik in a ir -c o n dit io n in g controller group control.
C an be operated s imultaneous ly C an be operated s imultaneous ly
BRC1D61 *1. When the auto-swing function is not available, the message, u n it s , t h u s s im plify in g in t e r lo c k in g or independently by remote c ontroller
(s et by ventilation mode)
by remote c ontroller
(s et by ventilation mode)
THIS FUNCTION IS NOT AVAILABLE is displayed when
o pe r a t io n s . Interlock control
the wind direction adjustment button is pressed.
*2. Applicable to only heat pump type. with HRV C entral remote c ontroller (option) C entral remote c ontroller (option)

•Standard remote controller (BRC1C61) is not required. Easily adaptable to large-scale, high-
•If the BRC1D61 is connected to the centralised remote controller, function, centralised remote control systems.
the schedule function is not available.
Installing and connecting control wiring between Zone link control by HR V HR V

SkyAir and other Daikin air-conditioning centralised control.


Wireless LCD remote controller equipment is easy. HR V for indoor units within a zone are operated by interlocking
C an also be operated independently by remote controller.
HR V for indoor units within a zone are operated
by interloc king
Optional interface adaptor for S kyAir series
Optional adaptor for external commands or Optional interfac e adaptor for S kyAir s eries
signal receiver mounted type The wireless remote controller is supplied in a set is necessary *1 is nec es s ary *1
with a signal receiver. remote control of external equipment has Note: When a wireless remote c ontroller is used, remote c ontrol by two remote c ontrollers is not possible.
Shape of signal receiver unit differs according to been standardised to one type. *1. DIII-net adaptor function is standard equipment for the FAY71L.
the indoor unit.

Note: The signal rec eiver unit shown in the Easily adaptable to large-scale, high-function, centralised remote control system.
photograph is for mounting inside the
dec oration panel of the c eiling mounted C e ntr a l r e m o te c o ntr o lle r U n ifie d o n /o ff c o n t r o lle r S c h e d u le t im e r
Indoor cunits
assette type.
applicable for the remote controller DCS302CA61 (Option) DCS301BA61 (Option) DST301BA61 (Option) DCS601C51 (Option)
Signal receiver unit Signal receiver unit is contained inside decoration panel or indoor unit
(For ceiling mounted Heat pump Cooling only
cassette type)
CEILING MOUNTED
CASSETTE TYPE BRC7C612W BRC7C613W

CEILING SUSPENDED TYPE BRC7E63W BRC7EA66


Centralised control, with setting as Centralised control of on/off by Unified control of weekly schedule With its high functionality, the full
CEILING SUSPENDED
CASSETTE TYPE BRC7C528W BRC7C529W simple as it is with a standard group or all at once for up to 256 for up to 1,024 indoor units. color “all-in-one” graphic controller
Wireless remote controller FAY71L BRC7EA618 BRC7E619 remote controller, of up to 64 groups indoor units. Schedule timer sets on/off time in 1 minute units facilitates management of Skyair
WALL MOUNTED TYPE (1,024 indoor units) is possible. to be executed twice a day for a week at a time. System in a variety of ways.
FAY100FA BRC7C610W BRC7C611W
DUCT CONNECTION *Please refer to the page 59 for the details.
BRC4C62
LOW STATIC PRESSURE TYPE Interface adaptor Enables centralised control via connection to Central control adaptor kit *2
DUCT CONNECTION for SkyAir series a high-speed, DIII-NET communication
BRC4C62 BRC4C64
MIDDLE STATIC PRESSURE TYPE system, adopted for the Daikin VRV system. DTA107A55 (Option) (for FD series)
DUCT CONNECTION DTA102A52 (Option) Necessary for interface adaptor for SkyAir series with the
BRC4C62
HIGH STATIC PRESSURE TYPE central remote control units shown at above. *2.The central control adaptor kit for FDB series
Note : DIII-net adaptor function is standard equipment for the FAY71L. can be made to order.

35 36
Abundance of functions that provide comfortable W ork a nd S e rvic ing
air-conditioning in stores and offices. D r a in pu m p m e c h a n is m L o w g a s pr e s s u r e d e t e c t io n
Note: Some features only available on selected models. See model pages for full list of features applicable to each unit. Steeper gradient realises more Insufficient gas charging is normally hard to detect.
efficient condensate drainage. During post-installation trials and regular inspection
C omfort High-lift is especially useful for procedures, the refrigerant level is monitored by
long lengths of drain piping. microprocessor to maintain proper gas
A u t o -s w in g H ig h fa n s pe e d m o d e pressure.Reliability is assured and maintenance and
P r e c h a r g e d fo r u p t o 3 0 m e t r e s
Delivers comfortable air-conditioning to all areas, You can increase fan speed approximately 10% inspection can be carried out more quickly.
near to and far from the air-conditioner. higher than the "high" setting. If refrigerant piping length does not exceed 30 m,
Applicable for wall mounted type
there is no need for on-site gas charging. E m e r g e n c y o pe r a t io n
(Applies to R(Y)71LU–140LU)
H ig h -c e ilin g a pplic a t io n If there is a malfunction elsewhere in the system, the fan
L o n g -life filt e r or compressor can still be operated.
Air discharge direction angle can be set (fixed setting) Delivers air-conditioning comfort all the way down to
the floor in air-conditioning zones with high ceilings. Maintenance is not required for one year (two years
S w in g pa t t e r n s e le c t io n when a ceiling mounted cassette type is used). S e lf d ia g n o s is fu n c t io n
(draft prevention, standard, ceiling soiling prevention)
C e ilin g s o ilin g pr e v e n t io n fu n c t io n The operating parameters of indoor and outdoor units,
You can freely set 3 air discharge positions by and sensor data at critical locations throughout the
remote controller. Daikin's innovative air discharge mechanism keeps system, are constantly monitored using a microcomputer.
Applicable for ceiling mounted cassette type and ceiling mounted airflow away from the ceiling. Ceiling cleaning is To facilitate quick response in the event of a
cassette corner type. less frequently required.
Note:When units are installed on high ceilings, depending on the model, various restrictions malfunction, a message appears on the LCD of the
(1) Air direction in concerning maximum height, air discharge direction, and choice of options may apply. remote controller and an LED on the unit illuminates.
standard position F ilt e r s ig n
T w o s e le c t a ble t e m pe r a t u r e -s e n s o r s
(2) Air direction in draft The filter sign warns you when it is time to clean the filter.
Temperature-sensors are included in the indoor unit and op- *When using a wired remote controller the sign is displayed in the LCD. When using a
prevention position
tional wired remote controller. wireless remote controller the filter sign lamp illuminates on the signal receiver unit.

(3) Air direction in ceiling Temperature sensing closer to


soiling prevention position target area is possible to further
Use the temperature-sensor in the C ontrol features
indoor unit when controlling air
D r a ft pr e v e n t io n fu n c t io n (heating) conditioning from another room.
Note: Wireless remote controllers have no A u t o -r e s t a r t C o n t r o l by 1 r e m o t e c o n t r o lle r
To prevent cold air drafts, automatically adjusts airflow temperature-sensor.
If there is a power outage while the equipment is op- You can turn up to 16 indoor units on/off with a
to horizontal vector when heating initially starts or H ot s ta rt (after defrost)
single remote controller. (When using connected
erating, operations will restart in the same mode as
when the thermostat turns off. Uncomfortable cold air draft is not discharged when indoor units, the settings must all be the same and
before the power cut when electricity is restored.
heating operation starts or when switching to heat on/off will be simultaneous.)
after defrosting. A u t o c o o l/h e a t c h a n g e -o v e r (Heat pump only)
(Horizontal air dis c harge) E x te rna l c om m a nd c ontrol
S w it c h a ble fa n s pe e d Y e a r -r o u n d c o o lin g a pplic a ble Detects difference in preset temperature and actual Operation and surveillance is carried out using the
Efficient cooling even in winter when indoor temperatures room temperature and automatically switches to contact signal from the operation control box in the
High setting provides maximum reach while low
are higher than those outside, such as in underground pub- cooling or heating accordingly. building surveillance (security) room.
setting minimises drafts.
lic spaces or offices with many computers.
P rogra m m e " Dry" • Heat pump/RY71—140LU: possible up to -5°C C o n t r o l by 2 r e m o t e c o n t r o lle r s C e ntra l re m ote c ontrol
• Cooling only/R71—140LU: possible up to -15°C
Dehumidification is microprocessor controlled to • The year-round cooling kit is required as option. Using 2 remote controllers you can operate the Optional central remote controller enables
equipment locally or from a remote location. centralised control of up to 1024 indoor units (64
prevent uncomfortable changes in air temperature. T im e r s e le c t o r groups) from up to 1 kilometer away.
Useful for reducing uncomfortable humidity without Note: When a wireless remote controller is used, remote control by
Operation starts when the preset time of the ON two remote controllers is not possible.
uncomfortable cooling. timer elapses and stops when the preset time of the I n t e r lo c k c o n t r o l
OFF timer elapses. Enables interlocking control with external
equipment such as heat reclaim ventilation (HRV).
Mould prevention
M o u ld -r e s is t a n t t r e a t m e n t fo r filt e r M o u ld -pr o o fin g d r a in pa n
Sanitary filter has mould-resistant treatment. Mould-proofing maintains hygiene by preventing
Options
growth in highly humid conditions.
H ig h -e ffic ie n c y filt e r u n it F r e s h -a ir in t a k e k it
Two types are available: 65% and 90% colorimetry. You can provide air-conditioning with fresh air from
Others outside. Convenient for places where a ventilation
U lt r a lo n g -life filt e r fan cannot be installed.
T w in / tr iple / do u ble tw in m u lti o pe r a tio n P E fin Note: *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as
Requires no maintenance for about 4 years* (10,000 h) in stores
Simultaneously operates 2–4 indoor units To achieve increased durability by improved resistance to salt corro- required, be procured locally.
and offices. * For dust concentration of 0.15 mg/m 3
**Outside Air fan interlocked with air conditioning unit is necessary. Optional
with a single outdoor unit. sion and atmospheric pollution, coated PE fins (with special acryl pre- PCB(KRP1C63)is required for interlocking.
treatment) are used for the heat exchanger of the outdoor unit. ***It is recommended that the volume of outdoor air introduced through the kit is limited
to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities
In high corrosive areas, regular maintenance needs to be carried out. will increase the operating noise and may also influence temperature sending.

37 38
CEILING MOUNTED CASSETTE TYPE CEILING SUSPENDED CASSETTE TYPE
35 50 60 71 100 125 140 71 100 125
Indoor unit FHC35KVE FHC50KVE FHC60KVE FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE Indoor unit FUY71FJV1 FUY100FJV1 FUY125FJV1
Model Model
Name R71LUV1 R100LUV1 Name R71LUV1 R100LUV1
Outdoor unit R35GV1 R50GV1 R60GV1 R125LUY1 R140LUY1 Outdoor unit R125LUY1
R71LUY1 R100LUY1 R71LUY1 R100LUY1
Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Cooling capacity 1a/1b kW 3.54/3.5 5.34/5.3 6.44/6.4 7.8/7.7 10.6/10.5 13.0/12.8 14.5/14.2 Cooling capacity 1a/1b kW 7.8/7.7 10.6/10.5 13.0/12.8
Btu/h 12,100/11,900 18,200/18,100 22,000/21,800 26,600/26,200 36,100/35,700 44,500/43,600 49,400/48,400 Btu/h 26,600/26,200 36,100/35,700 44,500/43,600
kcal/h 3,040/3,010 4,590/4,560 5,540/5,500 6,700/6,600 9,100/9,000 11,200/11,000 12,500/12,200 kcal/h 6,700/6,600 9,100/9,000 11,200/11,000
3.07/3.07 (V1) 4.01/4.01 (V1) 3.08/3.08 (V1) 4.07/4.07 (V1)
Power consumption 1a/1b kW 1.20/1.20 2.02/2.01 2.45/2.44 3.05/3.05 (Y1) 3.96/3.96 (Y1) 4.96/4.96 5.02/5.02 Power consumption 1a/1b kW 3.06/3.06 (Y1) 4.02/4.02 (Y1) 4.97/4.97

