Battery Calculation Sheet Lepton

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 18

© ARBL

EXCEL SIZING

EXCEL SIZING is a program devoloped for sizing & selection of Amara


Raja Industrial Batteries,Viz Improved Powerstack and Quanta Series.Easy
sizing calculation in printable format is possible after the input of Load
details ,Temperature and Margins

Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati.


All rights are reserved . No copying permitted. Unauthorized use prohibited.
ECV? 1.75
BACK UP TIME IN
MINUTES? 50
UPS SIZING

Load in KVA 20 KVA


End Cell Voltage 1.75 V
Design Margin in % %
Aging Factor in % %
Inverter Efficiency in % 93 %
Power Factor 0.7
Backup time 60 min
DC Voltage 300 V
Temperature 27 oC

No of cells 150 No's


 
TITLE Document Ref:T-235-07-08
ARBL SIZING CALCULATION SHEET Pg. : 1 of : 1
SIZING AS PER IEEE 485 Pg . Rev. : 00 Date :14/04/2008

Document Ref:
T-235-07-08
Pg . Rev. : 00 Date :
Load in KVA 20 KVA 14/04/2008
End Cell Voltage 1.75 V
Design Factor 1
Aging Factor 1

Inverter Efficiency 0.93


Power Factor 0.7
Backup time 60 min
DC Voltage 300 V
Temperature 27 oC
Temp corr. Fac 1
K-factor 1.75
No of cells 150 No's
.All rights are reserved . No copying permitted. Unauthorized use prohibited
.Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati

57.35
Load in KVA x 1000 x Power Factor
Load Current = = 57.35 A
No.of cells x ECV x Invertor Efficiency 57.35 A
Required Capacity = Load Current x K-Factor 100.3584 100.36 100.36 Ah
Ah Capacity considering
= Load current x K-Factor x Aging factor x Temperature Factor x Design Factor = 100.36 Ah
Various factors
100.36 100.36 Ah
Recommended Ah is 100 100.00 100 Ah

From the manufacturers catalogue,type F 100 P is recommended with 100 Ah at 1.75 ECV
From the manufacturers catalogue,type F 850 is recommended with 850 Ah at 1.75 ECV
APPROVED BY: PREPARED BY : Finolex urse
SINGLE LOAD SIZING

Total Load in Amperes 10 A


End Cell Voltage 1.75 V
Design Margin in % 10 %
Aging Factor in % 25 %
Duration of Load 600 min
Temperature 25 oC
2 LOAD SIZING

End Cell Voltage 1.75 V


Design Margin in % 10 %
Aging Factor in % 52 %
Temperature 25 oC
Load in Amperes Duration(min)
1 60 15
2 12 60
3 LOAD SIZING

End Cell Voltage 1.85 V


Design Margin in % 10 %
Aging Factor in % 25 %
Temperature 30 oC
Please select Input A or B and check the Load
cycle for respective inputs .
INPUT A
Load in Amperes Duration(min)
Intermittant Load 315 15
Emergency Load 200 60
Continuos Load 38 600
INPUT B
Load in Amperes Duration(min)
Initial/1 Period
st
60 15

2nd Period Load 38 45

3rd Period Load 60 540


UPS SIZING FOR QUANTA

Load in KVA 10 KVA


End Cell Voltage 1.75 V
Design Margin in % %
Aging Factor in % %
Inverter Efficiency in % 96 %
Power Factor 0.9
Backup time 30 min
Total System Voltage 240 V
Temperature 45 oC

No of Cells 120 No's


TITLE Document Ref:T-235-07-08
 
ARBL SIZING CALCULATION SHEET Pg. : 1 of : 1
SIZING AS PER IEEE 485 Pg . Rev. : 00 Date : 14/04/2008

Load in KVA 20 KVA


End Cell Voltage 1.75 V
Design Factor 1
Ageing Factor 1

Inverter Efficiency 0.93


Power Factor 0.7
Backup time 60 min
DC Voltage 300 V
Temperature 27 oC
Temp corr. Factor * 1
K-factor* 1.75
No of cells 150 No's
.All rights are reserved . No copying permitted. Unauthorized use prohibited
.Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati

