PAKISTAN (SEP) PROJECT Power System Stability • Definition ➢ The property of a power system which enables it to remain in a state of operating equilibrium under normal operating conditions and to regain an acceptable state of equilibrium following a disturbance • Traditionally the stability problem involves maintaining synchronous operation where: Power System Stability ➢ Power systems rely on synchronous machines for generation of power ➢ A necessary condition is that all synchronous machines remain in synchronism and “in-step” • We should always keep in mind the overall stability of the system: ➢ Solutions to problems of one category should not be at the expense of another. Power System Stability Classes Power System Stability – Voltage Stability • Ability of a power system to maintain acceptable voltages at all busses on the system under normal operating conditions and following disturbances • Voltage stability is characterized by a progressive and uncontrollable rise or fall in voltage. • Can be caused by the following: ➢ Increase in load ➢ Decrease in load ➢ Change in system conditions Power System Stability – Voltage Stability • Main factor causing voltage instability is the inability of the power system to maintain the required balance of reactive power and provide adequate voltage support throughout the system • Caused by large network disturbances (faults, switching, etc.) • In industrial systems, motor starts result in a drop in feeding voltage, which may not be sustainable, leading to high reactive power demand Power System Stability – Voltage Stability • Small disturbance voltage instability ➢ Caused by small network disturbances ➢ Increasing loads, leading to tap changer operation to increase local voltage ➢ This draws increasing reactive power and in turn lowers sending voltage ➢ Voltage collapse may result on heavily loaded networks Power System Stability – Frequency Stability • Ability to maintain a steady frequency within a nominal band following a disturbance resulting in a significant imbalance between generation and load • Larger systems have greater system inertia. The larger the inertia of the system, the smaller the change in frequency for the same change in generation/demand Power System Stability – Frequency Stability • Depends on the ability to restore balance between generation and load with the minimum loss of load. • Generally frequency stability problems are associated with inadequacies in equipment responses, and poor coordination of control (governors) and protection schemes (e.g load shedding schemes). Frequency Stability – Why is it Important? • Low frequency reduces the speed of AC motors – these are designed to operate at 60 HZ, and may overheat if run below this level for a sustained period. • Induced voltages are proportional to frequency, the output voltage of transformers is reduced with lower frequency. • Generator turbines will not be operating at their design speed. Frequency Stability – Why is it Important? • If the steam enters the turbine blades at the incorrect speed and angle, vibration and resonance may occur causing blade fatigue and life time reduction. • Fatigue and ageing is cumulative, all damage done adds up! Generator Turbine Governors • Variations in the load on a power system produce frequency variations. • These frequency changes are sometimes too rapid to be controlled by manual variations of generators alone, so the governor of each turbo alternator is given a “droop” characteristic which automatically varies generated power as the frequency changes. • A 4% droop setting is typical, which implies that a 4% change in frequency will open the governor from the no-load to the full-load position Frequency Stability – How? • Operator control for steady state generation dispatch • Automatic generation control systems (AGC) – static regulation of generation output, following small changes in system loading • Generator governor droop characteristics • Load curtailment – large loads are disconnected when a generation shortage is foreseen. Frequency Stability – How? • Automatic load shedding (to prevent the frequency dropping to a stage where under frequency protection of the generators would come into operation (typically 47.5 Hz): ➢ Time delayed frequency level triggered o Demand is sectioned into predetermined stages to be shed at different frequency levels. This method attempts to minimize the load shed, while discriminating between critical and non critical loads Frequency Stability – How? ➢ Df/dt triggered o Rate of change of frequency relays detect the rate of frequency fall, and trips load accordingly. This method is used on smaller power systems where quick response is required to arrest a rapid frequency decline Inherent System Stabilizer • Fortunately, a characteristic of all power systems is that the customer load reduces as frequency falls. • The lower system voltages lead to motor protection disconnecting load because of the higher current drawn Angle Stability – Small Signal Stability • Ability of power system to maintain stability during and following small disturbances • Small disturbances may set up a low frequency oscillation between generators on the network, and it is possible for this oscillation to be sustained or magnified due to the network configuration Angle Stability – Small Signal