Colour Unit ---------- Colour White


Indoor Indoor
Decoration panel White Airflow rate (H) m3/min 19 29 32
unit unit
Airflow rate (H) m3/min 14 15 19 19 28 33 35 cfm 670 1,023 1,129
cfm 494 529 670 670 988 1,164 1,235 Sound level (H/L) 2 dB(A) 40/35 43/38 44/39
Sound level (H/L) 2 dB(A) 33/29 33/29 35/30 35/30 39/34 42/36 44/37 Dimensions (HX WX D) mm 165X 895X 895 230X 895X 895 230X 895X 895
Dimensions Unit mm 230X 840X 840 230X 840X 840 230X 840X 840 230X 840X 840 288X 840X 840 288X 840X 840 288X 840X 840 Machine weight kg 25 31 31
(HX WX D) Decoration panel mm 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 Certified operation range °CWB 14 to 25
Unit kg 24 24 24 24 28 28 28 Colour Ivory white
Machine weight Outdoor
Decoration panel kg 5 5 5 5 5 5 5
unit Compressor Type Hermetically sealed scroll type
Certified operation range °CWB 14 to 23 14 to 25 Motor output kW 2.24 3.00 3.75
Colour Ivory white Refrigerant charge (R-22) kg 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m)
Outdoor
Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type Sound level 2 dB(A) 48 49 49
unit
Motor output kW 1.1 1.7 2.2 2.24 3.00 3.75 4.50 Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320
1.10 1.20 1.50 2.8 3.7 3.7 4.1 Machine weight kg 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98
Refrigerant charge (R-22) kg (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) Certified operation range °CDB 21 to 46, -15 to 46 3 (Option installed)
Sound level 2 dB(A) 48 49 54 48 49 49 54 Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5
Dimensions (HX WX D) mm 540X 750X 270 540X 750X 270 685X 800X 300 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 connections Gas (Flare) mm o/ 15.9 o/ 19.1 o/ 19.1
Machine weight kg 37 42 61 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 109 Drain Indoor unit mm I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26
Certified operation range °CDB 19.4 to 46 19.4 to 54 19.4 to 46 21 to 46, -15 to 46 3 (Option installed) Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)
Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 Max. interunit piping length m 50 (equivalent length 70 m)
connections Gas (Flare) mm o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 Max. installation level difference m 30
Drain Indoor unit mm I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 Heat insulation Both liquid and gas piping
Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)
Max. interunit piping length m 25 30 50 (equivalent length 70 m)
Max. installation level difference m 15 30
Heat insulation Both liquid and gas piping CEILING MOUNTED CASSETTE CORNER TYPE
35 45 60 71
Indoor unit FHK35FV1 FHK45FV1 FHK60FV1 FHYK71FJV1
Model
R71LUV1
CEILING SUSPENDED TYPE Name Outdoor unit R35GV1 R50GV1 R60GV1
R71LUY1
35 50 60 71 100 125 Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Indoor unit FH35BVE FH50BVE FH60BVE
FHY71BVE FHY100BVE FHY125BVE Cooling capacity 1a/1b kW 3.54/3.4 5.19/5.1 6.6/6.5 7.8/7.7
Model
Name R71LUV1 R100LUV1 Btu/h 12,100/11,600 17,700/17,500 22,760/22,200 26,600/26,200
Outdoor unit R35GV1 R50GV1 R60GV1 R125LUY1
R71LUY1 R100LUY1 kcal/h 3,040/2,930 4,460/4,400 5,690/5,600 6,700/6,600
Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz 3.07/3.07 (V1)
Power consumption 1a/1b kW 1.41/1.40 2.25/2.24 2.76/2.74 3.05/3.05 (Y1)
Cooling capacity 1a/1b kW 3.54/3.4 5.19/5.1 6.6/6.5 7.8/7.7 10.6/10.5 13.0/12.8
Btu/h 12,100/11,600 17,700/17,500 22,760/22,200 26,600/26,200 36,100/35,700 44,500/43,600 Colour Unit ----------
Indoor
kcal/h 3,040/2,930 4,460/4,400 5,690/5,600 6,700/6,600 9,100/9,000 11,200/11,000 Decoration panel White
unit
3.10/3.10 (V1) 3.90/3.90 (V1) Airflow rate (H) m3/min 12 12 17 17
Power consumption 1a/1b kW 1.51/1.50 2.16/2.15 2.80/2.78 4.92/4.92
3.08/3.08 (Y1) 3.85/3.85 (Y1) cfm 423 423 600 600
Colour White Sound level (H/L) 2 dB(A) 39/33 39/34 41/36 41/36
Indoor
Airflow rate (H) m3/min 13 13 16 17 24 30 Dimensions Unit mm 215X 1,110X 710 215X 1,110X 710 215X 1,310X 710 215X 1,310X 710
unit
cfm 458 458 564 600 847 1,059 (HX WX D) Decoration panel mm 70X 1,240X 800 70X 1,240X 800 70X 1,440X 800 70X 1,440X 800
Sound level (H/L) 2 dB(A) 37/32 38/33 38/33 39/35 42/37 44/39 Unit kg 30 31 33 33
Machine weight
Dimensions (HX WX D) mm 195X 960X 680 195X 960X 680 195X 1,160X 680 195X 1,160X 680 195X 1,400X 680 195X 1,590X 680 Decoration panel kg 8.5 8.5 9.5 9.5
Machine weight kg 23 24 26 27 32 35 Certified operation range °CWB 14 to 23 14 to 25
Certified operation range °CWB 14 to 23 14 to 25 Colour Ivory white
Outdoor
Colour Ivory white
unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type
Outdoor
unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type Motor output kW 1.1 1.7 2.2 2.24
Motor output kW 1.1 1.7 2.2 2.24 3.00 3.75 Refrigerant charge (R-22) kg 1.10 (Charged for 10 m) 1.20 (Charged for 10 m) 1.50 (Charged for 5 m) 2.8 (Charged for 30 m)
1.10 1.20 1.50 2.8 3.7 3.7 Sound level 2 dB(A) 48 49 54 48
Refrigerant charge (R-22) kg (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) Dimensions (HX WX D) mm 540X 750X 270 540X 750X 270 685X 800X 300 770X 900X 320
Sound level 2 dB(A) 48 49 54 48 49 49 Machine weight kg 37 42 61 72 (V1), 71 (Y1)
Dimensions (HX WX D) mm 540X 750X 270 540X 750X 270 685X 800X 300 770X 900X 320 1,170X 900X 320 1,170X 900X 320 °CDB 21 to 46
Certified operation range 19.4 to 46 19.4 to 54 19.4 to 46
Machine weight kg 37 42 61 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 -15 to 46 3 (Option installed)
Certified operation range °CDB 19.4 to 46 19.4 to 54 19.4 to 46 21 to 46, -15 to 46 3 (Option installed) Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5
Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 connections Gas (Flare) mm o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9
connections Gas (Flare) mm o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 Drain Indoor unit mm I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32
Drain Indoor unit mm I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole)
Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) Max. interunit piping length m 25 30 50 (equivalent length 70 m)
Max. interunit piping length m 25 30 50 (equivalent length 70 m) Max. installation level difference m 15 30
Max. installation level difference m 15 30 Heat insulation Both liquid and gas piping
Heat insulation Both liquid and gas piping Note :
1
Note : Rated cooling capacities are based on the following conditions:
1a
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)
2
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.) Anechoic chamber conversion value, measured according to JIS parameters and criteria.
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
3
During operation these values are somewhat higher owing to ambient conditions. This value is for when year-round cooling kit (option) is installed.
3
This value is for when year-round cooling kit (option) is installed.

39 40
CEILING MOUNTED BUILT-IN TYPE FLOOR STANDING TYPE
35 45 60 71 100 125 71 100 125
Indoor unit FHB35FV1 FHB45FV1 FHB60FV1 FHYB71FV1 FHYB100FV1 FHYB125FV1 Indoor unit FVY71LAVE FVY100LAVE FVY125LAVE
Model Model
Name R71LUV1 R100LUV1 Name R71LUV1 R100LUV1
Outdoor unit R35GV1 R50GV1 R60GV1 R125LUY1 Outdoor unit R125LUY1
R71LUY1 R100LUY1 R71LUY1 R100LUY1
Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Cooling capacity 1a/1b kW 3.54/3.4 5.19/5.1 6.6/6.5 7.8/7.7 10.6/10.5 13.0/12.8 Cooling capacity 1a/1b kW 7.8/7.7 10.6/10.5 13.0/12.8
Btu/h 12,100/11,600 17,700/17,500 22,760/22,200 26,600/26,200 36,100/35,700 44,500/43,600 Btu/h 26,600/26,200 36,100/35,700 44,500/43,600
kcal/h 3,040/2,930 4,460/4,400 5,690/5,600 6,700/6,600 9,100/9,000 11,200/11,000 kcal/h 6,700/6,600 9,100/9,000 11,200/11,000
3.13/3.13 (V1) 4.00/4.00 (V1) 3.18/3.18 (V1) 4.03/4.03 (V1)
Power consumption 1a/1b kW 1.47/1.46 2.33/2.32 2.78/2.76 3.11/3.11 (Y1) 3.95/3.95 (Y1) 4.74/4.74 Power consumption 1a/1b kW 3.16/3.16 (Y1) 3.98/3.98 (Y1) 5.06/5.06

Colour Unit ---------- Colour White


Indoor Indoor
Decoration panel White Airflow rate (H) m3/min 18 28 32
unit unit
Airflow rate (H) m3/min 11.5 14 17 19 27 35 cfm 635 988 1,129
cfm 405 494 600 670 953 1,235 Sound level (H/L) 2 dB(A) 41/35 46/40 49/43
Sound level (H/L) 2 dB(A) 38/32 39/34 41/35 41/35 41/35 44/38 Dimensions (HX WX D) mm 1,850X 600X 270 1,850X 600X 350 1,850X 600X 350
Dimensions Unit mm 300X 700X 800 300X 700X 800 300X 1,000X 800 300X 1,000X 800 300X 1,400X 800 300X 1,400X 800 Machine weight kg 39 46 47
(HX WX D) Decoration panel mm 55X 880X 500 55X 880X 500 55X 1,100X 500 55X 1,100X 500 55X 1,500X 500 55X 1,500X 500 Certified operation range °CWB 14 to 25
Unit kg 30 31 41 41 51 52 Colour Ivory white
Machine weight Outdoor
Decoration panel kg 3.5 3.5 4.5 4.5 6.5 6.5
unit Compressor Type Hermetically sealed scroll type
Certified operation range °CWB 14 to 23 14 to 25 Motor output kW 2.24 3.00 3.75
Colour Ivory white Refrigerant charge (R-22) kg 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m)
Outdoor
unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type Sound level 2 dB(A) 48 49 49
Motor output kW 1.1 1.7 2.2 2.24 3.00 3.75 Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320
1.10 1.20 1.50 2.8 3.7 3.7 Machine weight kg 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98
Refrigerant charge (R-22) kg
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) Certified operation range °CDB 21 to 46, -15 to 46 3 (Option installed)
Sound level 2 dB(A) 48 49 54 48 49 49 Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5
Dimensions (HX WX D) mm 540X 750X 270 540X 750X 270 685X 800X 300 770X 900X 320 1,170X 900X 320 1,170X 900X 320 connections Gas (Flare) mm o/ 15.9 o/ 19.1 o/ 19.1
Machine weight kg 37 42 61 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 Drain Indoor unit mm I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26
Certified operation range °CDB 19.4 to 46 19.4 to 54 19.4 to 46 21 to 46, -15 to 46 3 (Option installed) Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)
Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 Max. interunit piping length m 50 (equivalent length 70 m)
connections Gas (Flare) mm o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 Max. installation level difference m 30
Drain Indoor unit mm I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 Heat insulation Both liquid and gas piping
Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)
Max. interunit piping length m 25 30 50 (equivalent length 70 m)
Max. installation level difference m 15 30
Heat insulation Both liquid and gas piping DUCT CONNECTION LOW STATIC PRESSURE TYPE
25 35 50 60 71
Indoor unit FDBG25AVE FDBG35AVE FDBG50AVE FDBG60AVE FDBG71AVE
Model
R71FUV1
WALL MOUNTED TYPE Name Outdoor unit R25JV1 R35JV1 R50GV1 R60GV1
R71FUY1
71 100 Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Indoor unit FAY71LVE FAY100FAVE Cooling capacity 1a/1b, 4 kW 2.64/2.60 3.54/3.50 5.34/5.30 7.03/6.97 7.80/7.70
Model
Name R71LUV1 R100LUV1 Btu/h 9,000/8,900 12,100/11,900 18,200/18,100 24,000/23,800 26,600/26,200
Outdoor unit
R71LUY1 R100LUY1 kcal/h 2,270/2,250 3,040/3,010 4,590/4,560 6,050/6,000 6,700/6,600
Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz Power consumption 1a/1b kW 0.88/0.87 1.25/1.24 2.06/2.05 2.76/2.75 2.82/2.80
Cooling capacity 1a/1b kW 7.8/7.7 10.6/10.5 Colour ----------
Indoor
Btu/h 26,600/26,200 36,100/35,700 Airflow rate (H) m3/min 13 13 13 18 18
unit
kcal/h 6,700/6,600 9,100/9,000 cfm 458 458 458 635 635
2.98/ 2.98(V1) 3.90/3.90 (V1) Fan Driving system Direct drive (2 speed)
Power consumption 1a/1b kW 3.85/3.85 (Y1)
2.96/2.96(Y1) Sound level (H/L) 2 dB(A) 41/38 41/38 41/38 42/39 42/39
Colour White Dimensions (HX WX D) mm 260X 900X 580 260X 900X 580 260X 900X 580 260X 1,300X 580 260X 1,300X 580
Indoor
Airflow rate (H) m3/min 19 23 Machine weight kg 22 22 23 31 31
unit
cfm 670 811 Certified operation range °CWB 14 to 23 14 to 25
Sound level (H/L) 2 dB(A) 43/37 45/41 Colour Ivory white
Outdoor
Dimensions (HX WX D) mm 290X 1,050X 230 360X 1,570X 200
unit Compressor Type Hermetically sealed rotary type Hermetically sealed type
Machine weight kg 13 26 Motor output kW 0.7 1.1 1.7 2.2 2.2
Certified operation range °CWB 14 to 25 0.8 1.0 1.20 1.50 2.10
Refrigerant charge (R-22) kg
Colour Ivory white (Charged for 10 m) (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 5 m)
Outdoor
unit Compressor Type Hermetically sealed scroll type Sound level 2 dB(A) 46 48 49 54 52
Motor output kW 2.24 3.00 Dimensions (HX WX D) mm 560X 695X 265 560X 695X 265 540X 750X 270 685X 800X 300 816X 880X 370
Refrigerant charge (R-22) kg 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) Machine weight kg 27 33 42 61 87 (V1), 84 (Y1)
Sound level 2 dB(A) 48 49 Certified operation range °CDB 19.4 to 46 19.4 to 54 19.4 to 46 21 to 52
Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5
Machine weight kg 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) connections Gas (Flare) mm o/ 9.5 o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9
Certified operation range °CDB 21 to 46, -15 to 46 3 (Option installed) Drain Indoor unit mm 3/4B 3/4B 3/4B 3/4B 3/4B
Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole)
connections Gas (Flare) mm o/ 15.9 o/ 19.1 Max. interunit piping length m 25 30 50 (equivalent length 70 m)
Drain Indoor unit mm I.D o/ 13X O.D o/ 18 I.D o/ 20X O.D o/ 26 Max. installation level difference m 15 30
Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) Heat insulation Both liquid and gas piping
Max. interunit piping length m 50 (equivalent length 70 m) Note :
Max. installation level difference m 30 1
Rated cooling capacities are based on the following conditions:
Heat insulation Both liquid and gas piping (FVY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)
Note : (FDBG) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1 1b
Rated cooling capacities are based on the following conditions: Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
(FHB) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.) During operation these values are somewhat higher owing to ambient conditions.
(FAY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 3
This value is for when year-round cooling kit (option) is installed.
1b 4
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R100LU is 7.5 m.) Capacities are gross, with no deduction made for evaporator fan motor heat.
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
This value is for when year-round cooling kit (option) is installed.