Load in KVA x 1000 x Power Factor


Load Current = = 57.35 Amps
No.of cells x ECV x Invertor Efficiency

Ah Capacity considering
= Load current x K-Factor x Aging factor x Temperature Factor x Design Factor = 100.36 Ah
Various factors

Recommended Ah is 100 Ah

From the manufacturers catalogue,type F 100 P is recommended with 100 Ah at 1.75 ECV
*Temperature Factor and K-Factor cosidered as per manufacturer's catalogue

APPROVED BY: PREPARED BY : Finolex urse


TITLE
  Document Ref: T-234
ARBL SIZING CALCULATION SHEET Pg. : 01 of : 01

SIZING AS PER IEEE 485 Pg . Rev. : 00 Date 1-Jan-08

End Cell Voltage 1.75


Design Factor 1.1
Ageing Factor 1.25
Temperature 25 oC
Temp corr. Fac* 1.01
.Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati

Period Total Amperes Duration (min)


.All rights are reserved . No copying permitted. Unauthorized use prohibited

1 10.00 600

Period Load (Amps) Change in load Duration of load Time to end of section k-factor* Req. Capacity

Section :1

1 A1= 10.00 A1-0 = 10.00 M1= 600 T1 = M1 = 600 10 100.00

Calculated capacity = 100.00 Ah

Required capacity[considering various factors] = Capacity x Temp.Factor x Life Factor x Design Factor = 138.88 Ah

Recommended Ah is 200 Ah

From the manufacturers catalogue,type F 200 P is recommended with 200 Ah at 1.75 ECV

*Temperature Factor and K-Factor cosidered as per manufacturer's catalogue

APPROVED BY: PREPARED BY: Prathima


TITLE
  Document Ref: T-213-08
ARBL SIZING CALCULATION SHEET Pg. : 01 of : 01

SIZING AS PER IEEE 485 Pg . Rev. : 00 Date : 28/02/08

End Cell Voltage 1.75


Design Factor 1.1
Ageing Factor 1.52
Temperature 25 oC
Temp corr. Fac* 1.01

Period Total Amperes Duration (min)

1 60.00 15
2 12.00 60

Period Load (Amps) Change in load Duration of load Time to end of section k-factor* Req. Capacity

Section :1
.Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati
.All rights are reserved . No copying permitted. Unauthorized use prohibited

1 A1= 60.00 A1-0 = 60.00 M1= 15 T1 = M1 = 15 1.00 60.00


60.00

Section :2

1 A1= 60.00 A1-0 = 60.00 M1= 15 T1 = M1+M2 = 75 2.01 120.60


2 A2= 12.00 A2-A1= -48.00 M2= 60 T2 = M2 = 60 1.75 -84.00
36.60

Calculated capacity [select max. size] = 60.00 Ah


Required capacity[considering various factors] = Capacity x Temp.Factor x Life Factor x Design Factor = 101.32 Ah

From the manufacturers catalogue,type F 120 P is recommended with 120 Ah at 1.75 ECV
*Temperature Factor and K-Factors cosidered as per manufacturer's catalogue
APPROVED BY: PREPARED BY: SURYA PRAKASH
TITLE Document Ref:T-32-07-08
 
ARBL SIZING CALCULATION SHEET Pg. : 01 of : 01
SIZING AS PER IEEE 485 Pg . Rev. : 00 Date : 23/12/07

End Cell Voltage 1.85


Design Factor 1.1
Ageing Factor 1.25
Temperature 30 oC
Temp corr. Factor* 1

A Continuos Load = 38 Amps


B Emergency Load = 200 Amps
C Intermittent Load = 315 Amps

Period Total Amperes Duration (min)


1 A1=A+B+C = 553 15
2 A2 = A+B = 238 45
3 A 3 =A = 38 540

Req.
.All rights are reserved . No copying permitted. Unauthorized use prohibited
.Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati

Period Load (Amps) Change in load Duration of load Time to end of section k-factor* Capacity

