Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/258655121

On-site PD Diagnostics, FRA and Moisture Measurement for Power


Transformers

Article  in  IEEJ Transactions on Power and Energy · January 2012


DOI: 10.1541/ieejpes.132.134

CITATIONS READS

0 112

3 authors, including:

Stefan Tenbohlen
Universität Stuttgart
364 PUBLICATIONS   3,301 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Failure Analysis View project

Partial Discharge Measurement View project

All content following this page was uploaded by Stefan Tenbohlen on 14 July 2015.

The user has requested enhancement of the downloaded file.


電気学会論文誌 B(電力・エネルギー部門誌)
IEEJ Transactions on Power and Energy 2B11
Vol.132 No.2 pp.1–5 DOI: 10.1541/ieejpes.132.1

Special Issue Review

On-site PD Diagnostics, FRA and Moisture Measurement


for Power Transformers
Stefan Tenbohlen∗a) Non-member, Maximilian Heindl∗ Non-member
Mark Jovalekic∗ Non-member
(Manuscript received Nov. 11, 2011)

The paper presents three methods for condition assessment of power transformers which can be applied on-site. A
combination of UHF and acoustic partial discharge (PD) measurement methods enables to detect PD in power trans-
formers and to improve interpretation and localisation of their sources. Frequency response measurements are a widely
applied technique for power transformer winding deformation detection. Dielectric response methods deliver results
about the moisture condition of a transformer.

Keywords: power transformer, on-site condition assessment, partial discharge, frequency response analysis, dielectric response
measurement

the ageing condition and decide further actions. Moisture as-


1. Introduction
sessment can be done in various ways. For on-site off-line
The reliability of electrical energy networks depends on the measurements dielectric spectroscopy is a viable tool. Mois-
quality and availability of their components such as power ture has an effect on the dielectric response of the insulating
transformers. Due to the increasing age of the transformer system. Among different methods frequency domain spec-
population condition assessment and thus on-site diagnostics troscopy (FDS) will be presented in detail.
are important issues to secure a reliable operation of the elec-
2. Partial Discharge Diagnostics
trical power system.
Localised internal insulation failures can lead to catas- 2.1 Measuring Technique The electrical PD-mea-
trophic breakdown. To reduce such risk power transformers surement set-up according to IEC 60270 usually has sensi-
have to pass a range of factory tests including one for partial tivity limitations for on site/on-line measurements because of
discharge (PD) activity before acceptance and commission- the noise level in field. The so called “UHF PD measuring
ing. On-site PD measurements are often restricted by high method” (UHF: Ultra High Frequency) is based on the facts
site interference. Hence the electrical PD-measurement set- that PD under oil are very fast electrical processes and radiate
up according to IEC 60270 usually has sensitivity limitations electromagnetic waves with frequencies up to the ultrahigh
for on-site/on-line measurements. In contrast the sensitiv- range (UHF: 300–3000 MHz). Due to the moderately attenu-
ity of UHF PD measurements is sufficient and normally not ated propagation of UHF waves inside the transformer tank,
affected by external disturbances. Especially in noisy sur- the sensitivity to electromagnetic wave detection is good (1) (2) .
rounding it is a very helpful method to support other PD mea- UHF sensors can be inserted into the transformer during full
surement techniques for example dissolved gas analysis and operation through the oil filling valve. As a result of shielding
acoustic localisation of PD. characteristics of the transformer tank against external elec-
Frequency Response Analysis compares measured trans- tromagnetic waves, normally a clear decision can be made
fer functions of power transformers. Deviations between concerning the PD activity of the test object.
frequency response curves indicate electrical or mechanical When electrical or UHF PD measurements confirm PD ac-
damages of windings. Interpretation of the deviations be- tivity, a three dimensional localisation of PD sources is the
tween transfer funtions is not a standardized process and next step for risk evaluation of PD phenomena. This can
promises to be more reliable and meaningful if skilled knowl- be performed based on arrival time measurement. Because
edge about the transformer design is incorporated. piezo-electric acoustic sensors that can easily be mounted on
Another factor is the assessment of the transformer’s age- transformer tanks, the acoustic measurements remains attrac-
ing condition. Ageing depends directly on operating temper- tive for localisation purposes. However, acoustic sensors are
ature and time. The limiting factor is degradation of paper normally more sensitive to external disturbances than to the
insulation. This goes hand in hand with moisture production internal PD originated sound waves. They are also affected
from the ageing process. So by knowing the moisture con- by distortion within the tank from the winding core and sup-
tent in the solid insulation, it is possible to get an idea of port structures in the transit path which influences can partly
a) Correspondence to: stefan.tenbohlen@ieh.uni-stuttgart.de be eliminated with appropriate signal processing afterwards.
∗ The compromise is therefore, to use a combination of the two
University of Stuttgart
Pfaffenwaldring 47, 70569 Stuttgart, Germany methods, using sensitive UHF signals to provide triggering