41 42
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE DUCT CONNECTION HIGH STATIC PRESSURE TYPE
71 100 125 140 180 71 100 125 140
Indoor unit FDMG71AV1 FDMG100AV1 FDMG125AV1 FDMG140AV1 FDMG180AV1 Model Indoor unit FD03KY1 FD04KY1 FD05KY1 FD06KY1
Model
RG71AV1 R100FUV1 Name Outdoor unit R71FUY1 R100FUY1 R125FUY1 RU06KY1
Name Outdoor unit R125FUY1 RG140AY1 RG180AY1
RG71AY1 R100FUY1 Power supply Y1: 3 phase, 380–415 V, 50 Hz
Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz Cooling capacity 1a/1b kW 8.1/ 7.9 11.0/10.8 14.0/13.8 17.4/17.2
Cooling capacity 1a/1b kW 8.8/8.7 10.6/10.5 13.1/12.9 14.5/14.2 17.2/16.8 Btu/h 27,800/27,000 37,700/36,900 47,600/46,800 59,500/58,800
Btu/h 30,000/29,600 36,100/35,700 44,500/43,600 49,400/48,400 58,700/57,500 kcal/h 7,000/6,800 9,500/9,300 12,000/11,800 15,000/14,800
kcal/h 7,600/7,500 9,100/9,000 11,200/11,000 12,500/12,200 14,700/14,400 Power consumption 1a/1b kW 2.50/2.48 3.52/3.48 4.19/4.15 5.7/5.7
Power consumption 1a/1b kW 3.15/3.13 4.08/4.04 4.89/4.85 5.25/5.25 6.45/6.45 Colour ----------
Indoor
Colour ---------- Airflow rate (H) m3/min 26 30 46 52
Indoor unit
Fan Airflow rate (H) m3/min 23 34 37 42 42 cfm 917 1,059 1,623 1,835
unit
cfm 811 1,200 1,306 1,412 1,482 Fan External static pressure Pa(mmH2O) 69 (7) 88 (9)
Sound level (H) 2 dB(A) 42 44 45 46 47 Driving system Belt drive
Dimensions (HX WX D) mm 305X 1,350X 680 305X 1,550X 680 305X 1,550X 680 305X 1,550X 680 305X 1,900X 680 Sound level (H) 2 dB(A) 46 49 51
Machine weight kg 43 51 52 52 58 Dimensions (HX WX D) mm 450X 650X 850 450X 900X 850 450X 1,130X 850
Certified operation range °CWB 14 to 25 Machine weight kg 51 59 72 79
Colour Ivory white Certified operation range °CWB 14 to 25
Outdoor
unit Compressor Type Hermetically sealed type Hermetically sealed scroll type Colour Ivory white
Outdoor
Motor output kW 2.20 3.00 3.75 4.50 4.50
unit Compressor Type Hermetically sealed type Hermetically sealed scroll type
Refrigerant charge (R-22) kg 2.4 (Charged for 5 m) 2.4 (Charged for 5 m) 2.8 (Charged for 5 m) 2.9 (Charged for 5 m) 2.8 (Charged for 5 m) Motor output kW 3.0 3.8 4.5 4.5
Sound level 2 dB(A) 52 56 57 55 56 2.1 2.4 2.8 3.0
Refrigerant charge (R-22) kg (Charged for 5 m) (Charged for 5 m) (Charged for 5 m) (Charged for 5 m)
Dimensions (HX WX D) mm 816X 880X 370 1,215X 880X 370 1,215X 880X 370 1,345X 880X 370 1,345X 880X 370
Machine weight kg 87 (V1), 84 (Y1) 117 (V1), 109 (Y1) 110 113 114 Sound level 2 dB(A) 52 56 57 59
Certified operation range °CDB 21 to 52 21 to 50 Dimensions (HX WX D) mm 816X 880X 370 1,215X 880X 370 1,345X 880X 320
Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 Machine weight kg 84 109 110 112
connections Gas (Flare) mm o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 o/ 19.1 Certified operation range °CDB 21 to 52
Drain Indoor unit mm 3/4B 3/4B 3/4B 3/4B 3/4B Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5
Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) connections Gas (Flare) mm o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1
Max. interunit piping length m 50 (equivalent length 70 m) Drain Indoor unit mm 3/4B
Max. installation level difference m 30 Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) ----------
Heat insulation Both liquid and gas piping Max. interunit piping length m 50 (equivalent length 70 m)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
71 100 125 140
Indoor unit FDYM03FAV1 FDYM04FAV1 FDYM05FAV1 FDYM06FAV1
Model
Name R71LUV1 R100LUV1 200 250 400 500
Outdoor unit R125LUY1 R140LUY1
R71LUY1 R100LUY1 Model Indoor unit FD08KY1 FD10KY1 FD15KY1 FD20KY1
Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz Name Outdoor unit RU08KUY1 RU10KUY1 RU08KUY1X 2 RU10KUY1X 2
Cooling capacity 1a/1b kW 7.8/7.7 10.6/10.5 13.0/12.8 14.5/14.2 Power supply Y1: 3 phase, 380–415 V, 50 Hz
Btu/h 26,600/26,200 36,100/35,700 44,500/43,600 49,400/48,400 Cooling capacity 1a/1b kW 24.3/24.0 29.7/29.2 48.6/47.9 59.3/58.4
kcal/h 6,700/6,600 9,100/9,000 11,200/11,000 12,500/12,200 Btu/h 83,000/81,800 101,200/99,600 166,000/163,500 202,400/199,400
3.25/3.25 (V1) 4.08/4.08 (V1) kcal/h 20,900/20,600 25,500/25,100 41,800/41,200 51,000/50,200
Power consumption 1a/1b kW 3.23/3.23 (Y1) 4.03/4.03 (Y1) 5.06/5.06 5.18/5.18
Power consumption 1a/1b kW 7.5/7.4 9.9/9.8 15.0/14.8 19.8/19.6
Colour ---------- Colour ----------
Indoor Indoor
Fan Airflow rate (H) m3/min 20 26 35 37 Airflow rate (H) m3/min 68 83 136 166
unit unit
cfm 706 917 1,235 1,306 cfm 2,400 2,929 4,800 5,859
External static pressure Pa(mmH2O) 98(10) 98(10) 98(10) 98(10) Fan External static pressure Pa(mmH2O) 98 (10) 147 (15)
Sound level (H) 2 dB(A) 39 39 44 46 Driving system Belt drive
Dimensions (HX WX D) mm 295X 1,100X 680 295X 1,500X 680 295X 1,500X 680 295X 1,500X 680 Sound level (H) 2 dB(A) 51 53 58 60
Machine weight kg 42 56 57 57 Dimensions (HX WX D) mm 500X 1,130X 850 500X 1,330X 850 625X 1,620X 850 625X 1,980X 850
Certified operation range °CWB 14 to 25 Machine weight kg 93 104 161 187
Colour Ivory white Certified operation range °CWB 14 to 25
Outdoor
unit Compressor Type Hermetically sealed scroll type Colour Ivory white
Outdoor
Motor output kW 2.24 3.00 3.75 4.50
unit Compressor Type Hermetically sealed scroll type
Refrigerant charge (R-22) kg 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m) 4.1 (Charged for 30 m) Motor output kW 7.5 9.0 7.5 X 2 9.0X 2
Sound level 2 dB(A) 48 49 49 54 5.0 6.1 5.0 6.1
Refrigerant charge (R-22) kg (Charged for 5 m) (Charged for 5 m) (Charged for 5 m)X 2 (Charged for 5 m)X 2
Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320
Machine weight kg 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 109 Sound level 2 dB(A) 60 61 60 3 61 3
Certified operation range °CDB 21 to 46, -15 to 46 3 (Option installed) Dimensions (HX WX D) mm 1,220X 1,280X 690 1,440X 1,280X 690 (1,220X 1,280X 690) X 2 (1,440X 1,280X 690) X 2
Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 Machine weight kg 185 200 185X 2 200X 2
connections Gas (Flare) mm o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 Certified operation range °CDB 21 to 52
Drain Indoor unit mm I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 Piping Liquid (Flare) mm o/ 12.7 o/ 15.9 o/ 12.7 X 2 o/ 15.9 X 2
Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) connections Gas (Brazing) mm o/ 25.4 o/ 31.8 o/ 25.4 X 2 o/ 31.8 X 2
Max. interunit piping length m 50 (equivalent length 70 m) Drain Indoor unit mm 3/4B 1B
Max. installation level difference m 30 Outdoor unit mm ----------
Heat insulation Both liquid and gas piping Max. interunit piping length m 50 (equivalent length 70 m)
Note : Max. installation level difference m 30
1
Rated cooling capacities are based on the following conditions: Heat insulation Both liquid and gas piping
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.) Note :
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria. Models RU08K(U)Y1 and RU10K(U)Y1 are recommended for commercial facilities.
1
During operation these values are somewhat higher owing to ambient conditions. Rated cooling capacities are based on the following conditions:
1a
3
This value is for when year-round cooling kit (option) is installed. Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
Specification for outdoor unit is for a single unit only.

43 44
Simultaneous operation system TWIN & TRIPLE & DOUBLE TWIN MULTI
DUCT CONNECTION HIGH STATIC PRESSURE TYPE CEILING MOUNTED CASSETTE TYPE
200 250 400 500
71 100 125 140 200 250
Model Indoor unit FD08KY1 FD10KY1 FD15KY1 FD20KY1
Indoor unit FHYC35KVEX 2 FHYC50KVEX 2 FHYC60KVEX 2 FHYC71KVEX 2 FHYC100KVEX 2 FHYC125KVEX 2
Name Outdoor unit RU08KY1 RU10KY1 RU08KY1X 2 RU10KY1X 2 Model
Name R71LUV1 R100LUV1
Power supply Y1: 3 phase, 380–415 V, 50 Hz Outdoor unit R125LUY1 R140LUY1 R200KUY1 R250KUY1
R71LUY1 R100LUY1
Cooling capacity 1a/1b kW 24.3/24.0 29.7/29.2 48.6/47.9 59.3/58.4
Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Btu/h 83,000/81,800 101,200/99,600 166,000/163,500 202,400/199,400
Cooling capacity 1a/1b kW 7.8/7.7 10.6/10.5 13.0/12.8 14.5/14.2 22.5/22.2 27.1/26.6
kcal/h 20,900/20,600 25,500/25,100 41,800/41,200 51,000/50,200
Btu/h 26,600/26,200 36,100/35,700 44,500/43,600 49,400/48,400 76,800/75,800 92,500/90,800
Power consumption 1a/1b kW 7.5/7.4 9.9/9.8 15.0/14.8 19.8/19.6
kcal/h 6,700/6,600 9,100/9,000 11,200/11,000 12,500/12,200 19,400/19,100 23,300/22,900
Colour ----------
Indoor 3.17/3.17 (V1) 4.06/4.06 (V1)
Airflow rate (H) m3/min 68 83 136 166 Power consumption 1a/1b kW 5.01/5.01 5.02/5.02 7.7/7.6 9.7/9.7
unit 3.15/3.15 (Y1) 4.01/4.01 (Y1)
cfm 2,400 2,929 4,800 5,859
Colour Unit -------------
Fan External static pressure Pa(mmH2O) 98 (10) 147 (15) Indoor
Decoration panel White
Driving system Belt drive unit 3
Airflow rate (H) m3/min 14 15 19 19 28 33
Sound level (H) 2 dB(A) 51 53 58 60
cfm 494 529 670 670 988 1,164
Dimensions (HX WX D) mm 500X 1,130X 850 500X 1,330X 850 625X 1,620X 850 625X 1,980X 850
Sound level (H/L) 2 dB(A) 33/29 33/29 35/30 35/30 39/34 42/36
Machine weight kg 93 104 161 187
Dimensions Unit mm 230X 840X 840 230X 840X 840 230X 840X 840 230X 840X 840 288X 840X 840 288X 840X 840
Certified operation range °CWB 14 to 25
(HX WX D) Decoration
Colour Ivory white panel mm 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950
Outdoor
unit Compressor Type Hermetically sealed scroll type
Unit kg 24 24 24 24 28 28
Motor output kW 7.5 9.0 7.5 X 2 9.0X 2
Machine weight Decoration
5.0 6.1 5.0 6.1 panel kg 5 5 5 5 5 5
Refrigerant charge (R-22) kg (Field charge required for 5 m) 4 (Field charge required for 5 m) 4 (Field charge required for 5 m) 4 X 2 (Field charge required for 5 m) 4 X 2
Certified operation range °CWB 14 to 25
Sound level 2 dB(A) 60 61 60 3 61 3
Colour Ivory white
Dimensions (HX WX D) mm 1,220X 1,280X 690 1,440X 1,280X 690 (1,220X 1,280X 690) X 2 (1,440X 1,280X 690) X 2 Outdoor
Compressor Type Hermetically sealed scroll type
Machine weight kg 177 190 177 X 2 190 X 2 unit
Motor output kW 2.24 3.00 3.75 4.50 5.5 9.0
Certified operation range °CDB 21 to 52
2.8 3.7 3.7 4.1 5.3 5.7
Piping Liquid (Brazing) mm o/ 12.7 o/ 15.9 o/ 12.7 X 2 o/ 15.9 X 2 Refrigerant charge (R-22) kg
(Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 5 m) (Charged for 5 m)
connections Gas (Brazing) mm o/ 25.4 o/ 31.8 o/ 25.4 X 2 o/ 31.8 X 2
Sound level 2 dB(A) 48 49 49 54 60 61
Drain Indoor unit mm 3/4B 1B
Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 1,220X 1,280X 690 1,440X 1,280X 690
Outdoor unit mm ----------
Machine weight kg 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 109 178 202
Max. interunit piping length m 50 (equivalent length 70 m)
Certified operation range °CDB 21 to 46, -15 to 46 4 (Option installed) -5 to 52
Max. installation level difference m 30
Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 12.7 o/ 15.9
Heat insulation Both liquid and gas piping
connections Gas mm o/ 15.9 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 25.4 (Flange) o/ 28.6 (Flange)
Note : Drain Indoor unit mm I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32
Models RU08K(U)Y1 and RU10K(U)Y1 are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions: Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) --------- ---------
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). Max. interunit piping length m 50 (equivalent length 70 m)
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). Max. installation level difference m 30
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions. Heat insulation Both liquid and gas piping
3
Specification for outdoor unit is for a single unit only.
4
This is the amount of refrigerant required for piping of five meters or less.
Since the unit does not contain refrigerant when shipped from the factory, it must be added at the installation site.
140 200 200 250
For details, please refer to the installation manual.
Model Indoor unit FHYC50KVEX 3 FHYC71KVEX 3 FHYC50KVEX 4 FHYC60KVEX 4
Name Outdoor unit R140LUY1 R200KUY1 R200KUY1 R250KUY1
Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Cooling capacity 1a/1b kW 14.5/14.2 22.5/22.2 22.5/22.2 27.1/26.6
Btu/h 49,400/48,400 76,800/75,800 76,800/75,800 92,500/90,800
kcal/h 12,500/12,200 19,400/19,100 19,400/19,100 23,300/22,900
Power consumption 1a/1b kW 5.02/5.02 7.7/7.6 7.7/7.6 9.7/9.7
Colour Unit -------------
Indoor
Decoration panel White
unit 3
Airflow rate (H) m3/min 15 19 15 19
cfm 529 670 529 670
Sound level (H/L) 2 dB(A) 33/29 33/29
35/30 33/29 35/30
Dimensions Unit mm 230X 840X 840 230X 840X 840 230X 840X 840 230X 840X 840
(HX WX D) Decoration
panel mm 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950