Section :1

1 A1= 553 A1-0 = 553 M1= 15 T1 = M1 = 15 1.16 641.48


641.48
Section :2

1 A1= 553 A1-0 = 553 M1= 15 T1 = M1+M2 = 60 1.90 1050.70


2 A2= 238 A2-A1= -315 M2= 45 T2 = M2 = 45 1.68 -529.20
521.50
Section : 3
1 A1= 553 A1-0 = 553 M1= 15 T1 = M1+M2+M3 = 600 11.02 6094.06
2 A2= 238 A2-A1= -315 M2= 45 T2 = M2+M3 = 585 10.78 -3394.91
2 A3= 38 A3-A2= -200 M3= 540 T3 = M3 = 540 10.05 -2010.00
689.15
Calculated capacity [select max. size] = 689.15 Ah
Required capacity [considering various factors] = Capacity * Temp.Factor * Life Factor * Design Factor = 947.58 Ah
From the manufacturers catalogue,type F 1020 P is recommended with 1020 Ah at 1.75 ECV
*Temperature Factor and K-Factors cosidered as per manufacturer's catalogue
APPROVED BY: PREPARED BY: Halim sha
TITLE Document Ref:T-32-07-08
 
ARBL SIZING CALCULATION SHEET Pg. : 01 of : 01
SIZING AS PER IEEE 485 Pg . Rev. : 00 Date : 23/12/07

End Cell Voltage 1.85


Design Factor 1.1
Ageing Factor 1.25
Temperature 30 oC
Temp corr. Fac* 1

Period Total Amperes Duration (min)


1 A1 = 60 15
2 A2 = 38 45
3 A3 = 60 540

Req.
.All rights are reserved . No copying permitted. Unauthorized use prohibited
.Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati

Period Load (Amps) Change in load Duration of load Time to end of section k-factor* Capacity

Section :1

1 A1= 60 A1-0 = 60 M1= 15 T1 = M1 = 15 1.16 69.60


69.60
Section :2

1 A1= 60 A1-0 = 60 M1= 15 T1 = M1+M2 = 60 1.90 114.00


2 A2= 38 A2-A1= -22 M2= 45 T2 = M2 = 45 1.68 -36.96
77.04
Section : 3
1 A1= 60 A1-0 = 60 M1= 15 T1 = M1+M2+M3 = 600 11.02 661.20
2 A2= 38 A2-A1= -22 M2= 45 T2 = M2+M3 = 585 10.78 -237.11
2 A3= 60 A3-A2= 22 M3= 540 T3 = M3 = 540 10.05 221.10
645.20
Calculated capacity [select max. size] = 645.20 Ah
Required capacity[considering various factor] = Capacity x Temp.Factor x Life Factor x Design Factor = 887.14 Ah
From the manufacturers catalogue,type F 900 P is recommended with 900 Ah at 1.75 ECV
*Temperature Factor and K-Factors cosidered as per manufacturer's catalogue
APPROVED BY: PREPARED BY: Halim sha
 
TITLE Document Ref:0
ARBL SIZING CALCULATION SHEET Pg. : 1 of : 1
SIZING AS PER IEEE 485 Pg . Rev. : 00 Date : 23-Jan-20

Load in KVA 10 KVA


End Cell Voltage 1.75 V
Design Factor 1
Aging Factor 1
Inverter Efficiency 0.96
Power Factor 0.9
Backup time 30 min
DC Voltage 240 V
Temperature 45 oC
Temp corr. Factor* 1
K-factor* 1.01
No of cells 120 No's
.All rights are reserved . No copying permitted. Unauthorized use prohibited
.Proprietary Material of M/s. AMARA RAJA GROUP OF COMPANIES, Thirupati

Load in KVA x 1000 x Power Factor


Load Current = = 44.64 Amps
No.of cells x ECV x Invertor Efficiency

Ah Capacity considering
= Load current x K-Factor x Aging factor x Temperature Factor x Design Factor = 45.09 Ah
Various factors

Recommended Ah is 65 Ah

From the manufacturers catalogue,model 12AL 065 is recommended with 65 Ah at 1.75 ECV
*Temperature Factor and K-Factors cosidered as per manufacturer's catalogue

APPROVED BY: PREPARED BY : 0