c 2012 The Institute of Electrical Engineers of Japan. 1
On-site PD Diagnostics, FRA and Moisture Measurement for Power Transformers(Stefan Tenbohlen et al.)

and by using averaging of acoustic signals for de-noising. By inaccuracy is thereby within the range of approx. 40 cm on
using averaged signals (averaging in time domain), the acous- all space axes. This inaccuracy is caused by using different
tic PD pulses remain constructively overlapped whereas the combinations of time of flight differences and different local-
white background noise is averaged to zero. isation methods. Thereby the time of flight differences were
2.2 Case Study Because of increasing gas-in-oil val- measured with six sensors which are the three UHF sensors
ues, a 333 MVA, 400/220 kV single-phase autotransformer (UHF 1–UHF 3) and the three acoustic sensors (A2, A5, A6)
was tested on-site and on-line for PD. The high noise level placed near to the PD source.
at site strongly disturbed the conventional PD measurements After transportation of the transformer to the manufacturer
made according to IEC 60270 at frequencies lower than the localisation result was confirmed by an IEC triggered
1 MHz. Source of noise was in that case the 400 kV bus bar acoustic measurement in a shielded test area and the trans-
above the transformer producing audible corona discharge. former was detanked for repair. The visual inspection of the
Consequently, UHF PD measurements for PD detection in active parts at the tap changer confirmed the localisation re-
combination with acoustic measurements for PD localisation sults. After repair procedure the transformer passed the ac-
were performed in order to get reliable results. In this case the ceptance test without any indication of PD activity and was
transformer possessed three oil filling valves and three identi- put back into service.
cal UHF Sensors were installed. Figure 2 shows the positions
3. Frequency Response Analysis
of the UHF sensors (UHF 1–UHF 3) and the acoustic sensors
(A1–A6). 3.1 Motivation Frequency response measurements
At nominal voltage, UHF signals from internal sources are a widely applied technique for power transformer wind-
were detectable with all three sensors. The travelling speed ing failure detection after lightning stroke, short circuit or
of the electromagnetic waves is approximately two-thirds of transport and are considered to be usually more sensitive than
speed of light inside the transformer. Thus for localisation, the conventional short-circuit voltage measurements. De-
UHF signals are detected almost the same time PDs occur. viations between frequency responses indicate mechanical
Conversely, the speed of acoustic waves is 1400 m/s, produc- and/or electrical changes of the active part of a transformer.
ing transit times within the range of milliseconds. With at The basic principle of FRA is the investigation of differ-
least three acoustic sensors and corresponding time of flights, ences between frequency responses. The electrical transfer
it is possible to calculate the intersection of the spheres and behaviour in the frequency range up to 2 MHz, in other words
thus to determine the PD location. It must be assumed that the frequency response, is identified by numerous charac-
the acoustic waves travel directly in the line of sight from the teristic resonances, which depend on the stray capacitances
PD source through the oil and through the steal tank to the and inductances that are determined by the geometry and ar-
sensor without any reflections. But furthermore the localisa- rangement of active part and transformer tank. The trans-
tion process has also to deal with acoustic waves travelling fer function T F( f ) as a state variable displays the geometric
faster through the tank wall than through the oil. The time structural condition like a finger print. Known damage types,
of flights of the acoustic signals can be computed objectively e.g. deformations, have an effect on the transfer functions like
with the help of the Hinkley criterion (3) . It is based on the sig- shifting, creating or disappearing of resonances. However,
nal energy of the measured signal and results in an absolute interpretation of particular differences between two transfer
minimum for the signal starting point. function curves is the missing link between failure identi-
As illustrated in Fig. 1, the supposed position of the PD fication, measurement and assessment of the transformer (4) .
source is in the vicinity of the tap changer. Geometrical Figure 3 shows the frequency ranges with their corresponding
winding parts beeing sensitive towards mechanical changes
as identified by Cigre WG A2.26. For smaller power trans-
formers, the frequency ranges of interest tend to be shifted
towards higher frequency.
3.2 Measuring Technique The two most commonly
used test types for transfer function measurement of power
transformers are the so-called end-to-end transfer function
Fig. 1. UHF PD Probe for standard oil filling valve measurement T F EE ( f ) and the capacitive inter-winding mea-
surement T F CI ( f ), see also Ref. (5). Figure 4 shows the as-
sociated connection diagrams. The obtained transfer function