Unit kg 24 24 24 24
Machine weight Decoration
panel kg 5 5 5 5

Certified operation range °CWB 14 to 25


Colour Ivory white
Outdoor
Compressor Type Hermetically sealed scroll type
unit
Motor output kW 4.50 5.5 5.5 9.0
Refrigerant charge (R-22) kg 4.1 (Charged for 30 m) 5.3 (Charged for 5 m) 5.3 (Charged for 5 m) 5.7 (Charged for 5 m)
Sound level 2 dB(A) 54 60 60 61
Dimensions (HX WX D) mm 1,345X 900X 320 1,220X 1,280X 690 1,220X 1,280X 690 1,440X 1,280X 690
Machine weight kg 109 178 178 202
Certified operation range °CDB 21 to 46, -15 to 46 4 (Option installed) -5 to 52
Piping Liquid (Flare) mm o/ 9.5 o/ 12.7 o/ 12.7 o/ 15.9
connections Gas mm o/ 19.1 (Flare) o/ 25.4 (Flange) o/ 25.4 (Flange) o/ 28.6 (Flange)
Drain Indoor unit mm I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32
Outdoor unit mm o/ 26.0 (Hole) --------- --------- ---------
Max. interunit piping length m 50 (equivalent length 70 m)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
Note :
Models R200KU and R250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
Values shown are for a single unit only.
4
This value is for when year-round cooling kit (option) is installed.

45 46
Simultaneous operation system TWIN & TRIPLE & DOUBLE TWIN MULTI
CEILING SUSPENDED TYPE DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
71 100 125 140 200 250 200 250 200
Indoor unit FHY35BVE × 2 FHY50BVE × 2 FHY60BVE × 2 FHY71BVE × 2 FHY100BVE × 2 FHY125BVE × 2 Model Indoor unit FDYM04FAV1 × 2 FDYM05FAV1 × 2 FDYM03FAV1 × 3
Model
R71LUV1 R100LUV1 Name Outdoor unit R200KUY1 R250KUY1 R200KUY1
Name Outdoor unit R125LUY1 R140LUY1 R200KUY1 R250KUY1
R71LUY1 R100LUY1 Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz Cooling capacity 1a/1b kW 22.5/22.2 27.1/26.6 22.5/22.2
Cooling capacity 1a/1b kW 7.8/7.7 10.6/10.5 13.0/12.8 14.5/14.2 22.5/22.2 27.1/26.6 Btu/h 76,800/75,800 92,500/90,800 76,800/75,800
Btu/h 26,600/26,200 36,100/35,700 44,500/43,600 49,400/48,400 76,800/75,800 92,500/90,800 kcal/h 19,400/19,100 23,300/22,900 19,400/19,100
kcal/h 6,700/6,600 9,100/9,000 11,200/11,000 12,500/12,200 19,400/19,100 23,300/22,900 Power consumption 1a/1b kW 7.7/7.6 9.9/9.9 8.0/7.9
3.20/3.20 (V1) 3.95/3.95 (V1) Colour ----------
Power consumption 1a/1b kW 4.98/4.98 5.17/5.17 7.7/7.6 9.7/9.7 Indoor
3.18/3.18 (Y1) 3.90/3.90 (Y1) Fan Airflow rate (H) m3/min 26 35 20
unit 3
Colour White cfm 917 1,235 706
Indoor
Airflow rate (H) m3/min 13 13 16 17 24 30 External static pressure Pa(mmH2O) 98(10) 98(10) 98(10)
unit 3
cfm 458 458 564 600 847 1,059 Sound level (H) 2 dB(A) 39 44 39
Sound level (H/L) 2 dB(A) 37/32 38/33 38/33 39/35 42/37 44/39 Dimensions (HX WX D) mm 295X 1,500X 680 295X 1,500X 680 295X 1,100X 680
Dimensions (HX WX D) mm 195X 960X 680 195X 960X 680 195X 1,160X 680 195X 1,160X 680 195X 1,400X 680 195X 1,590X 680 Machine weight kg 56 57 42
Machine weight kg 23 24 26 27 32 35 Certified operation range °CWB 14 to 25
°
Certified operation range CWB 14 to 25 Colour Ivory white
Outdoor
Colour Ivory white Compressor Type Hermetically sealed scroll type
Outdoor unit
Compressor Type Hermetically sealed scroll type Motor output kW 5.5 9.0 5.5
unit
Motor output kW 2.24 3.00 3.75 4.50 5.5 9.0 Refrigerant charge (R-22) kg 5.3 (Charged for 5 m) 5.7 (Charged for 5 m) 5.3 (Charged for 5 m)
2.8 3.7 3.7 4.1 5.3 5.7 Sound level 2 dB(A) 60 61 60
Refrigerant charge (R-22) kg
(Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 5 m) (Charged for 5 m) Dimensions (HX WX D) mm 1,220X 1,280X 690 1,440X 1,280X 690 1,220X 1,280X 690
Sound level 2 dB(A) 48 49 49 54 60 61 Machine weight kg 178 202 178
Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 1,220X 1,280X 690 1,440X 1,280X 690 Certified operation range °CDB -5 to 52
Machine weight kg 72 (V1), 71 (Y1) 87 (V1), 84 (Y1) 98 109 178 202 Piping Liquid (Flare) mm o/ 12.7 o/ 15.9 o/ 12.7
Certified operation range °CDB 21 to 46, -15 to 46 4 (Option installed) -5 to 52 connections Gas (Flange) mm o/ 25.4 o/ 28.6 o/ 25.4
Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 12.7 o/ 15.9 Drain Indoor unit mm o/ 25I.D.,o/ 32O.D. o/ 25I.D.,o/ 32O.D. o/ 25I.D.,o/ 32O.D.
connections Gas mm o/ 15.9 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 25.4 (Flange) o/ 28.6 (Flange) Outdoor unit mm --------- --------- ---------
Drain Indoor unit mm I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 Max. interunit piping length m 50 (equivalent length 70 m)
Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) --------- --------- Max. installation level difference m 30
Max. interunit piping length m 50 (equivalent length 70 m) Heat insulation Both liquid and gas piping
Max. installation level difference m 30 Note :
Heat insulation Both liquid and gas piping Models R200KU and R250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
140 200 200 250 2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
Indoor unit FHY50BVE × 3 FHY71BVE × 3 FHY50BVE × 4 FHY60BVE × 4 During operation these values are somewhat higher owing to ambient conditions.
Model 3
Values shown are for a single unit only.
Name Outdoor unit R140LUY1 R200KUY1 R200KUY1 R250KUY1
Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V,50 Hz
Cooling capacity 1a/1b kW 14.5/14.2 22.5/22.2 22.5/22.2 27.1/26.6
Btu/h 49,600/48,400 76,800/75,800 76,800/75,800 92,500/90,800
kcal/h 12,500/12,200 19,400/19,100 19,400/19,100 23,300/22,900
Power consumption 1a/1b kW 5.17/5.17 7.7/7.6 7.7/7.6 9.7/9.7
Colour White
Indoor
Airflow rate (H) m3/min 13 17 13 16
unit 3
cfm 458 600 458 564
Sound level (H/L) 2 dB(A) 38/33 39/35 38/33 38/33
Dimensions (HX WX D) mm 195X 960X 680 195X 1,160X 680 195X 960X 680 195X 1,160X 680
Machine weight kg 24 27 24 26
Certified operation range °CWB 14 to 25
Colour Ivory white
Outdoor
Compressor Type Hermetically sealed scroll type
unit
Motor output kW 4.50 5.5 5.5 9.0
Refrigerant charge (R-22) kg 4.1 (Charged for 30 m) 5.3 (Charged for 5 m) 5.3 (Charged for 5 m) 5.7 (Charged for 5 m)
Sound level 2 dB(A) 54 60 60 61
Dimensions (HX WX D) mm 1,345X 900X 320 1,220X 1,280X 690 1,220X 1,280X 690 1,440X 1,280X 690
Machine weight kg 109 178 178 202
Certified operation range °CDB 21 to 46, -15 to 46 4 (Option installed) -5 to 52
Piping Liquid (Flare) mm o/ 9.5 o/ 12.7 o/ 12.7 o/ 15.9
connections Gas mm o/ 19.1 (Flare) o/ 25.4 (Flange) o/ 25.4 (Flange) o/ 28.6 (Flange)
Drain Indoor unit mm I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26
Outdoor unit mm o/ 26.0 (Hole) --------- --------- ---------
Max. interunit piping length m 50 (equivalent length 70 m)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
Note :
Models R200KU and R250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
Values shown are for a single unit only.
4
This value is for when year-round cooling kit (option) is installed.

