1300 Edi Series-Electropack

z 1500/50 Hertz, can be wired 3 ways,


(auto or manual, (load share) or stand alone, (isochronous)
z 1800/60Hertz, can be wired 3 ways
(auto or manual, (load share) or stand alone, (isochronous)
z 1500/1800 Switchable, can be wired 2 ways
1500 or 1800, Isochronous Only

z 12 Volt and 24 Volt ECM’s available.


If you are not sure of the voltage and the markings have been removed
check PIN 35 to ground 1.4K Ohms – 12 volts / 2.8K Ohms – 24 volts.

@Perkins

Notes:
On start up for genset applications the ECM automatically determines which speed/load
signal ‘out of range’ (o.o.r.) fault management to use. This is dependant on the wiring
configuration it observes
Stand alone (isochronous) operation – APS & RPS inputs are both inactive.

Manual synchronised load sharing – APS input is active, RPS input is inactive.

Automatic synchronised load sharing – APS input is inactive, RPS input is active.

2 way protection is achieved by selecting 3 way protection and ‘normally open (plastic
tank)’ for the CLS type. No connection should then be made to the CLS input.

APS >>>>> PIN 8


RPS >>>>> PIN 30
See next page for adequate wiring driagrams

Page 8
Perkins Gen Set Power, TPD 1440E, issue 2

Wiring diagram - Stand alone (isochronous) running


1300 Series EDi
Terminal can be Interface harness
To starter and marked 87 or G
charging circuits (if used) Chassis harness connector
1
Stand alone (isochronous) Main
power rly
See note 5
ECM
operation Emergency 10 86 85 18 AWG 18 AWG
25 Power relay out
stop device
APS (PIN 8) & RPS (PIN 30) AWG 30 AMP 10 AWG 14 AWG
87 21 DC/DC Converter
30
14 AWG
inputs are both inactive Rating 30A
min
87a
14 AWG
22 (+) Feed

18 AWG
41 HSO (+) Feed
See note 4 See note 2 14 AWG
+ 23 HSO Ground feed
14 AWG
42 DPS O/P’s Ground feed
Battery 14 AWG
1 DC/DC Converter
- 10 AWG 14 AWG
2 Ground feed

12V or 24V 5 AMP 18 AWG


37 PRE Input
18 AWG
Attention Diagnostic 32 SCS Input (set coast)
+
1 switch
Battery 18 AWG 18 AWG
Note: Power supply for ECM must 34 STI Switch
- On/off switch
be taken directly from the battery, 5 AMP
16 AWG 18 AWG
not the starter motor terminal. 24 VIGN - IPR (+) Feed

Notes

1) Wire sizing:
10AWG (approx. 5mm 2 ) Main feed and return to battery
14AWG (approx. 2mm 2 ) ECM pin Nos 21.22.41.23.42.1.2
16AWG (approx. 1mm 2 ) Ignition and diagnostic socket supply
18AWG (approx. 0.8mm 2 ) All other circuits
16 AWG

18 Red
2) Main Power Relay 10 AMP AWG lamp
12V part no. 1688314C1 18 AWG
54 Oil water lamp output
(12V alternative part no’s. 2848A203)
Amber See note 6
24V part no. 2848A226 lamp 18 AWG
55 ENG Warn light output
0
3) Where shown, cables must be twisted together (360 per 25 mm and
screened to minimise noise effects. Connect screen at one end only. Diagnostic
4) connector
All fuses must comply with SAE J1284 and be located close to the CEBA
battery so as to protect the wiring. 10 AMP 16 AWG
5) Clear wire 18 AWG
All unused interface harness cables must be insulated. 16 ATA (+)
16 AWG Black wire 18 AWG (Data link J1708)
17 ATA (-)
6) Recommended rating for lamps is between 2 and 2.2 watts.
See note 3
W1361/1