Fig. 2. Positions of UHF Sensors, acoustic sensors and Fig. 3. Frequency ranges with known sensitivity to-
the PD source at 333 MVA single phase autotransformer wards changes of the winding geometry (5)

2 IEEJ Trans. PE, Vol.132, No.2, 2012


On-site PD Diagnostics, FRA and Moisture Measurement for Power Transformers(Stefan Tenbohlen et al.)

of a measured phase then is: explained by unbalances of the ground capacitances and the
practical realization of the winding lead outs.
U 2,EE
T F EE ( f ) = · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · (1) FB3 and the lower part of FB4 reflect the most impor-
U1 tant part of the frequency response. Deviations occuring in
For the second measurement type, the transfer function is: this frequency range indicate mechical changes such as bulk
winding movement or buckling of windings (6) .
U 2,CI
T F CI ( f ) = . · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · (2) 4. Moisture Measurement
U1
3.3 Case Study Fig. 5 shows a representative case 4.1 Motivation Moisture is a critical parameter of the
of transfer functions of all phases measured at a 200 MVA insulating system. This has several reasons. One is that the
110 kV/65 kV three phase power transformer. dielectric strength of insulating liquid is strongly affected by
There are characteristic frequency bands which reflect dif- moisture. The risk of partial discharges and the bubble effect
ferent electrical properties of the transformer. The frequency (evaporation of water vapour under high load conditions) is
bands FB1 and FB2 are related to the core magnetizing in- higher. Water is also hazardous to the cellulose based insula-
ductance and winding series capacitance, while FB3 and FB4 tion as it accelerates further ageing. So by knowing the water
are related to the leakage inductances of the windings and the content of a transformer’s solid insulation it is possible to get
capacitances of adjacent windings. The high frequency part an idea of its ageing condition and thus plan further actions.
of FB4 up to 2 MHz represents smaller details of the active 4.2 Sources of Water in Transformers The first
part geometry together with the winding leads. Additionally, source of water in the lifetime of a transformer can be from
the bushing capacitances influence the high frequency part of improper drying in the factory. Another can be moisture
the transfer functions. ingress from the atmosphere. This can happen for free-
Differences between transfer functions of differents phases breathing transformers if the air-drying system is poorly
are greater in FB1, FB2 and in the upper part of FB4. For maintained. Another source is during repair in the field where
FB1 and FB2 the differences can be explained by the unbal- there are no possibilities of dry storage. The last, if not
ance of the core (magnetic circuit) and remanence of the core. the most important one is moisture originating from ageing
Mismatching between phases in the upper part of FB4 can be of paper and pressboard. This means, that even a perfectly
serviced transformer will become wet with increasing age.
There are studies which show that the ageing accelerates with
higher moisture content and at the same time water is pro-
duced due to ageing (see Fig. 6) (7) . One can conclude that
lifetime estimations of cellulosic insulating systems do not
only depend on operating temperature but also on moisture
content of solid insulation. This is the reason why water
assessment in combination with other diagnostic techniques
can help finding the health condition of a transformer.
4.3 Methods of Moisture Assessment The aim is to
know the water content of the critical solid insulation which
is the thin paper. It is nearly impossible to measure this di-
rectly as the paper cannot be sampled for measurement with-
out destroying it. Here only indirect methods can help. Ba-
sically there are two groups of techniques: first are the mois-
ture equilibrium charts and second are the dielectric response
Fig. 4. Connection schemes for measurements of end-
to-end (EE) and capacitive inter-winding (CI) frequency measurements. The equilibrium diagrams use the fact that
response the moisture in the paper-oil system reaches an equilibrium