47 48
CEILING MOUNTED CASSETTE TYPE
35 50 60 71 100 125 140 CEILING SUSPENDED CASSETTE TYPE
Indoor unit FHYC35KVE FHYC50KVE FHYC60KVE FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE 71 100 125
Model
RY71LUV1 RY100LUV1 Indoor unit FUY71FJV1 FUY100FJV1 FUY125FJV1
Name Outdoor unit RY35FV1A RY50GAV1A RY60GAV1A RY125LUY1 RY140LUY1 Model
RY71LUY1 RY100LUY1 Name RY71LUV1 RY100LUV1
Outdoor unit RY125LUY1
Power supply VE: 1 Phase 220–240/220 V, 50/60 Hz V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz RY71LUY1 RY100LUY1
Cooling capacity 1a/1b kW 3.79/3.75 5.27/5.2 6.24/6.15 7.8/7.7 10.5/10.4 13.0/12.8 14.5/14.2 Power supply V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Btu/h 12,900/12,800 18,000/17,800 21,300/21,000 26,600/26,200 35,700/35,300 44,500/43,600 49,400/48,400 Cooling capacity 1a/1b kW 7.8/7.7 10.5/10.4 13.0/12.8
kcal/h 3,260/3,230 4,530/4,470 5,370/5,290 6,700/6,600 9,000/8,900 11,200/11,000 12,500/12,200 Btu/h 26,600/26,200 35,700/35,300 44,500/43,600
Heating capacity 2 kW 4.22 5.8 7.0 7.9 11.2 14.2 16.3 kcal/h 6,700/6,600 9,000/8,900 11,200/11,000
Btu/h 14,400 19,800 23,900 27,000 38,100 48,400 56,000 Heating capacity 2 kW 7.9 11.2 14.2
kcal/h 3,630 4,990 6,020 6,800 9,600 12,200 14,000 Btu/h 27,000 38,100 48,400
Cooling 1a/1b kW 1.51/1.50 1.92/1.91 2.35/2.33 3.01 /3.01 (V1), 2.99/2.99 (Y1) 3.93 /3.93 (V1), 3.88/3.88 (Y1) 4.89/4.89 4.95/4.95 kcal/h 6,800 9,600 12,200
Power consumption
Heating 2 kW 1.37 1.68 2.26 2.84 (V1), 2.82 (Y1) 3.64 (V1), 3.60 (Y1) 4.68 4.84 Cooling 1a/1b kW 3.02/3.02 (V1), 3.00/3.00 (Y1) 3.99/3.99 (V1), 3.94/3.94 (Y1) 4.90/4.90
Power consumption
Colour Unit ---------- Heating 2 kW 2.87 (V1), 2.84 (Y1) 3.66 (V1), 3.62 (Y1) 4.61
Indoor
Decoration panel White Colour White
unit Indoor
Airflow rate (H) m3/min 14 15 19 19 28 33 35 Airflow rate (H) m3/min 19 29 32
unit
cfm 494 529 670 670 988 1,164 1,235 cfm 670 1,023 1,129
Sound level (H/L) 3 dB(A) 33/29 33/29 35/30 35/30 39/34 42/36 44/37 Sound level (H/L) 3 dB(A) 40/35 43/38 44/39
Dimensions Unit mm 230×840×840 230×840×840 230×840×840 230×840×840 288×840×840 288×840×840 288×840×840 Dimensions (HX WX D) mm 165X 895X 895 230X 895X 895 230X 895X 895
(H×W×D) Decoration panel mm 40×950×950 40×950×950 40×950×950 40×950×950 40×950×950 40×950×950 40×950×950 Machine weight kg 25 31 31
Machine weight Unit kg 24 24 24 24 28 28 28 Cooling °CWB 12 to 25
Certified
Decoration panel kg 5 5 5 5 5 5 5 operation range Heating °CDB 15 to 27
Certified Cooling °CWB 14 to 23 12 to 25 Colour Ivory white
operation range Heating Outdoor
°CDB 15 to 28 15 to 27 Compressor Type Hermetically sealed scroll type
unit
Colour Ivory white Motor output kW 2.24 3.00 3.75
Outdoor
unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type Refrigerant charge (R-22) kg 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m)
Motor output kW 1.3 1.7 2.2 2.24 3.00 3.75 4.50 Sound level (Cooling/Heating) 3 dB(A) 48/49 49/52 49/52
kg 1.12 1.55 1.75 2.8 3.7 3.7 4.1 Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320
Refrigerant charge (R-22) (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) Machine weight kg 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) 101
Sound level (Cooling/Heating) 3 dB(A) 47/48 49/51 54/54 48/49 49/52 49/52 54/56 Cooling °CDB -5 to 46
Certified
Dimensions (H×W×D) mm 540×750×270 685×800×300 685×880×350 770×900×320 1,170×900×320 1,170×900×320 1,345×900×320 operation range Heating °CWB -10 to 15
Machine weight kg 41 51 75 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) 101 112 Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5
Certified Cooling °CDB 19.4 to 46 -5 to 46 connections Gas (Flare) mm o/ 15.9 o/ 19.1 o/ 19.1
operation range Heating °CWB -10 to 15.5 -10 to 15 Drain Indoor unit mm I.D o/ 20X O.D o/ 26
Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)
connections Gas (Flare) mm o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 Max. interunit piping length m 50 (equivalent length 70 m)
Drain Indoor unit mm I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 Max. installation level difference m 30
Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) Heat insulation Both liquid and gas piping
Max. interunit piping length m 20 30 50 (equivalent length 70 m)
Max. installation level difference m 15 30
Heat insulation Both liquid and gas piping CEILING MOUNTED CASSETTE CORNER TYPE
35 45 60 71
CEILING SUSPENDED TYPE Indoor unit FHYK35FJV1 FHYK45FJV1 FHYK60FJV1 FHYK71FJV1
Model
35 50 60 71 100 125 Name RY71LUV1
Outdoor unit RY35FV1A RY50GAV1A RY60GAV1A
Indoor unit FHY35BVE FHY50BVE FHY60BVEFHY71BVE FHY100BVE FHY125BVE RY71LUY1
Model
RY71LUV1 RY100LUV1 Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Name Outdoor unit RY35FV1A RY50GAV1A RY60GAV1A RY125LUY1
RY71LUY1 RY100LUY1 Cooling capacity 1a/1b kW 3.5/3.5 5.0/4.85 6.3/6.15 7.8/7.7
Power supply VE: 1 Phase 220–240/220 V, 50/60 Hz V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz Btu/h 12,100/11,900 16,900/16,600 21,400/21,000 26,600/26,200
Cooling capacity 1a/1b kW 3.5/3.5 5.0/4.85 6.3/6.15 7.8/7.7 10.5/10.4 13.0/12.8 kcal/h 3,040/3,000 4,260/4,200 5,390/5,300 6,700/6,600
Btu/h 12,100/11,900 16,900/16,600 21,400/21,000 26,600/26,200 35,700/35,300 44,500/43,600 Heating capacity 2 kW 4.1 5.5 7.1 7.9
kcal/h 3,040/3,000 4,260/4,200 5,390/5,300 6,700/6,600 9,000/8,900 11,200/11,000 Btu/h 14,000 18,800 24,000 27,000
Heating capacity 2 kW 4.1 5.5 7.1 7.9 11.2 14.2 kcal/h 3,520 4,740 6,080 6,800
Btu/h 14,000 18,800 24,200 27,000 38,100 48,400 Cooling 1a/1b kW 1.47/1.46 1.95/1.94 2.87/2.85 3.01/3.01 (V1), 2.99/2.99 (Y1)
Power consumption
kcal/h 3,520 4,750 6,100 6,800 9,600 12,200 Heating 2 kW 1,25 1.72 2.65 2.91 (V1), 2.88 (Y1)
Cooling 1a/1b kW 1.58/1.57 2.17/2.16 3.14/3.12 3.04/3.04 (V1), 3.02/3.02 (Y1) 3.82/3.82 (V1), 3.77/3.77 (Y1) 4.85/4.85 Colour Unit ----------
Power consumption Indoor
Heating 2 kW 1.37 1.96 2.94 2.98 (V1), 2.95 (Y1) 3.69 (V1), 3.64 (Y1) 4.77 Decoration panel White
unit
Colour White Airflow rate (H) m3/min 12 12 17 17
Indoor
Airflow rate (H) m3/min 13 13 16 17 24 30 cfm 423 423 600 600
unit
cfm 458 458 564 600 847 1,059 Sound level (H/L) 3 dB(A) 39/33 39/34 41/36 41/36
Sound level (H/L) 3 dB(A) 37/32 38/33 38/33 39/35 42/37 44/39 Dimensions Unit mm 215X 1,110X 710 215X 1,110X 710 215X 1,310X 710 215X 1,310X 710
Dimensions (HX WX D) mm 195X 960X 680 195X 960X 680 195X 1,160X 680 195X 1,160X 680 195X 1,400X 680 195X 1,590X 680 (HX WX D) Decoration panel mm 70X 1,240X 800 70X 1,240X 800 70X 1,440X 800 70X 1,440X 800
Machine weight kg 23 24 26 27 32 35 Machine weight Unit kg 30 31 33 33
Cooling °CWB 14 to 23 12 to 25 Decoration panel kg 8.5 8.5 9.5 9.5
Certified
operation range Heating °CDB 15 to 28 15 to 27 Certified Cooling °CWB 14 to 23 12 to 25
Colour Ivory white operation range Heating °CDB 15 to 28 15 to 27
Outdoor
unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type Colour Ivory white
Outdoor
Motor output kW 1.3 1.7 2.2 2.24 3.00 3.75
unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type
1.12 1.55 1.75 2.8 3.7 3.7 Motor output kW 1.3 1.7 2.2 2.24
Refrigerant charge (R-22) kg (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) Refrigerant charge (R-22) kg 1.12 (Charged for 10 m) 1.55 (Charged for 10 m) 1.75 (Charged for 5 m) 2.8 (Charged for 30 m)
Sound level (Cooling/Heating) 3 dB(A) 47/48 49/51 54/54 48/49 49/52 49/52 Sound level (Cooling/Heating) 3 dB(A) 47/48 49/51 54/54 48/49
Dimensions (HX WX D) mm 540X 750X 270 685X 800X 300 685X 880X 350 770X 900X 320 1,170X 900X 320 1,170X 900X 320 Dimensions (HX WX D) mm 540×750×270 685×800×300 685×880×350 770×900×320
Machine weight kg 41 51 75 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) 101 Machine weight kg 41 51 75 73 (V1), 72 (Y1)
Cooling °CDB 19.4 to 46 -5 to 46 Cooling °CDB 19.4 to 46 -5 to 46
Certified Certified
operation range Heating °CWB -10 to 15.5 -10 to 15 operation range Heating °CWB -10 to 15.5 -10 to 15
Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5
connections Gas (Flare) mm o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 connections Gas (Flare) mm o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9
Drain Indoor unit mm I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 Drain Indoor unit mm I.D o/ 25×O.D o/ 32 I.D o/ 25×O.D o/ 32 I.D o/ 25×O.D o/ 32 I.D o/ 25×O.D o/ 32
Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole)
Max. interunit piping length m 20 30 50 (equivalent length 70 m) Max. interunit piping length m 20 30 50 (equivalent length 70 m)
Max. installation level difference m 15 30 Max. installation level difference m 15 30
Heat insulation Both liquid and gas piping Heat insulation Both liquid and gas piping
Note : Note :
1 1
Rated cooling capacities are based on the following conditions: Rated cooling capacities are based on the following conditions:
1a 1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b 1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.)
2 2
Rated heating capacities are based on the following conditions: Rated heating capacities are based on the following conditions:
Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.)
3 3
Anechoic chamber conversion value, measured according to JIS parameters and criteria. Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions. During operation these values are somewhat higher owing to ambient conditions.

49 50
CEILING MOUNTED BUILT-IN TYPE FLOOR STANDING TYPE
35 45 60 71 100 125 71 100 125
Indoor unit FHYB35FV1 FHYB45FV1 FHYB60FV1 FHYB71FV1 FHYB100FV1 FHYB125FV1 Indoor unit FVY71LAVE FVY100LAVE FVY125LAVE
Model Model
Name RY71LUV1 RY100LUV1 Name RY71LUV1 RY100LUV1
Outdoor unit RY35FV1A RY50GAV1A RY60GAV1A RY125LUY1 Outdoor unit RY125LUY1
RY71LUY1 RY100LUY1 RY71LUY1 RY100LUY1
Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Cooling capacity 1a/1b kW 3.5/3.5 5.0/4.85 6.3/6.15 7.8/7.7 10.5/10.4 13.0/12.8 Cooling capacity 1a/1b kW 7.8/7.7 10.5/10.4 13.0/12.8
Btu/h 12,100/11,900 16,900/16,600 21,400/21,000 26,600/26,200 35,700/35,300 44,500/43,600 Btu/h 26,600/26,200 35,700/35,300 44,500/43,600
kcal/h 3,040/3,000 4,260/4,200 5,390/5,300 6,700/6,600 9,000/8,900 11,200/11,000 kcal/h 6,700/6,600 9,000/8,900 11,200/11,000
Heating capacity 2 kW 4.1 5.5 7.1 7.9 11.2 14.2 Heating capacity 2 kW 7.9 11.2 14.2
Btu/h 14,000 18,800 24,200 27,000 38,100 48,400 Btu/h 27,000 38,100 48,400
kcal/h 3,520 4,750 6,100 6,800 9,600 12,200 kcal/h 6,800 9,600 12,200
Cooling 1a/1b kW 1.53/1.52 1.97/1.96 2.91/2.89 3.07/3.07 (V1), 3.05/3.05 (Y1) 3.92/3.92 (V1), 3.87/3.87 (Y1) 4.67/4.67 Cooling 1a/1b kW 3.12/3.12 (V1), 3.10/3.10 (Y1) 3.95/3.95 (V1), 3.90/3.90 (Y1) 4.99/4.99
Power consumption Power consumption
Heating 2 kW 1.34 1.92 2.71 3.06 (V1), 3.03 (Y1) 3.75 (V1), 3.70 (Y1) 4.63 Heating 2 kW 3.00 (V1), 2.97 (Y1) 3.75 (V1), 3.70 (Y1) 4.73
Colour Unit ---------- Colour White
Indoor Indoor
Decoration panel White Airflow rate (H) m3/min 18 28 32
unit unit
Airflow rate (H) m3/min 11.5 14 17 19 27 35 cfm 635 988 1,129
cfm 405 494 600 670 953 1,235 Sound level (H/L) 3 dB(A) 41/35 46/40 49/43
Sound level (H/L) 3 dB(A) 38/32 39/34 41/35 41/35 41/35 44/38 Dimensions (HX WX D) mm 1,850X 600X 270 1,850X 600X 350 1,850X 600X 350
Dimensions Unit mm 300X 700X 800 300X 700X 800 300X 1,000X 800 300X 1,000X 800 300X 1,400X 800 300X 1,400X 800 Machine weight kg 39 46 47
(HX WX D) Decoration panel mm 55X 880X 500 55X 880X 500 55X 1,100X 500 55X 1,100X 500 55X 1,500X 500 55X 1,500X 500 Certified Cooling °CWB 12 to 25
Machine weight Unit kg 30 31 41 41 51 52 operation range Heating °CDB 15 to 27
Decoration panel kg 3.5 3.5 4.5 4.5 6.5 6.5 Colour Ivory white
Outdoor
Certified Cooling °CWB 14 to 23 12 to 25 Compressor Type Hermetically sealed scroll type
unit
operation range Heating °CDB 15 to 28 15 to 27 Motor output kW 2.24 3.00 3.75
Colour Ivory white Refrigerant charge (R-22) kg 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m)
Outdoor
unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type Sound level (Cooling/Heating) 3 dB(A) 48/49 49/52 49/52
Motor output kW 1.3 1.7 2.2 2.24 3.00 3.75 Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320
1.12 1.55 1.75 2.8 3.7 3.7 Machine weight kg 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) 101
Refrigerant charge (R-22) kg (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) Certified Cooling °CDB -5 to 46
Sound level (Cooling/Heating) 3 dB(A) 47/48 49/51 54/54 48/49 49/52 49/52 operation range Heating °CWB -10 to 15
Dimensions (HX WX D) mm 540X 750X 270 685X 800X 300 685X 880X 350 770X 900X 320 1,170X 900X 320 1,170X 900X 320 Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5
Machine weight kg 41 51 75 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) 101 connections Gas (Flare) mm o/ 15.9 o/ 19.1 o/ 19.1
Certified Cooling °CDB 19.4 to 46 -5 to 46 Drain Indoor unit mm I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26
operation range Heating °CWB -10 to 15.5 -10 to 15 Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)
Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5 o/ 9.5 o/ 9.5 Max. interunit piping length m 50 (equivalent length 70 m)
connections Gas (Flare) mm o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9 o/ 19.1 o/ 19.1 Max. installation level difference m 30
Drain Indoor unit mm I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 Heat insulation Both liquid and gas piping
Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)
Max. interunit piping length m 20 30 50 (equivalent length 70 m)
Max. installation level difference m 15 30 DUCT CONNECTION LOW STATIC PRESSURE TYPE
Heat insulation Both liquid and gas piping 35 50 60 71
Indoor unit FDYB35KAVE FDYB50KAVE FDYB60KAVE FDYB71KAVE
WALL MOUNTED TYPE Model
Name RY71LUV1
Outdoor unit RY35FV1A RY50GAV1A RY60GAV1A
71 100 RY71LUY1
Indoor unit FAY71LVE FAY100FAVE Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Model Cooling capacity 1a/1b kW 3.79/3.75 5.27/5.20 6.24/6.15 7.8/7.7
Name RY71LUV1 RY100LUV1
Outdoor unit Btu/h 12,900/12,800 18,000/17,800 21,300/21,000 26,600/26,200
RY71LUY1 RY100LUY1
Power Supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz kcal/h 3,260/3,230 4,530/4,470 5,370/5,290 6,700/6,600
Cooling capacity 1a/1b kW 7.8/7.7 10.5/10.4 Heating capacity 2 kW 4.22 5.80 7.0 7.9
Btu/h 26,600/26,200 35,700/35,300 Btu/h 14,400 19,800 23,900 27,000
kcal/h 6,700/6,600 9,000/8,900 kcal/h 3,630 4,990 6,020 6,800
Heating capacity 2 kW 7.9 11.2 Cooling 1a/1b kW 1.51/1.50 2.01/2.00 2.38/2.36 3.08/3.08 (V1), 3.06/3.06 (Y1)
Power consumption
Btu/h 27,000 38,100 Heating 2 kW 1.33 1.78 2.29 2.91 (V1), 2.88 (Y1)
kcal/h 6,800 9,600 Colour ----------
Indoor
Cooling 1a/1b kW 2.92/2.92 (V1), 2.90/2.90 (Y1) 3.82/ 3.82 (V1), 3.77/ 3.77 (Y1) unit Airflow rate (H) m3/min 13 18
Power consumption cfm 460 635
Heating 2 kW 2.85 (V1), 2.82 (Y1) 3.66 (V1), 3.61 (Y1)
Colour White Fan External static pressure Pa(mmH2O) 20 (2)
Indoor Direct drive (2 speed)
Airflow rate (H) m3/min 19 23 Driving system
unit
cfm 670 811 Sound level (H/L) 3 dB(A) 41/38 43/40
Sound level (H/L) 3 dB(A) 43/37 45/41 Dimensions(HX WX D) mm 260X 900X 580 260X 1,300X 580
Dimensions (HX WX D) mm 290X 1,050X 230 360X 1,570X 200 Machine weight kg 22 23 31
Machine weight kg 13 26 Certified Cooling °CWB 14 to 23 12 to 25
12 to 25 operation range Heating °CDB 15 to 28 15 to 27
Certified Cooling °CWB
operation range Heating °CDB 15 to 27 Colour Ivory white
Outdoor
Colour Ivory white unit Compressor Type Hermetically sealed rotary type Hermetically sealed scroll type
Outdoor Motor output kW 1.3 1.7 2.2 2.24
unit Compressor Type Hermetically sealed scroll type
Motor output kW 2.24 3.00 1.12 1.55 1.75 2.8
Refrigerant charge (R-22) kg (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m)
Refrigerant charge (R-22) kg 2.8 (Charged for 30 m) 3.7 (Charged for 30 m)
Sound level (Cooling/Heating) 3 dB(A) 48/49 49/52 Sound level (Cooling/Heating) 3 dB(A) 47/48 49/51 54/54 48/49
Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 Dimensions (HX WX D) mm 540X 750X 270 685X 800X 300 685X 880X 350 770X 900X 320
Machine weight kg 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) Machine weight kg 41 51 75 73 (V1), 72 (Y1)
Certified Cooling °CDB -5 to 46 Certified Cooling °CDB 19.4 to 46 -5 to 46
operation range Heating °CWB -10 to 15 operation range Heating °CWB -10 to 15.5 -10 to 15
Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 Piping Liquid (Flare) mm o/ 6.4 o/ 6.4 o/ 6.4 o/ 9.5
connections Gas (Flare) mm o/ 15.9 o/ 19.1 connections Gas (Flare) mm o/ 12.7 o/ 15.9 o/ 15.9 o/ 15.9
Drain Indoor unit mm I.D o/ 13X O.D o/ 18 I.D o/ 20X O.D o/ 26 Drain Indoor unit mm 3/4B
Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) Outdoor unit mm o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole)
Max. interunit piping length m 50 (equivalent length 70 m) Max. interunit piping length m 20 30 50 (equivalent length 70 m)
Max. installation level difference m 30 Max. installation level difference m 15 30
Heat insulation Both liquid and gas piping Heat insulation Both liquid and gas piping
Note : Note :
1
1
Rated cooling capacities are based on the following conditions: Rated cooling capacities are based on the following conditions:
(FHYB) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (FVY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.) Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
(FAY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (FDYB) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal). Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
2
Rated heating capacities are based on the following conditions: Rated heating capacities are based on the following conditions:
(FHYB) Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.) (FVY) Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
(FAY) Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). (FDYB) Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal).
3
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria. Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions. During operation these values are somewhat higher owing to ambient conditions.
51 52
Simultaneous operation system
TWIN & TRIPLE & DOUBLE TWIN MULTI

