Grounding Principle 3P-0036C
Grounding Principle 3P-0036C
Grounding Principle 3P-0036C
LIGHTNING ROD
ODU ANTENNA
COAX CONNECTOR
ODU GROUNDING
CABLE 10 sq.mm
COAX CABLE
ODU - IFU
Optional arrangement
SURGE ARRESTOR GROUNDED WALL GLAND PLATE
EQ UIPM EN T R OO M
COAX CONNECTOR COAX CONNECTOR
COAX CABLE
GROUNDING KIT
10 to 16 sq.mm RACK GROUNDING
CABLE 10 sq.mm
T
O
W UNIT GROUNDING
CABLE 6 sq.mm
E
R
OD U - IFU
WALL PLATE JUMP ER
S GROUNDING CABLE CA BLE
T 10 to 16 sq.mm
R EVOLUTION IFU
U DC POWER CONNECTION
C TNC- CONNECTOR ODU CABLE
T GR OUND IN G C ONNE CTION
U
MOUNTING HOLES
R
E
STATIO N M AIN
G RO UNDING BAR R ACK FRA ME OTHER RACKS
70 sq.m m
50 sq.mm Insula te d
TOW ER AND SITE EART HING RING
50 sq.mm
EA R TH IN G R O D S
Page 1(1)
Product Information
Description Sign. Date Rev. Document ID
Grounding Principle – Evolution Series Mje 2007-08-23 C 3P-0036C
1. Evolution ODU and IFU has integrated surge protection circuits at the entrance of coax connectors
2. The ODU must be grounded to tower structure
3. The coax cable ODU-IFU must be grounded to tower structure at the lowest point, on the vertical run in
tower, before the bending towards building.
4. Ensure that all groundings are connected to same network (equal potential)
5. Tower structure must be grounded to a quality site earthing network.
Nera standard installation practice is based on the above criteria and requires no extra protection.
Optional Protection:
Customers may have better knowledge of the status on actual site and may require additional
protection.
1. Surge arrestor at building cable entrance. (Extra set of cable connectors are needed)
2. The wall mounting plate for surge arrestor must be grounded outdoor, to the building / site earthing
network. The wall plate is generally the standard feed-through plate of the building. Hole dimension for
surge arrestor is found on data sheet.
Reference documentation:
Page 2(2)