Fig. 5. Characteristic frequency bands of measured end-


to-end frequency responses of a three phase power trans- Fig. 6. Life expectance of oil impregnated paper de-
former pending on temperature and water content (7)

3 IEEJ Trans. PE, Vol.132, No.2, 2012


On-site PD Diagnostics, FRA and Moisture Measurement for Power Transformers(Stefan Tenbohlen et al.)

made concerning the PD activity of the test object. Acoustic


PD measurements should not be used exclusively and ben-
efit from a sensitive trigger method as e.g. UHF for double
checking and noise suppression.
FRA is a helpful diagnostic tool when clearing up trans-
former failures after short circuit events or drop out after
lightning strokes. Time-based comparison of frequency re-
sponses of a certain transformer unit promises most reliable
assessments, as design-based or type-based comparison are
always critical due to natural unbalances between phases in
design and inaccuracies of the production process.
Fig. 7. Interpretation of the dissipation factor vs. fre- Dielectric response methods deliver reliable results about
quency of an oil-paper-insulation (9) the moisture condition of a transformer. They can be ap-
plied on-site even under conditions where the equilibrium
state cannot be guaranteed. Disturbances can be reduced by
and will be distributed between oil and paper. So by knowing proper connections and guarding.
the temperature and water content of the oil, one can esti-
mate the water content in the solid. If the thermal and kinetic
equilibrium cannot be guaranteed, these charts can give erro- References
neous estimations additionally to sources of error during oil
sampling and measurement in the laboratory (8) . (1) S. Coenen, S. Tenbohlen, S.M. Markalous, and S. Strehl: “Sensitivity of UHF
PD Measurements in Power Transformers”, IEEE Trans. Dielect. Elect. In-
4.4 Dielectric Response Methods Dielectric diag- sulation, Vol.15, No.6, pp.1553–1558
nostic methods deduce moisture in paper or pressboard from (2) S. Coenen, S. Tenbohlen, S.M. Markalous, and T. Strehl: “Fundamental char-
dielectric properties like return voltage, polarisation and de- acteristics of UHF PD sensors and the radiation behaviour of PD sources in
power transformer”, Proc. of 17th ISH, No: C-26, Cape Town, South Africa
polarisation currents and dissipation factor. Primary moti-
(2009)
vations for the development of dielectric response methods (3) S.M. Markalous, S. Tenbohlen, and K. Feser: “Detection and Location of
were the lack of methods for on-site moisture assessment in Partial Discharges in Power Transformers using acoustic and electromagnetic
power transformers. signals”, IEEE Trans. Dielect. Elect. Insulation, Vol.15, No.6, pp.1576–1583
(4) M. Heindl, S. Tenbohlen, et al.: “Algorithmic Determination of Pole-Zero
4.5 Measuring Technique A time domain current Representations of Power Transformers‘ Transfer Function for Interpretation
measurement records the charging and discharging currents of FRA Data”, Proc. of the 16th International Symposium on High Voltage
of the insulation. They are usually called Polarisation and Engineering, paper No.D-26, Cape Town, South Africa, 24 to 28 August
(5) P. Picher, J. Lapworth, T. Noonan, J. Christian, et al.: “Mechanical Condition
Depolarisation Currents (PDC). Frequency domain measure-
Assessment of Transformer Windings using Frequency Response Analysis”,
ments (FDS) are derived from dissipation factor measure- Cigre Report 342 (2008)
ments, yet with a frequency range particularly enhanced for (6) A. Kraetge, M. Krüger, J.L. Velásquez, H. Viljoen, and A. Dierks: “Aspects
low frequencies. Figure 7 shows the typical s-shaped curve of the Practical Application of Sweep Frequency Response Analysis (SFRA)
on Power Transformers”, Cigré 6th Southern Africa Regional Conference,
of the dissipation factor via frequency and the scientifically Paper P504 (2009)