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE CEILING MOUNTED CASSETTE TYPE
71 100 125 140 200 250
71 100 125 140
Indoor unit FHYC35KVEX 2 FHYC50KVEX 2 FHYC60KVEX 2 FHYC71KVEX 2 FHYC100KVEX 2 FHYC125KVEX 2
Indoor unit FDYM03FAV1 FDYM04FAV1 FDYM05FAV1 FDYM06FAV1 Model
Model RY71LUV1 RY100LUV1
RY71LUV1 RY100LUV1 Name Outdoor unit RY125LUY1 RY140LUY1 RY200KUY1 RY250KUY1
Name Outdoor unit RY125LUY1 RY140LUY1 RY71LUY1 RY100LUY1
RY71LUY1 RY100LUY1
Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Cooling capacity 1a/1b kW 7.8/7.7 10.5/10.4 13.0/12.8 14.5/14.2 22.5/22.2 27.1/26.6
Cooling capacity 1a/1b kW 7.8/7.7 10.5/10.4 13.0/12.8 14.5/14.2
Btu/h 26,600/26,200 35,700/35,300 44,500/43,600 49,400/48,400 76,800/75,800 92,500/90,800
Btu/h 26,600/26,200 35,700/35,300 44,500/43,600 49,400/48,400
kcal/h 6,700/6,600 9,000/8,900 11,200/11,000 12,500/12,200 19,400/19,100 23,300/22,900
kcal/h 6,700/6,600 9,000/8,900 11,200/11,000 12,500/12,200
Heating capacity 2 kW 7.9 11.2 14.2 16.3 22.7 28.4
Heating capacity 2 kW 7.9 11.2 14.2 16.3
Btu/h 27,000 38,100 48,400 56,000 77,500 97,000
Btu/h 27,000 38,100 48,400 56,000
kcal/h 6,800 9,600 12,200 14,000 19,500 24,400
kcal/h 6,800 9,600 12,200 14,000
Power Cooling 1a/1b kW 3.11/3.11 (V1), 3.09/3.09 (Y1) 3.98/3.98 (V1), 3.93/3.93 (Y1) 4.94/4.94 4.95/4.95 7.7/7.6 9.7/9.7
Cooling 1a/1b kW 3.19/3.19 (V1), 3.17/3.17 (Y1) 4.00/4.00 (V1), 3.95/3.95 (Y1) 4.99/4.99 5.10/5.10
Power consumption consumption Heating 2 kW 2.94 (V1), 2.92 (Y1) 3.69 (V1), 3.65 (Y1) 4.73 4.84 6.5 9.2
Heating 2 kW 2.95 (V1), 2.92 (Y1) 3.91 (V1), 3.86 (Y1) 4.75 4.96
Colour Unit -------------
Colour ---------- Indoor
Indoor Decoration panel White
Fan Airflow rate (H) m3/min 20 26 35 37 unit 3
unit Airflow rate (H) m3/min 14 15 19 19 28 33
cfm 706 917 1,235 1,306
cfm 494 529 670 670 988 1,164
External static pressure Pa(mmH2O) 98 (10) 98 (10) 98 (10) 98 (10)
Sound level (H/L) 4 dB(A) 33/29 33/29 35/30 35/30 39/34 42/36
Sound level (H) 3 dB(A) 39 39 44 46
Dimensions Unit mm 230X 840X 840 230X 840X 840 230X 840X 840 230X 840X 840 288X 840X 840 288X 840X 840
Dimensions (HX WX D) mm 295X 1,100X 680 295X 1,500X 680 295X 1,500X 680 295X 1,500X 680
(HX WX D) Decoration panel mm 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950
Machine weight kg 42 56 57 57
Machine Unit kg 24 24 24 24 28 28
Certified Cooling °CWB 12 to 25
operation range Heating weight Decoration panel kg 5 5 5 5 5 5
°CDB 15 to 27
Certified Cooling °CWB 12 to 25 14 to 25
Colour Ivory white operation range Heating
Outdoor °CDB 15 to 27 15 to 27
unit Compressor Type Hermetically sealed scroll type
Colour Ivory white
Motor output kW 2.24 3.00 3.75 4.50 Outdoor
Compressor Type Hermetically sealed scroll type
Refrigerant charge (R-22) kg 2.8 (Charged for 30 m) 3.7 (Charged for 30 m) 3.7 (Charged for 30 m) 4.1 (Charged for 30 m) unit
Motor output kW 2.24 3.00 3.75 4.50 5.5 9.0
Sound level (Cooling/Heating) 3 dB(A) 48/49 49/52 49/52 54/56
2.8 3.7 3.7 4.1 4.0 5.5
Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 Refrigerant charge (R-22) kg (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 5 m) (Charged for 5 m)
Machine weight kg 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) 101 112
Sound level (Cooling/Heating) 4 dB(A) 48/49 49/52 49/52 54/56 60/62 61/63
Certified Cooling °CDB -5 to 46
operation range Heating Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 1,220X 1,280X 690 1,440X 1,280X 690
°CWB -10 to 15
Machine weight kg 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) 101 112 180 206
Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5
Certified Cooling °CDB -5 to 46 0 to 50
connections Gas (Flare) mm o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1 operation range Heating °CWB -10 to 15 -10 to 15
Drain Indoor unit mm I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 oI.Do/ 25X O.Do/ 32
Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 12.7 o/ 15.9
Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)
connections Gas mm o/ 15.9 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 25.4 (Flange) o/ 28.6 (Flange)
Max. interunit piping length m 50 (equivalent length 70 m)
Drain Indoor unit mm I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32
Max. installation level difference m 30
Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) --------- ---------
Heat insulation Both liquid and gas piping
Max. interunit piping length m 50 (equivalent length 70 m)
Max. installation level difference m 30
DUCT CONNECTION HIGH STATIC PRESSURE TYPE Heat insulation Both liquid and gas piping

140 200 250 400 500 140 200 200 250


Model Indoor unit FDY06KAY1 FDY08KAY1 FDY10KAY1 FDY15KAY1 FDY20KAY1 Model Indoor unit FHYC50KVEX 3 FHYC71KVEX 3 FHYC50KVEX 4 FHYC60KVEX 4
Name Outdoor unit RY140LUY1 RY200KUY1 RY250KUY1 RY200KUY1X 2 RY250KUY1X 2 Name Outdoor unit RY140LUY1 RY200KUY1 RY200KUY1 RY250KUY1
Power supply Y1: 3 phase, 380–415 V (4 wires), 50 Hz Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Cooling capacity 1a/1b kW 14.5/14.2 22.5/22.2 27.6/27.1 44.0/43.5 53.9/53.0 Cooling capacity 1a/1b kW 14.5/14.2 22.5/22.2 22.5/22.2 27.1/26.6
Btu/h 49,500/48,500 76,800/75,700 94,200/92,500 150,000/148,000 184,000/181,000 Btu/h 49,400/48,400 76,800/75,800 76,800/75,800 92,500/90,800
kcal/h 12,500/12,220 19,300/19,100 23,700/23,300 37,800/37,400 46,400/45,600 kcal/h 12,500/12,200 19,400/19,100 19,400/19,100 23,300/22,900
Heating capacity 2 kW 15.3 23.2 29.5 44.8 56.8 Heating capacity 2 kW 16.3 22.7 22.7 28.4
Btu/h 52,200 79,200 100,700 153,000 194,000 Btu/h 56,000 77,500 77,500 97,000
kcal/h 13,200 20,000 25,400 38,500 48,800 kcal/h 14,000 19,500 19,500 24,400
Cooling 1a/1b kW 5.14/5.14 7.2/7.1 9.3/9.2 14.4/14.2 18.5/18.3 Power Cooling 1a/1b kW 4.95/4.95 7.7/7.6 7.7/7.6 9.7/9.7
Power consumption consumption
Heating 2 kW 4.54 6.1 8.8 12.2 17.6 Heating 2 kW 4.84 6.5 6.5 9.2
Colour --------- Colour Unit -------------
Indoor Indoor
Airflow rate (H) m3/min 52 68 83 136 166 Decoration panel White
unit unit 3
cfm 1,835 2,400 2,929 4,800 5,859 Airflow rate (H) m3/min 15 19 15 19
Fan External static pressure Pa(mmH2O) 108 (11) 118 (12) 147 (15) cfm 529 670 529 670
Driving system Belt drive Sound level (H/L) 4 dB(A) 33/29 35/30 33/29 35/30
Sound level (H) 3 dB(A) 51 53 58 60 Dimensions Unit mm 230X 840X 840 230X 840X 840 230X 840X 840 230X 840X 840
Dimensions(HX WX D) 5 mm 450X 1,130X 850 500X 1,130X 850 500X 1,330X 850 625X 1,620X 850 625X 1,980X 850 (HX WX D) Decoration panel mm 40X 950X 950 40X 950X 950 40X 950X 950 40X 950X 950
Machine weight kg 80 94 105 161 187 Machine Unit kg 24 24 24 24
Certified Cooling °CWB 12 to 25 14 to 25 weight Decoration panel kg 5 5 5 5
operation range Heating °CDB 15 to 27 Certified Cooling °CWB 12 to 25 14 to 25
Colour Ivory white operation range Heating °CDB 15 to 27 15 to 27
Outdoor
Compressor Type Hermetically sealed scroll type Colour Ivory white
unit Outdoor
Motor output kW 4.5 5.5 9.0 5.5 X 2 9.0 X 2 Compressor Type Hermetically sealed scroll type
unit
4.1 4.0 5.5 4.0 5.5 Motor output kW 4.50 5.5 5.5 9.0
Refrigerant charge (R-22) kg (Charged for 30 m) (Charged for 5 m) (Charged for 5 m) (Charged for 5 m) X 2 (Charged for 5 m) X 2 Refrigerant charge (R-22) kg 4.1 (Charged for 30 m) 4.0 (Charged for 5 m) 4.0 (Charged for 5 m) 5.5 (Charged for 5 m)
Sound level (Cooling/Heating) 3 dB(A) 54/56 60/62 61/63 60/62 4 61/63 4 Sound level (Cooling/Heating) 4 dB(A) 54/56 60/62 60/62 61/63
Dimensions (HX WX D) mm 1,345X 900X 320 1,220X 1,280X 690 1,440X 1,280X 690 (1,220X 1,280X 690) X 2 (1,440X 1,280X 690) X 2 Dimensions (HX WX D) mm 1,345X 900X 320 1,220X 1,280X 690 1,220X 1,280X 690 1,440X 1,280X 690
Machine weight kg 112 180 206 180 X 2 206 X 2 Machine weight kg 112 180 180 206
Certified Cooling °CDB -5 to 46 0 to 50 0 to 50 Certified Cooling °CDB -5 to 46 0 to 50
operation range Heating °CWB -10 to 15 -10 to 15 -10 to 15 operation range Heating °CWB -10 to 15 -10 to 15
Piping Liquid (Flare) mm o/ 9.5 o/ 12.7 o/ 15.9 o/ 12.7 X 2 o/ 15.9 X 2 Piping Liquid (Flare) mm o/ 9.5 o/ 12.7 o/ 12.7 o/ 15.9
connections Gas mm o/ 19.1 (Flare) o/ 25.4 (Flange) o/ 28.6 (Flange) o/ 25.4 X 2 (Flange) o/ 28.6 X 2 (Flange) connections Gas mm o/ 19.1 (Flare) o/ 25.4 (Flange) o/ 25.4 (Flange) o/ 28.6 (Flange)
Drain Indoor unit mm 3/4B 1B Drain Indoor unit mm I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32
Outdoor unit mm o/ 26.0 (Hole) --------- Outdoor unit mm o/ 26.0 (Hole) --------- --------- ---------
Max. interunit piping length m 50 (equivalent length 70 m) Max. interunit piping length m 50 (equivalent length 70 m)
Max. installation level difference m 30 Max. installation level difference m 30
Heat insulation Both liquid and gas piping Heat insulation Both liquid and gas piping
Note : Note :
Models RY200KU and RY250KU are recommended for commercial facilities. Models RY200KU and RY250KU are recommended for commercial facilities.
1 1
Rated cooling capacities are based on the following conditions: Rated cooling capacities are based on the following conditions:
1a 1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b 1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
2 2
Rated heating capacities are based on the following conditions: Rated heating capacities are based on the following conditions:
Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
3 3
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. Values shown are for a single unit only.
4 4
Specification for outdoor unit is for a single unit only. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
5
Without control box.