6
95
96

Wiring diagram - Manual synchronised load sharing


6
To starter and Terminal can be
charging circuits marked 87 or G Interface harness (if used) Chassis harness connector

Manual synchronised load 1 Main See note 5


power rly ECM
sharing Emergency 10
stop device AWG
86 85 18 AWG 18 AWG
25 Power relay out
30 AMP
APS input (PIN 8) is active 30
87
10 AWG 14 AWG
14 AWG
21 DC/DC Converter
RPS input (PIN 30) is inactive Rating 30A 87a
22 (+) Feed
min 14 AWG
41 HSO (+) Feed
+ See note 4 See note 2 14 AWG
23 HSO Ground feed
Battery 14 AWG
42 DPS O/P’s Ground feed
14 AWG
- 1 DC/DC Converter
10 AWG 14 AWG
2 Ground feed
Attention 12V On/off switch
16 AWG 5 AMP 18 AWG
or
1 24 VIGN - IPR (+) Feed
24V
Note: Power supply for ECM must
be taken directly from the battery, Manual speed
+ 250
not the starter motor terminal. (demand) signal.
Battery Ohms
(working range 3 VBREF (5V) Sensor supply
Notes - 0.5 to 4.5 volts 2K
8 APS Input
into ECM pin 8). Ohms
1) Wire sizing: 11 VBREF GND Sensor supply
All resistors rated 250 See note 7
10AWG (approx. 5mm 2 ) Main feed and return to battery See
14AWG (approx. 2mm 2 ) ECM pin Nos 21.22.41.23.42.1.2 at 0.25 watts. Ohms note 3
16AWG (approx. 1mm 2 ) Ignition and diagnostic socket supply Diagnostic
18AWG (approx. 0.8mm 2 ) All other circuits
Perkins Gen Set Power, TPD 1440E, issue 2

switch
18 AWG 18 AWG
2) Main Power Relay 34 STI Switch
12V part no. 1688314C1 16 AWG
(12V alternative part no’s. 2848A203) 18
10 AMP Red lamp
AWG 18 AWG
24V part no. 2848A226 54 Oil water lamp output
0 See note 6
3) Where shown, cables must be twisted together (360 per 25 mm and Amber lamp
screened to minimise noise effects. Connect screen at one end only. 18 AWG
55 ENG Warn light output
4)
All fuses must comply with SAE J1284 and be located close to the Diagnostic
battery so as to protect the wiring.

1300 Series EDi


connector
5) CEBA
All unused interface harness cables must be insulated. 10 AMP 16 AWG
6) Recommended rating for lamps is between 2 and 2.2 watts. Clear wire 18 AWG
16 ATA (+)
16 AWG Black wire 18 AWG (Data link J1708)
0
7) Where shown, cables must be twisted together (360 per 25 mm a 17 ATA (-)
W1362/1

See note 3
Perkins Gen Set Power, TPD 1440E, issue 2

Wiring diagram - Automatic synchronised load sharing


1300 Series EDi
To starter and Terminal can be
charging circuits 1 marked 87 or G Interface harness (if used) Chassis harness connector
Main See note 5
power rly ECM
Emergency 10
Automatic synchronised load 86 85 18 AWG 18 AWG
stop device AWG 30 AMP 25 Power relay out
10 AWG 14 AWG
sharing
87 21 DC/DC Converter
30
Rating 30A 87a 14 AWG
22 (+) Feed
APS input (PIN 8) is inactive min 14 AWG
41 HSO (+) Feed

5 AMP
RPS input (PIN 30) is active See note 4 See note 2 14 AWG
23 HSO Ground feed
14 AWG
+ 42 DPS O/P’s Ground feed
14 AWG
Battery 1 DC/DC Converter
10 AWG 14 AWG
2 Ground feed
- 18 AWG
On/off switch 37 RPRE Input
Attention 5 AMP
16 AWG 18 AWG
1 12V or 24V 24 VIGN - IPR (+) Feed
Note: Power supply for ECM must
be taken directly from the battery, + Auto speed
not the starter motor terminal. (demand)
Battery signal 3 VBREF (5V) Sensor supply
Notes - 30 RPS Input
Working input
11 VBREF GND Sensor supply
1) Wire sizing: voltage into ECM See note 7
10AWG (approx. 5mm 2 ) Main feed and return to battery pin 30 is 0.5 to 4.5
14AWG (approx. 2mm 2 ) ECM pin Nos 21.22.41.23.42.1.2
16AWG (approx. 1mm 2 ) Ignition and diagnostic socket supply Diagnostic
18AWG (approx. 0.8mm 2 ) All other circuits switch
18 AWG 18 AWG
34 STI Switch
2) Main Power Relay
16 AWG

