Off Grid Professional Design

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 16

Load description Quantity Power (W) consumption period (hour/day)

Lamp 460 36 8
Air condition 10 1150 4
Computer 10 210 5
Ceiling fan 1 75 4
Printer 1 550 2
Extra 1 500 4

Total load (KW)


Total daily energy demand(Wh)
Total daily energy demand(KWh)
Daily energy demand (Wh)
132480
46000
10500
300
1100
2000

31.285
192380
192.38
System Detail
Total energy demand(Wh) 192380
System DC voltage (V) 120
PSH 5.73

Factors considered in sizing


Oerall inverter efficiency 0.97
Oversupply co-efficient 1.3
coulombic efficiency of battery 0.9
loss in charge regulator and cables 0.95
loss due to temperature 0.95
Manufacturer tolarnce 1
soling loss 0.95

Module
Pmax 310
Vmp 36
Imp 8.33
Voc 45.1
Isc 8.95
Price ($) 106
Array sizing
AC sub system efficiency 0.82935
DC daily load demand (Ah) 2512.9519
Module derating factor 0.9025
Module output (Ah) 43.077137
NO of parallel module 58.336094 59
No of series module 3.3333333 4
Total module 236
System detial Battery sizing
Total energy demand (Wh) 192380 Battery capacity (Ah)
System Dc voltage 120 NO of battery in parallel
Backup (Day) 3 NO of battery in series
DOD 0.7 Total NO of Battery
Derating factor 0.85
Rate factor 1.8

Battery
Voltage 12
Capacity (Ah) 1200
Price ($) 120
ttery sizing
4490.6629
3.7422191 4
10 10
40
IN

System detial Inveter sizing


Total Load demand (KW) 31.285 Inveter rating 39.10625
Safety Factor 1.25

2*20 KW off grid inverter


Model number PI9000S
Eelectrical specifications
Input voltage 100-700V
Input ampere 100-250 A
Output voltage 220-240
Efficiency 0.97
Power factor 1
MPPt 1
Price 1 inverter 1000 $
Module
Pmax 310
Vmp 36 Location
Imp 8.33
String
Voc 45.1
Isc 8.95
Between array& Inverter

Sub array 1
NO of parallel module 30
Between Inverter& Load
No of series module 4
Total module 120

Sub array 1
NO of parallel module 29 Location
No of series module 4
String
Total module 116
Between array& Inverter
sub array 1-2
Name Itrip
Fuse (P) 20 A
Between Inverter& Load
Isolator DC 500 A
IsolatorAC 500 A
Sub array 1
Protection & Disconnection Description Protection & Disconnection Device Guidelines
Fult Fuse 1.5*Isc<Itrip<2.4*ISC

Disconnection DC isolator 1.5*Isc<Itrip<2.4*ISC

Disconnection AC isolator 1.5*Isc<Itrip<2.4*ISC

Sub array 1
Protection & Disconnection Description Protection & Disconnection Device Guidelines
Fult Fuse 1.5*Isc<Itrip<2.4*ISC

Disconnection DC isolator 1.5*Isc<Itrip<2.4*ISC

Disconnection AC isolator 1.5*Isc<Itrip<2.4*ISC


Itripe
13.425
21.48
402.75
644.4

402.75
644.4

Itripe
13.425
21.48
389.325
622.92

389.325
622.92
Module Location
Pmax 310 String cable
Vmp 36 Array cable
Imp 8.33 AC cable
Voc 45.1
Isc 8.95

NO of parallel module 30
No of series module 4 Cable mark
Total module 120 N
Y
Y

Loaction Type Area (mm2)


string cable NYY 3.3
Array cable NYY 450
Ac Cable NYY 450
Span
Between module to where multiple string join toghether
Between Array and inverter& battery
Between inverter and load

NYY
‫مسی‬
‫ عایق‬PVC
Cover PVC
Protection size
Rated trip current of the fault current prodection
Rated trip current of the fault current prodection
Rated trip current of the fault current prodection
Name Quanity Price( $/Panel)
PV panel 236 217
Battery 100 235
Inverter 2 1000
Cabling&Wh meter&SOS prodection 5% total cost
Maintenance 1% total cost
Replacement Period Total cost for firest period($)
1 51212 Interest rate (%)
5 23500 inflation rate (%)
2 2000 life time of PV panel (year)
5% total cost 3835.6
1% total cost 805.476
Name
X ($) for inverter after 12 year

X ($) for Battery after 5 year


X ($) for Battery after 10 year
X ($) for Battery after 15 year
X ($) for Battery after20 year
Name Total cost ($) for all lifetem of system
5 PV panel 51212
7 Inverter 2942.79529065674
25 battery 98163.7379091228
Cabling&Wh meter&SOS prodection 3835.6
Maintenance 805.476
Cost($) Total system cost($) 156959.60919978
942.7953

21384.32
19459.11
17707.23
16113.07