53 54
Simultaneous operation system
TWIN & TRIPLE & DOUBLE TWIN MULTI

CEILING SUSPENDED TYPE DUCT CONNECTION LOW STATIC PRESSURE TYPE


71 100 125 140 200 250 200 200 250
Indoor unit FHY35BVE × 2 FHY50BVE × 2 FHY60BVE × 2 FHY71BVE × 2 FHY100BVE × 2 FHY125BVE × 2 Model Indoor unit FDYB50KAVE × 4 FDYB71KAVE × 3 FDYB60KAVE × 4
Model
RY71LUV1 RY100LUV1 Name Outdoor unit RY200KUY1 RY200KUY1 RY250KUY1
Name Outdoor unit RY125LUY1 RY140LUY1 RY200KUY1 RY250KUY1
RY71LUY1 RY100LUY1 Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz Cooling capacity 1a/1b kW 22.5/22.2 22.5/22.2 27.1/26.6
Cooling capacity 1a/1b kW 7.8/7.7 10.5/10.4 13.0/12.8 14.5/14.2 22.5/22.2 27.1/26.6 Btu/h 76,800/75,800 76,800/75,800 92,500/90,800
Btu/h 26,600/26,200 35,700/35,300 44,500/43,600 49,400/48,400 76,800/75,800 92,500/90,800 kcal/h 19,400/19,100 19,400/19,100 23,300/22,900
kcal/h 6,700/6,600 9,000/8,900 11,200/11,000 12,500/12,200 19,400/19,100 23,300/22,900 Heating capacity 2 kW 22.7 22.7 28.4
Heating capacity 2 kW 7.9 11.2 14.2 16.3 22.7 28.4 Btu/h 77,500 77,500 97,000
Btu/h 27,000 38,100 48,400 56,000 77,500 97,000 kcal/h 19,500 19,500 24,400
kcal/h 6,800 9,600 12,200 14,000 19,500 24,400 Cooling 1a/1b kW 7.7/7.6 7.7/7.6 9.7/9.7
Power consumption
Power 3.14/3.14 (V1) 3.87/3.87 (V1) Heating 2 kW 6.5 6.5 9.2
Cooling 1a/1b kW 4.91/4.91 5.10/5.10 7.7/7.6 9.7/9.7
consumption 3.12/3.12 (Y1) 3.82/3.82 (Y1) Colour –––
Indoor
Heating 2 kW 3.08 (V1), 3.05 (Y1) 3.74 (V1),3.69 (Y1) 4.83 4.99 6.5 9.2 Airflow rate (H) m3/min 13 18 18
unit 3
Colour White cfm 458 635 635
Indoor
unit 3 Airflow rate (H) m3/min 13 13 16 17 24 30 Fan External static pressure Pa(mmH2O) 20 (2)
cfm 458 458 564 600 847 1,059 Sound level (H) 4 dB(A) 41 43 43
Sound level (H/L) 4 dB(A) 37/32 38/33 38/33 39/35 42/37 44/39 Dimensions (HX WX D) mm 260X 900X 580 260X 1,300X 580 260X 1,300X 580
Dimensions (HX WX D) mm 195X 960X 680 195X 960X 680 195X 1,160X 680 195X 1,160X 680 195X 1,400X 680 195X 1,590X 680 Machine weight kg 23 31 31
Machine weight kg 23 24 26 27 32 35 Certified Cooling °CWB 14 to 25 14 to 25 14 to 25
Certified Cooling °CWB 12 to 25 14 to 25 operation range Heating °CDB 15 to 27 15 to 27 15 to 27
operation range Heating °CDB 15 to 27 15 to 27 Colour Ivory white
Outdoor
Colour Ivory white unit Compressor Type Hermetically sealed scroll type
Outdoor
Compressor Type Hermetically sealed scroll type Motor output kW 5.5 5.5 9.0
unit
Motor output kW 2.24 3.00 3.75 4.50 5.5 9.0 Refrigerant charge (R-22) kg 4.0 (Charged for 5 m) 4.0 (Charged for 5 m) 5.5 (Charged for 5 m)
2.8 3.7 3.7 4.1 4.0 5.5 Sound level (Cooling/Heating) 4 dB(A) 60/62 60/62 61/63
Refrigerant charge (R-22) kg (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 5 m) (Charged for 5 m) Dimensions (HX WX D) mm 1,220X 1,280X 690 1,220X 1,280X 690 1,440X 1,280X 690
Sound level (Cooling/Heating) 4 dB(A) 48/49 49/52 49/52 54/56 60/62 61/63 Machine weight kg 180 180 206
Dimensions (HX WX D) mm 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320 1,220X 1,280X 690 1,440X 1,280X 690 Certified Cooling °CDB 0 to 50
Machine weight kg 73 (V1), 72 (Y1) 89 (V1), 86 (Y1) 101 112 180 206 operation range Heating °CWB -10 to 15
Certified Cooling °CDB -5 to 46 0 to 50 Piping Liquid mm 12.7 (Flare) 12.7 (Flare) 15.9 (Flare)
operation range Heating °CWB -10 to 15 -10 to 15 connections Gas mm 25.4 (Flange) 25.4 (Flange) 28.6 (Flange)
Piping Liquid (Flare) mm o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5 o/ 12.7 o/ 15.9 Drain Indoor unit mm 3/4B
connections Gas mm o/ 15.9 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 19.1 (Flare) o/ 25.4 (Flange) o/ 28.6 (Flange) Outdoor unit mm –––
Drain Indoor unit mm I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 Max. interunit piping length m 50 (equivalent length 70 m)
Outdoor unit mm o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) --------- --------- Max. installation level difference m 30
Max. interunit piping length m 50 (equivalent length 70 m) Heat insulation Both liquid and gas piping
Max. installation level difference m 30
Heat insulation Both liquid and gas piping

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE


140 200 200 250
200 250 200
Model Indoor unit FHY50BVE × 3 FHY71BVE × 3 FHY50BVE × 4 FHY60BVE × 4 Model Indoor unit FDYM04FAV1 × 2 FDYM05FAV1 × 2 FDYM03FAV1 × 3
Name Outdoor unit RY140LUY1 RY200KUY1 RY200KUY1 RY250KUY1 Name Outdoor unit RY200KUY1 RY250KUY1 RY200KUY1
Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Cooling capacity 1a/1b kW 14.5/14.2 22.5/22.2 22.5/22.2 27.1/26.6 Cooling capacity 1a/1b kW 22.5/22.2 27.1/26.6 22.5/22.2
Btu/h 49,400/48,400 76,800/75,800 76,800/75,800 92,500/90,800 Btu/h 76,800/75,800 92,500/90,800 76,800/75,800
kcal/h 12,500/12,200 19,400/19,100 19,400/19,100 23,300/22,900 kcal/h 19,400/19,100 23,300/22,900 19,400/19,100
Heating capacity 2 kW 16.3 22.7 22.7 28.4 Heating capacity 2 kW 22.7 28.4 22.7
Btu/h 56,000 77,500 77,500 97,000 Btu/h 77,500 97,000 77,500
kcal/h 14,000 19,500 19,500 24,400 kcal/h 19,500 24,400 19,500
Power Cooling 1a/1b kW 5.10/5.10 7.7/7.6 7.7/7.6 9.7/9.7 kW
Power Cooling 1a/1b 7.7/7.6 9.9/9.9 8.0/7.9
consumption Heating 2 kW 4.99 6.5 6.5 9.2 consumption Heating 2 kW 6.5 9.2 6.8
Colour White ----------
Indoor Colour
Airflow rate (H) m3/min 13 17 13 16 Indoor
unit 3 Fan Airflow rate (H) m3/min 26 35 20
cfm 458 600 458 564 unit 3
cfm 917 1,235 706
Sound level (H/L) 4 dB(A) 38/33 39/35 38/33 38/33
External static pressure Pa(mmH2O) 98 (10) 98 (10) 98 (10)
Dimensions (HX WX D) mm 195X 960X 680 195X 1,160X 680 195X 960X 680 195X 1,160X 680 dB(A)
Sound level (H) 4 39 44 39
Machine weight kg 24 27 24 26 mm
Dimensions (HX WX D) 295X 1,500X 680 295X 1,500X 680 295X 1,100X 680
Certified Cooling °CWB 12 to 25 14 to 25 kg
Machine weight 56 57 42
operation range Heating °CDB 15 to 27 15 to 27
Certified Cooling °CWB 14 to 25
Colour Ivory white operation range Heating °CDB
Outdoor 15 to 27
Compressor Type Hermetically sealed scroll type
unit Colour Ivory white
Motor output kW 4.50 5.5 5.5 9.0 Outdoor
unit Compressor Type Hermetically sealed scroll type
Refrigerant charge (R-22) kg 4.1 (Charged for 30 m) 4.0 (Charged for 5 m) 4.0 (Charged for 5 m) 5.5 (Charged for 5 m)
Motor output kW 5.5 9.0 5.5
Sound level (Cooling/Heating) 4 dB(A) 54/56 60/62 60/62 61/63
Refrigerant charge (R-22) kg 4.0 (Charged for 5 m) 5.5 (Charged for 5 m) 4.0 (Charged for 5 m)
Dimensions (HX WX D) mm 1,345X 900X 320 1,220X 1,280X 690 1,220X 1,280X 690 1,440X 1,280X 690 dB(A)
Sound level (Cooling/Heating) 4 60/62 61/63 60/62
Machine weight kg 112 180 180 206 mm
Dimensions (HX WX D) 1,220X 1,280X 690 1,440X 1,280X 690 1,220X 1,280X 690
Certified Cooling °CDB -5 to 46 0 to 50 kg
Machine weight 180 206 180
operation range Heating °CWB -10 to 15 -10 to 15
Certified Cooling °CDB 0 to 50
Piping Liquid (Flare) mm o/ 9.5 o/ 12.7 o/ 12.7 o/ 15.9 operation range Heating °CWB -10 to 15
connections Gas mm o/ 19.1 (Flare) o/ 25.4 (Flange) o/ 25.4 (Flange) o/ 28.6 (Flange)
Piping Liquid (Flare) mm o/ 12.7 o/ 15.9 o/ 12.7
Drain Indoor unit mm I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 connections mm
Gas o/ 25.4 (Flange) o/ 28.6 (Flange) o/ 25.4 (Flange)
Outdoor unit mm o/ 26.0 (Hole) --------- --------- ---------
Drain Indoor unit mm I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32
Max. interunit piping length m 50 (equivalent length 70 m) mm
Outdoor unit --------- --------- ---------
Max. installation level difference m 30 m
Max. interunit piping length 50 (equivalent length 70 m)
Heat insulation Both liquid and gas piping m
Max. installation level difference 30
Note : Heat insulation Both liquid and gas piping
Models RY200KU and RY250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions: Note :
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). Models RY200KU and RY250KU are recommended for commercial facilities.
1
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) Rated cooling capacities are based on the following conditions:
1a
2
Rated heating capacities are based on the following conditions: Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.) Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal)
2
3
Values shown are for a single unit only. Rated heating capacities are based on the following conditions:
4
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal)
3
Values shown are for a single unit only.
4
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.