12V part no. 1688314C1 18


(12V alternative part no’s. 2848A203) Red
10 AMP AWG lamp 18 AWG
54 Oil water lamp output
24V part no. 2848A226
0 Amber See note 6
3) Where shown, cables must be twisted together (360 per 25 mm and lamp 18 AWG
screened to minimise noise effects. Connect screen at one end only. 55 ENG Warn light output
4)
All fuses must comply with SAE J1284 and be located close to the Diagnostic
battery so as to protect the wiring. connector
5) CEBA
All unused interface harness cables must be insulated. 10 AMP 16 AWG
Clear wire 18 AWG
6) Recommended rating for lamps is between 2 and 2.2 watts. 16 ATA (+)
16 AWG Black wire 18 AWG (Data link J1708)
17 ATA (-)
7) Where shown, cables must be twisted together (360 0 per 25 mm a
See note 3
W1363/1

6
97
98

Wiring diagram - 1500/1800 rev/min Switchable stand alone isochronous (non-load sharing)
6
To starter and Terminal can be
charging circuits marked 87 or G Interface harness (if used) Chassis harness connector
1 Main See note 5
power rly ECM
Emergency 10 86 85 18 AWG 18 AWG
stop device AWG 30 AMP 25 Power relay out
87
10 AWG 14 AWG
30 21 DC/DC Converter
Rating 30A 87a 14 AWG
22 (+) Feed

18 AWG
min 14 AWG
41 HSO (+) Feed
See note 4 See note 2 14 AWG
23 HSO Ground feed
+ 14 AWG
42 DPS O/P’s Ground feed
14 AWG
Battery 1 DC/DC Converter
10 AWG 14 AWG
- 2 Ground feed
5 AMP 18 AWG
Attention 37 PRE Input
12V or 24V J1
1 18 AWG
32 SCS Input (set coast)
Note: Power supply for ECM must See note 7 J2
18 AWG
be taken directly from the battery, + 31 RAS Input (resume/accel)
Diagnostic
not the starter motor terminal. Battery switch
18 AWG 18 AWG
- 34 STI Switch
Notes
On/off switch
16 AWG 5 AMP 18 AWG
1) Wire sizing:
24 VIGN - IPR (+) Feed
10AWG (approx. 5mm 2 ) Main feed and return to battery
14AWG (approx. 2mm 2 ) ECM pin Nos 21.22.41.23.42.1.2
16AWG (approx. 1mm 2 ) Ignition and diagnostic socket supply
Perkins Gen Set Power, TPD 1440E, issue 2

18AWG (approx. 0.8mm 2 ) All other circuits

2) Main Power Relay 16 AWG


12V part no. 1688314C1 18 Red
(12V alternative part no’s. 2848A203) 10 AMP AWG lamp 18 AWG
54 Oil water lamp output
24V part no. 2848A226
Amber See note 6
3) Where shown, cables must be twisted together (360 0 per 25 mm and lamp 18 AWG
screened to minimise noise effects. Connect screen at one end only. 55 ENG Warn light output
4)
All fuses must comply with SAE J1284 and be located close to the Diagnostic
battery so as to protect the wiring. connector

1300 Series EDi


CEBA
5)
All unused interface harness cables must be insulated. 10 AMP 16 AWG
Clear wire 18 AWG
6) Recommended rating for lamps is between 2 and 2.2 watts. 16 ATA (+)
16 AWG Black wire 18 AWG (Data link J1708)
17 ATA (-)
7) Genset speed settings. See note 3
W1364/1

For 1500 rpm connect link J1


For 1800 rpm connect link J2
Perkins Gen Set Power, TPD 1440E, issue 2

Wiring diagram - Gen Set options


1300 Series EDi
Emergency
Chassis harness connector
stop Vbal
Coolant
10 Coolant level switch
level

Request to
switch See note 2 PIN 10
+ +
shutdown
Battery Battery
See note 1
- -
On/off 10 AMP
Red 54 OWL Output (press/temp)

Standard operating mode circuit PIN 54

Additional notes

1) Maximum total current from OWL (54) output = 1 Amp (including lamp and Engine harness connector
’request to shutdown’ signal).

2) Coolant level sensor operation depends on EPN option selected Snooze


Single pin
’normally closed (metal tank)’ connector
’narmally open (plastic tank)’. 11 Snooze (run enable)

3) Customers must specify the relay, the wiring and appropriate fuses for 10 AMP
86 85
A
the radiator shutter control circuit. B 9 Radiator shutter
30
87 Two pin
87a connector
Radiator
shutter
Snooze (run enable) single pin connector: control relay
Packard part # Description See note 3
12065171...............Mating connector
12065249...............Secondary lock
12048159...............Male terminal 18 - 16 AWG
W1365

6
99