Stability • Instability that may result can be of two forms: • Aperiodic increase in rotor angle due to lack of sufficient synchronizing torque • Periodic rotor oscillations of increasing amplitude due to lack of sufficient damping torque • Generally occurs when two large areas or networks have “weak”/high impedance interconnections Sub Synchronous Resonance • A resonance condition may occur on a generator shaft between the electrical system and the mechanical system • The electrical system causes a natural vibration of the shaft, interacting with the turbine/boiler system Sub Synchronous Resonance • Altering the network impedance could lead to sub synchronous resonance. Network impedance may be changed by: ➢ Network disturbances ➢ Network reinforcement – series capacitors alter the series reactance of a network ➢ Static VAR compensators and their controllers ➢ HVDC convertor stations Sub Synchronous Resonance - Mitigation • The system impedance needs to change • Build more transmission circuits to “strengthen” the transmission system • Protection to remove generator, or to bypass series compensation • Install damping controllers ➢ Thyristor controlled series compensation ➢ HVDC Angle Stability – Transient Stability • A term used to denote large disturbance angle stability • Ability of a power system to maintain synchronism when subjected to a severe transient disturbance (e.g. three phase fault followed by the trip of a generator) Angle Stability – Transient Stability • The resulting system response involves large excursions of generator rotor angles and is influenced by the non-linear power-angle relationship • The power system should be designed and operated so as to be stable for a selected set of severe contingencies • Time window up to 5 seconds Angle Stability – Transient Stability • Transient stability is also called rotor stability or dynamic stability • Electromechanical phenomenon • All synchronous machines must remain in synchronism with each other • Motion of the generator is influenced by two forces ➢ Mechanical torque form prime mover (turbine) - Tm Angle Stability – Transient Stability ➢ Electrical torque developed by the output of the machine - Te • Accelerating torque is Ta = Tm – Te ➢ If Tm > Te, rotor accelerated to store the excess kinetic energy ➢ If Tm < Te, rotor will slow down as it draws the difference from stored kinetic energy • Post-disturbance operating point is usually different to pre-disturbance Causes of Transient Instability ➢ Short circuits ➢ Loss of generation ➢ Loss of load ➢ Starting of a large motor ➢ Switching operations (lines and shunt compensation) ➢ Sudden large change in load and generation Causes of Transient Instability • Short circuits • Loss of generation • Loss of load • Starting of a large motor • Switching operations (lines and shunt compensation) • Sudden large change in load and generation Consequences of Transient Instability • Pole slipping of synchronous generators – generator tripping • Power swings • Mal-operation of protection devices – distance protection • Interruption of critical loads • Low voltage conditions – motor contactor drop-offs • Damage to equipment • Blackouts and brownouts Why Do We Study Transient Stability? • In order to prevent system instability, the system must be designed to reduce the likelihood of instability • System protection must be set up to protect the system from undesirable operating conditions which may lead to instability • Critical fault clearing time • Fast load transferring • Load shedding Power Transfer Equation Normal Operating Angle • As a general rule in transmission systems, the maximum angle between major voltage control points (essentially power stations) should not exceed 30 degrees! • This means that an acceptable margin exists between the operating power level and Pmax. Normal Operating Angle • This margin is adequate to allow the system to accept system faults, which prevent transfer of power between locations, by ensuring that “post fault” power transfers can be high enough to restore a stable operating condition. Equal Area Criteria for Transient Stability • The equal area criteria states that the amount of energy required to slow the rotor to synchronous speed must be able to match the amount of energy added to accelerate it from synchronous speed. If this is not possible, instability will occur! • Area A1 – accelerating period (energy being absorbed by rotor) Equal Area Criteria for Transient Stability • Area A2 – decelerating period • Operating point rises above C until Area A2 = Area A1 • If Area2 Area1 by the time the curve reaches point F, the power system will be unstable Equal Area Criteria - Instability • This slide shows a three-phase fault at generator HV bus • Area A2 << Area A1, generator pulls out of step from system • Past point G – generator is operating as a motor, accelerating Equal Area Criteria - Instability • Area A3 >>> Area A4, out of step continues, protection will remove generator! Power System Stability – Conclusions • All types of system stability should be considered when planning a power system • Care must be taken to ensure that the “cure” for one type of stability does not result in another type of instability (e.g. SVC installed for voltage stability leading to sub synchronous resonance of a generator on the system)