EXCEL SIZING
Document Ref:
T-235-07-08
Pg . Rev. : 00 Date :
Load in KVA 20 KVA 14/04/2008
End Cell Voltage 1.75 V
Design Factor 1
Aging Factor 1
57.35
Load in KVA x 1000 x Power Factor
Load Current = = 57.35 A
No.of cells x ECV x Invertor Efficiency 57.35 A
Required Capacity = Load Current x K-Factor 100.3584 100.36 100.36 Ah
Ah Capacity considering
= Load current x K-Factor x Aging factor x Temperature Factor x Design Factor = 100.36 Ah
Various factors
100.36 100.36 Ah
Recommended Ah is 100 100.00 100 Ah
From the manufacturers catalogue,type F 100 P is recommended with 100 Ah at 1.75 ECV
From the manufacturers catalogue,type F 850 is recommended with 850 Ah at 1.75 ECV
APPROVED BY: PREPARED BY : Finolex urse
SINGLE LOAD SIZING
Ah Capacity considering
= Load current x K-Factor x Aging factor x Temperature Factor x Design Factor = 100.36 Ah
Various factors
Recommended Ah is 100 Ah
From the manufacturers catalogue,type F 100 P is recommended with 100 Ah at 1.75 ECV
*Temperature Factor and K-Factor cosidered as per manufacturer's catalogue
1 10.00 600
Period Load (Amps) Change in load Duration of load Time to end of section k-factor* Req. Capacity
Section :1
Required capacity[considering various factors] = Capacity x Temp.Factor x Life Factor x Design Factor = 138.88 Ah
Recommended Ah is 200 Ah
From the manufacturers catalogue,type F 200 P is recommended with 200 Ah at 1.75 ECV
1 60.00 15
2 12.00 60
Period Load (Amps) Change in load Duration of load Time to end of section k-factor* Req. Capacity
Section :1
.Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati
.All rights are reserved . No copying permitted. Unauthorized use prohibited
Section :2
From the manufacturers catalogue,type F 120 P is recommended with 120 Ah at 1.75 ECV
*Temperature Factor and K-Factors cosidered as per manufacturer's catalogue
APPROVED BY: PREPARED BY: SURYA PRAKASH
TITLE Document Ref:T-32-07-08
ARBL SIZING CALCULATION SHEET Pg. : 01 of : 01
SIZING AS PER IEEE 485 Pg . Rev. : 00 Date : 23/12/07
Req.
.All rights are reserved . No copying permitted. Unauthorized use prohibited
.Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati
Period Load (Amps) Change in load Duration of load Time to end of section k-factor* Capacity
Section :1
Req.
.All rights are reserved . No copying permitted. Unauthorized use prohibited
.Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati
Period Load (Amps) Change in load Duration of load Time to end of section k-factor* Capacity
Section :1
Ah Capacity considering
= Load current x K-Factor x Aging factor x Temperature Factor x Design Factor = 45.09 Ah
Various factors
Recommended Ah is 65 Ah
From the manufacturers catalogue,model 12AL 065 is recommended with 65 Ah at 1.75 ECV
*Temperature Factor and K-Factors cosidered as per manufacturer's catalogue