agreed interpretation scheme for a power transformer. (7) L.E. Lundgaard, W. Hansen, D. Linhjell, and T.J. Painter: “Aging of oil-
The transformer under investigation has to be off-line. The impregnated paper in power transformers”, IEEE Trans. Power Delivery,
dielectric response of the oil-paper system should be mea- Vol.19, No.1, pp.230–239 (2004-1)
(8) M. Koch, S. Tenbohlen, and T. Stirl: “Diagnostic Application of Moisture
sured between HV and LV winding. On one side a variable Equilibrium for Power Transformers”, IEEE Trans. Power Delivery, Vol.25,
frequency AC voltage source is connected and on the other No.4, pp.2574–2581 (2010-10)
winding the resulting current is recorded. With this infor- (9) M. Koch, M. Krüger, and S. Tenbohlen: “Comparing Various Moisture De-
termination Methods for Power Transformers”, Cigre South Africa Regional
mation the loss factor can be calculated. These currents are Conference, Cape Town, South Africa (2009)
very low and can easily be disturbed in the field. One protec-
tive means on-site is guarding, which avoids surface currents
over the bushings from LV to HV. These fault currents would Stefan Tenbohlen (Non-member) received the Diploma and Dr.-Ing.
impede the measurement of the correct dielectric response degrees from the Technical University of Aachen,
and thus make the water assessment difficult. By combining Germany, in 1992 and 1997, respectively. 1997
PDC and FDS measurement times can be reduced even fur- he joined ALSTOM, Mönchen¬gladbach, Germany,
where he was responsible for the development and
ther and the moisture assessment process is completed after
design of power transformers. 2004 he was appointed
3 to 6 hours. to a professorship and head of the Institute of Power
Transmission and High Voltage Technology of the
5. Conclusion
University of Stuttgart, Germany. In this position his
PD-measurement set-up according to IEC 60270 usually main research fields are electric power transmission
and electromagnetic compatibility (EMC). Prof. Tenbohlen holds several
has sensitivity limitations for on-site/on-line measurements
patents and published more than 200 papers. He is member of the IEEE,
because of the high noise level in field. UHF PD mea- CIGRE and VDE ETG. He is convener of CIGRE WG A2.37 (Transformer
surements can easily support PD measurements even on-line Reliability Survey) and member of several other working groups.
and are mostly sensitive enough against PD. As a result of
shielding characteristics of the transformer tank against exter-
nal electromagnetic waves, normally a clear decision can be

4 IEEJ Trans. PE, Vol.132, No.2, 2012


On-site PD Diagnostics, FRA and Moisture Measurement for Power Transformers(Stefan Tenbohlen et al.)

Maximilian Heindl (Non-member) received the Diploma degree in Mark Jovalekic (Non-member) received his diploma degree in elec-
electrical engineering and information technology trical engineering and information technology from
from the University of Stuttgart, Germany, in 2007 University of Stuttgart, Germany in 2008. Since then
and joined the Institute of Power Transmission and he joined the Institute of Power Transmission and
High Voltage Technology, where he currently is doc- High Voltage Technology as research assistant. His
toral research assistant. The focus of his work and field of research is the oil-paper insulation system,
research lies on frequency response analysis, trans- especially with focus on natural ester fluids. This in-
former transient interaction and transformer related cludes the fundamental characteristics and ageing be-
modeling of both high and low frequency problem haviour of these dielectric liquids as well as diagno-
types. Mr. Heindl is member of CIGRE and VDE sis of power transformers by means of dissolved gas
ETG and published several papers. analysis and moisture assessment. Mark Jovalekic is member of VDE ETG
and published several papers.

5 IEEJ Trans. PE, Vol.132, No.2, 2012

View publication stats

You might also like