55 56
CEILING MOUNTED CASSETTE CORNER TYPE
Indoor unit Kit name
Name of option Remark Cooling only Heat pump
CEILING MOUNTED CASSETTE TYPE FHK35F/45F FHK60F/FHYK71F FHYK35FJ/45FJ FHYK60FJ/71FJ
Kit name Decoration panel BYK45FJW1 BYK71FJW1 BYK45FJW1 BYK71FJW1
Cooling only Heat pump Panel spacer KPBJ52F56W KPBJ52F80W KPBJ52F56W KPBJ52F80W
Name of option Remark
FHC35K/50K/60K Air discharge blind panel KDBJ52F56W KDBJ52F80W KDBJ52F56W KDBJ52F80W
FHYC100K/125K/140K FHYC35K/50K/60K/71K FHYC100K/125K/140K
FHYC35K/50K/60K/71K Replacement long-life filter Resin net KAFJ521F56 KAFJ521F80 KAFJ521F56 KAFJ521F80
Decoration panel BYC125K-W1 BYC125K-W1 Discharge grille K-HV7AW K-HV9AW K-HV7AW K-HV9AW
Sealing member for air discharge outlet KDBHJ55K160 KDBHJ55K160 Flexible duct with shutter KFDJ52F56 KFDJ52F80 KFDJ52F56 KFDJ52F80
Panel spacer KDBP55H160WA KDBP55H160WA Remote controller Wired type1 BRC1C61 BRC1C61
Fresh air intake kit1 Chamber Without the T-joint pipe and fan KDDP55D160 KDDP55D160 Wired LCD remote controller with weekly schedule timer BRC1D61 BRC1D61
type With the T-joint pipe,without fan KDDP55D160K KDDP55D160K Central remote controller2 DCS302CA61 DCS302CA61
Direct installation type KDDJ55X160 KDDJ55X160 Unified ON/OFF controller2 DCS301BA61 DCS301BA61
Chamber connection kit2 KKSJ55K160 KKSJ55K160 Schedule timer2 DST301BA61 DST301BA61
High-efficiency filter (Colorimetric method 65%) KAFP556D80 KAFP556D160 KAFP556D80 KAFP556D160 intelligent Touch Controller2 DCS601C51 DCS601C51
(Colorimetric method 90%) KAFP557D80 KAFP557D160 KAFP557D80 KAFP557D160 Adaptor for wiring (interlock for fresh air intake fan) KRP1B51 KRP1B51
Replacement (Colorimetric method 65%) KAFP552H80 KAFP552H160 KAFP552H80 KAFP552H160 Wiring adaptor for electrical appendices KRP4AA51 KRP4AA51
high-efficiency filter (Colorimetric method 90%) KAFP553H80 KAFP553H160 KAFP553H80 KAFP553H160 Interface adaptor for SkyAir series DTA102A52 DTA102A52
High-efficiency filter chamber KDDFP55D160 KDDFP55D160 Note: 1Wiring for wired remote controller to be procured locally.
2
Replacement long-life filter KAFJ551K160 KAFJ551K160 This optional accessory requires DTA102A52.
Ultra long-life filter KAFP55D160 KAFP55D160
Replacement ultra long-life filter KAFJ55K160H KAFJ55K160H CEILING MOUNTED BUILT-IN TYPE
Branch duct chamber KDJ55K80 KDJ55K160 KDJ55K80 KDJ55K160 Kit name
Remote controller Wired type3 BRC1C61 BRC1C61 Name of option Remark Cooling only Heat pump
Wireless type BRC7C613W BRC7C612W FHB35F/45F FHB60F/FHYB71F FHYB100F FHYB125F FHYB35F/45F FHYB60F/71F FHYB100F FHYB125F
Wired LCD remote controller with weekly schedule timer BRC1D61 BRC1D61 Decoration panel BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1
Central remote controller4 DCS302CA61 DCS302CA61 Service access panel KTBJ25K56W KTBJ25K80W KTBJ25K160W KTBJ25K56W KTBJ25K80W KTBJ25K160W
Unified ON/OFF controller4 DCS301BA61 DCS301BA61 High-efficiency filter (Colorimetric method 65%) KAFJ252L56 KAFJ252L80 KAFJ252L160 KAFJ252L56 KAFJ252L80 KAFJ252L160
Schedule timer4 DST301BA61 DST301BA61 (Colorimetric method 90%) KAFJ253L56 KAFJ253L80 KAFJ253L160 KAFJ253L56 KAFJ253L80 KAFJ253L160
intelligent Touch Controller4 DCS601C51 DCS601C51 Replacement long-life filter Resin net KAFJ251K56 KAFJ251K80 KAFJ251K160 KAFJ251K56 KAFJ251K80 KAFJ251K160
Adaptor for wiring5 KRP1BA57 KRP1BA57 Filter chamber for bottom suction KAJ25L56D KAJ25L80D KAJ25L160D KAJ25L56D KAJ25L80D KAJ25L160D
Wiring adaptor for electrical appendices5 KRP4AA53 KRP4AA53 Filter chamber for rear suction KAJ25L56B KAJ25L80B KAJ25L160B KAJ25L56B KAJ25L80B KAJ25L160B
Interface adaptor for SkyAir series DTA102A52 DTA102A52 Canvas duct KSA-25K56 KSA-25K80 KSA-25K160 KSA-25K56 KSA-25K80 KSA-25K160
Installation box for adaptor PCB KRP1B98 KRP1B98 Discharge grille (o/ 150) K-DG4DW K-DG5DW K-DG4DW K-DG5DW K-DG4DW K-DG5DW K-DG4DW K-DG5DW
Note: (o/ 200) K-DG7DW K-DG9DW K-DG7DW K-DG9DW K-DG7DW K-DG9DW K-DG7DW K-DG9DW
1
Refer to page 14 for the details. Discharge chamber (o/ 150) K-DGC4D K-DGC5D K-DGC4D K-DGC5D K-DGC4D K-DGC5D K-DGC4D K-DGC5D
2
Required for installing high-efficiency or ultra long-life filter.
3
Wiring for wired remote controller to be procured locally.
(o/ 200) K-DGC7D K-DGC9D K-DGC7D K-DGC9D K-DGC7D K-DGC9D K-DGC7D K-DGC9D
4
This optional accessory requires DTA102A52. Branch duct o/ 200 o/ 150 K-DDV20A K-DDV20A
5
Installation box for adaptor PCB (KRP1B98) is necessary. Flexible duct (o/ 150) K-FDS151D (1 m) K-FDS152D (2 m) K-FDS153D (3 m) K-FDS151D (1 m) K-FDS152D (2 m) K-FDS153D (3 m)
K-FDS154D (4 m) K-FDS155D (5 m) K-FDS156D (6 m) K-FDS154D (4 m) K-FDS155D (5 m) K-FDS156D (6 m)
(o/ 200) K-FDS201D (1 m) K-FDS202D (2 m) K-FDS203D (3 m) K-FDS201D (1 m) K-FDS202D (2 m) K-FDS203D (3 m)
K-FDS204D (4 m) K-FDS205D (5 m) K-FDS206D (6 m) K-FDS204D (4 m) K-FDS205D (5 m) K-FDS206D (6 m)
CEILING SUSPENDED TYPE Blind board KBBJ25K56 KBBJ25K80 KBBJ25K160 KBBJ25K56 KBBJ25K80 KBBJ25K160
Kit name Adaptor for discharge KDAJ25K56 KDAJ25K71 KDAJ25K140 KDAJ25K56 KDAJ25K71 KDAJ25K140
Name of option Remark Cooling only Heat pump Flange for suction KDJ2507K56 KDJ2507K80 KDJ2507K160 KDJ2507K56 KDJ2507K80 KDJ2507K160
FH(Y)35B FH(Y)50B FH(Y)60B FHY71B FHY100B FHY125B FHY35B FHY50B FHY60B FHY71B FHY100B FHY125B Remote controller Wired type1 BRC1C61 BRC1C61
Replacement long-life filter Resin net KAFJ501D56 KAFJ501D80 KAFJ501D112 KAFJ501D160 KAFJ501D56 KAFJ501D80 KAFJ501D112 KAFJ501D160 Wired LCD remote controller with weekly schedule timer BRC1D61 BRC1D61
Drain-up kit KDU50B50VE KDU50B71VE KDU50B125VE KDU50B50VE KDU50B71VE KDU50B125VE Central remote controller2 DCS302CA61 DCS302CA61
L-type piping kit (for upward direction) KHFJ5F50 KHFJ5F60 KHFJ5F80 KHFJ5F160 KHFJ5F50 KHFJ5F60 KHFJ5F80 KHFJ5F160 Unified ON/OFF controller 2 DCS301BA61 DCS301BA61
Remote controller Wired type1 BRC1C61 BRC1C61 Schedule timer2 DST301BA61 DST301BA61
Wireless type BRC7EA66 BRC7E63W
intelligent Touch Controller2 DCS601C51 DCS601C51
Wired LCD remote controller with weekly schedule timer BRC1D61 BRC1D61 Adaptor for wiring (interlock for fresh air intake fan) KRP1BA54 KRP1BA54
Central remote controller2 DCS302CA61 DCS302CA61 Wiring adaptor for electrical appendices3 KRP4AA51 KRP4AA51
Unified ON/OFF controller 2 DCS301BA61 DCS301BA61 Interface adaptor for SkyAir series DTA102A52 DTA102A52
Schedule timer2 DST301BA61 DST301BA61
Note: 1Wiring for wired remote controller to be procured locally. 2This optional accessory requires DTA102A52.
intelligent Touch Controller2 DCS601C51 DCS601C51 3
Installation box for adaptor PCB (KRP1B97) is necessary.
Adaptor for wiring KRP1BA54 KRP1BA54
Wiring adaptor for electrical appendices3 KRP4AA52 KRP4AA52 WALL MOUNTED TYPE
Interface adaptor for SkyAir series DTA102A52 DTA102A52 Kit name
Installation box for adaptor PCB KRP1CA93 KRP1CA93 Name of option Remark Cooling only Heat pump
Note: FAY71L FAY100FA FAY71L FAY100FA
1
Wiring for wired remote controller to be procured locally.
2 Drain-up kit K-KDU572CVE K-KDU572CVE
This optional accessory requires DTA102A52.
3
Installation box for adaptor PCB (KRP1CA93) is necessary. Remote controller Wired type1 BRC1C61 BRC1C61
Wireless type BRC7E619 BRC7C611W BRC7EA618 BRC7C610W
Wired LCD remote controller with weekly schedule timer BRC1D61 BRC1D61
Central remote controller DCS302CA61 DCS302CA61 2 DCS302CA61 DCS302CA61 2
CEILING SUSPENDED CASSETTE TYPE Unified ON/OFF controller DCS301BA61 DCS301BA61 2 DCS301BA61 DCS301BA61 2
Kit name Schedule timer DST301BA61 DST301BA61 2 DST301BA61 DST301BA61 2
Name of option Remark Cooling only Heat pump intelligent Touch Controller DCS601C51 DCS601C51 2 DCS601C51 DCS601C51 2
FUY71FJ FUY100FJ/125FJ FUY71FJ FUY100FJ/125FJ Wiring adaptor for electrical appendices (2) KRP4AA51 3 KRP4AA51 KRP4AA51 3 KRP4A51
Replacement long-life filter KAFJ495F140 KAFJ495F140 Interface adaptor for SkyAir series3 DTA102A52 DTA102A52
Sealing member for air discharge outlet1 KDBHJ49F80 KDBHJ49F140 KDBHJ49F80 KDBHJ49F140 Installation box for adaptor PCB KRP4AA93 KRP4AA93
Decoration panel for air discharge KDBTJ49F80 KDBTJ49F140 KDBTJ49F80 KDBTJ49F140 1
Wiring for wired remote controller to be procured locally. 2This optional accessory requires DTA102A52.
Vertical flap kit KDGJ49F80 KDGJ49F140 KDGJ49F80 KDGJ49F140 3
Installation box for adaptor PCB (KRP4AA93) is necessary.
L-connection piping kit KHFJ49F80 KHFJ49F140 KHFJ49F80 KHFJ49F140
Remote controller Wired type2 BRC1C61 BRC1C61 FLOOR STANDING TYPE
Wireless type BRC7C529W BRC7C528W Kit name
Wired LCD remote controller with weekly schedule timer BRC1D61 BRC1D61 Name of option Remark Cooling only Heat pump
Central remote controller3 DCS302CA61 DCS302CA61 FVY71LA/100LA/125LA FVY71LA/100LA/125LA
Unified ON/OFF controller3 DCS301BA61 DCS301BA61 Replacement long-life filter KAFJ95L160 KAFJ95L160
Schedule timer3 DST301BA61 DST301BA61 Wired LCD remote controller with weekly schedule timer BRC1D61 BRC1D61
intelligent Touch Controller3 DCS601C51 DCS601C51 Central remote controller1 DCS302CA61 DCS302CA61
Wiring adaptor for electrical appendices4 KRP4AA53 KRP4AA53 Unified ON/OFF controller1 DCS301BA61 DCS301BA61
Interface adaptor for SkyAir series DTA102A52 DTA102A52 Schedule timer1 DST301BA61 DST301BA61
Installation box for adaptor PCB KRP1B97 KRP1B97 intelligent Touch Controller2 DCS601C51 DCS601C51
Note: Remote controller for 2 remote control system BRC1C61 BRC1C61
1
Required at time of installation for setting two-way opposing air flow. Adaptor for wiring2 KRP1BA57 KRP1BA57
2
Wiring for wired remote controller to be procured locally.
3
This optional accessory requires DTA102A52.
Group control adaptor2 KRP4AA52 KRP4AA52
4
Installation box for adaptor PCB (KRP1B97) is necessary. Interface adaptor for SkyAir series DTA102A52 DTA102A52
Installation box for adaptor PCB KRP4A95 KRP4A95
Note: 1This optional accessory requires DTA102A52.
57 2
Installation box for adaptor PCB (KRP4A95) is necessary. 58