Professional Documents
Culture Documents
Basic of Control Component PDF
Basic of Control Component PDF
Basic of Control Component PDF
Components
INC 100 Electrotechnology
Assist. Prof. Pakorn Kaewtrakulpong, Ph.D.
INC, KMUTT
Objectives
State the purpose and general principles of control
components and circuits
Identify various symbols which represent control
components
Read a basic line diagram
Describe the construction and operating principles of
magnetic contactors and control relays
Control Loads and
Control Devices
The control load is an electrical device that uses
electrical power. E.g.
Pilot lights,
relays, and
Contactors.
Control devices are used to activate the control load.
E.g.
Pushbuttons and
switches.
Electrical Symbols
Contact
Switch
Pushbutton
Coil
Overload Relay
Pilot Light
etc
Contact
used to indicate an open or closed path of
current flow.
require an action to change their state.
can be
Normally Open (NO) or
Normally Closed (NC).
Switch
also used to indicate an open or closed path of
current flow.
require another device or action to change their
state.
can be
Normally Open (NO) or
Normally Closed (NC).
Selector Switch
Two-position
Three-position
Etc.
Switch (cont.)
Variations of this symbol are used to represent
limit switches,
foot switches,
pressure switches,
level switches,
temperature-actuated switches,
flow switches, and
selector switches.
Pushbutton
Pushbutton (cont.)
2 basic types of pushbuttons:
momentary
maintained (latches in place when the button is
pressed.)
can be
Normally Open (NO) or
Normally Closed (NC).
Pilot Lights
Pilot Light
a small electric light used to indicate a specific
condition of a circuit.
E.g., a red light might be used to indicate a motor is
running.
The letter in the center of the pilot light symbol
indicates the color of the light.
Control Relays
Control Relays (cont.)
Relays are widely used in control circuits.
They are used
for switching multiple control circuits and
for controlling light loads e.g. starting coils, pilot
lights, and audible alarms.
Relay Operation
Coil
used in electromagnetic starters, contactors, and
relays.
The purpose of contactors and relays is to open
and close associated contacts.
A letter is used to designate the coil; the
associated contacts have the same identifying
letter.
Coil (cont.)
Associated contacts can be
Normally Open (NO) or
Normally Closed (NC).
Coil Example
Magnetic Contactors
Basic Contactor Operation
Magnetic Contactors: Interior
Control Transformers
Timing Relays
On-Delay, Time Closed
Off-Delay, Timed Open
Line Diagrams
also referred to as a ladder diagrams.
show the functional relationship of
components and devices in an electrical circuit,
not the physical relationship.
made up of 2 circuits,
the control circuit and
the power circuit.
Line Diagrams (cont.)
Electrical wires in a line diagram are represented by
lines.
Control-circuit wiring is represented by a lighter-weight
line and power-circuit wiring is represented by a heavier-
weight line.
A small dot or node at the intersection of 2 or more
wires indicates an electrical connection.
Line diagrams are read from left to right.
Example: Power Circuit and Control
Circuit
Connecting Loads and
Control Devices
Control circuits are made up of control loads
and control devices.
Line Numbering
Two-Wire Control
A two-wire control circuit provides low-voltage
release but not low-voltage protection.
low-voltage release
In the event of a power loss the contactor will
deenergize, stopping the motor.
However, when power is restored, the motor will
restart without warning if the control device is still
closed.
Two-Wire Control (cont.)
This type of control scheme is used for remote
or inaccessible installations such as water-
treatment plants or pumping stations. In these
applications it is desirable to have an immediate
return to service when power is restored.
Two-Wire Control (cont.)
Holding Circuit
Three-Wire Control
low-voltage protection.
If an overload causes the “OL” contacts in the control
circuit to open,
the “M” coil is deenergized and
the motor shut down.
When the overload is cleared,
the motor will not suddenly restart on its own.
An operator must depress the “Start” button to restart the
motor.
Holding Circuit
Three-Wire Control (cont.)
Interposing a Relay
A 24 VAC coil may not be strong enough to
operate a large starter. E.g.
the electromagnetic coil of the “M” contactor
selected is rated for 460 VAC.
The electromagnetic coil of the control relay (CR)
selected is 24 VAC.
Interposing a Relay (cont.)
Schematic Diagram
Wiring Diagram
Some Simple Motor Control
Applications
Forward-Reverse Motor Control
Star-Delta Motor-Starting Control
Forward-Reverse Motor Control
e.g.
Jogging circuits
Reversing-after-stop
circuits
Jogging Circuits