Professional Documents
Culture Documents
On-Site PD Diagnostics, FRA and Moisture Measurement For Power Transformers
On-Site PD Diagnostics, FRA and Moisture Measurement For Power Transformers
net/publication/258655121
CITATIONS READS
0 112
3 authors, including:
Stefan Tenbohlen
Universität Stuttgart
364 PUBLICATIONS 3,301 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Stefan Tenbohlen on 14 July 2015.
The paper presents three methods for condition assessment of power transformers which can be applied on-site. A
combination of UHF and acoustic partial discharge (PD) measurement methods enables to detect PD in power trans-
formers and to improve interpretation and localisation of their sources. Frequency response measurements are a widely
applied technique for power transformer winding deformation detection. Dielectric response methods deliver results
about the moisture condition of a transformer.
Keywords: power transformer, on-site condition assessment, partial discharge, frequency response analysis, dielectric response
measurement
c 2012 The Institute of Electrical Engineers of Japan. 1
On-site PD Diagnostics, FRA and Moisture Measurement for Power Transformers(Stefan Tenbohlen et al.)
and by using averaging of acoustic signals for de-noising. By inaccuracy is thereby within the range of approx. 40 cm on
using averaged signals (averaging in time domain), the acous- all space axes. This inaccuracy is caused by using different
tic PD pulses remain constructively overlapped whereas the combinations of time of flight differences and different local-
white background noise is averaged to zero. isation methods. Thereby the time of flight differences were
2.2 Case Study Because of increasing gas-in-oil val- measured with six sensors which are the three UHF sensors
ues, a 333 MVA, 400/220 kV single-phase autotransformer (UHF 1–UHF 3) and the three acoustic sensors (A2, A5, A6)
was tested on-site and on-line for PD. The high noise level placed near to the PD source.
at site strongly disturbed the conventional PD measurements After transportation of the transformer to the manufacturer
made according to IEC 60270 at frequencies lower than the localisation result was confirmed by an IEC triggered
1 MHz. Source of noise was in that case the 400 kV bus bar acoustic measurement in a shielded test area and the trans-
above the transformer producing audible corona discharge. former was detanked for repair. The visual inspection of the
Consequently, UHF PD measurements for PD detection in active parts at the tap changer confirmed the localisation re-
combination with acoustic measurements for PD localisation sults. After repair procedure the transformer passed the ac-
were performed in order to get reliable results. In this case the ceptance test without any indication of PD activity and was
transformer possessed three oil filling valves and three identi- put back into service.
cal UHF Sensors were installed. Figure 2 shows the positions
3. Frequency Response Analysis
of the UHF sensors (UHF 1–UHF 3) and the acoustic sensors
(A1–A6). 3.1 Motivation Frequency response measurements
At nominal voltage, UHF signals from internal sources are a widely applied technique for power transformer wind-
were detectable with all three sensors. The travelling speed ing failure detection after lightning stroke, short circuit or
of the electromagnetic waves is approximately two-thirds of transport and are considered to be usually more sensitive than
speed of light inside the transformer. Thus for localisation, the conventional short-circuit voltage measurements. De-
UHF signals are detected almost the same time PDs occur. viations between frequency responses indicate mechanical
Conversely, the speed of acoustic waves is 1400 m/s, produc- and/or electrical changes of the active part of a transformer.
ing transit times within the range of milliseconds. With at The basic principle of FRA is the investigation of differ-
least three acoustic sensors and corresponding time of flights, ences between frequency responses. The electrical transfer
it is possible to calculate the intersection of the spheres and behaviour in the frequency range up to 2 MHz, in other words
thus to determine the PD location. It must be assumed that the frequency response, is identified by numerous charac-
the acoustic waves travel directly in the line of sight from the teristic resonances, which depend on the stray capacitances
PD source through the oil and through the steal tank to the and inductances that are determined by the geometry and ar-
sensor without any reflections. But furthermore the localisa- rangement of active part and transformer tank. The trans-
tion process has also to deal with acoustic waves travelling fer function T F( f ) as a state variable displays the geometric
faster through the tank wall than through the oil. The time structural condition like a finger print. Known damage types,
of flights of the acoustic signals can be computed objectively e.g. deformations, have an effect on the transfer functions like
with the help of the Hinkley criterion (3) . It is based on the sig- shifting, creating or disappearing of resonances. However,
nal energy of the measured signal and results in an absolute interpretation of particular differences between two transfer
minimum for the signal starting point. function curves is the missing link between failure identi-
As illustrated in Fig. 1, the supposed position of the PD fication, measurement and assessment of the transformer (4) .
source is in the vicinity of the tap changer. Geometrical Figure 3 shows the frequency ranges with their corresponding
winding parts beeing sensitive towards mechanical changes
as identified by Cigre WG A2.26. For smaller power trans-
formers, the frequency ranges of interest tend to be shifted
towards higher frequency.
3.2 Measuring Technique The two most commonly
used test types for transfer function measurement of power
transformers are the so-called end-to-end transfer function
Fig. 1. UHF PD Probe for standard oil filling valve measurement T F EE ( f ) and the capacitive inter-winding mea-
surement T F CI ( f ), see also Ref. (5). Figure 4 shows the as-
sociated connection diagrams. The obtained transfer function
Fig. 2. Positions of UHF Sensors, acoustic sensors and Fig. 3. Frequency ranges with known sensitivity to-
the PD source at 333 MVA single phase autotransformer wards changes of the winding geometry (5)
of a measured phase then is: explained by unbalances of the ground capacitances and the
practical realization of the winding lead outs.
U 2,EE
T F EE ( f ) = · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · (1) FB3 and the lower part of FB4 reflect the most impor-
U1 tant part of the frequency response. Deviations occuring in
For the second measurement type, the transfer function is: this frequency range indicate mechical changes such as bulk
winding movement or buckling of windings (6) .
U 2,CI
T F CI ( f ) = . · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · (2) 4. Moisture Measurement
U1
3.3 Case Study Fig. 5 shows a representative case 4.1 Motivation Moisture is a critical parameter of the
of transfer functions of all phases measured at a 200 MVA insulating system. This has several reasons. One is that the
110 kV/65 kV three phase power transformer. dielectric strength of insulating liquid is strongly affected by
There are characteristic frequency bands which reflect dif- moisture. The risk of partial discharges and the bubble effect
ferent electrical properties of the transformer. The frequency (evaporation of water vapour under high load conditions) is
bands FB1 and FB2 are related to the core magnetizing in- higher. Water is also hazardous to the cellulose based insula-
ductance and winding series capacitance, while FB3 and FB4 tion as it accelerates further ageing. So by knowing the water
are related to the leakage inductances of the windings and the content of a transformer’s solid insulation it is possible to get
capacitances of adjacent windings. The high frequency part an idea of its ageing condition and thus plan further actions.
of FB4 up to 2 MHz represents smaller details of the active 4.2 Sources of Water in Transformers The first
part geometry together with the winding leads. Additionally, source of water in the lifetime of a transformer can be from
the bushing capacitances influence the high frequency part of improper drying in the factory. Another can be moisture
the transfer functions. ingress from the atmosphere. This can happen for free-
Differences between transfer functions of differents phases breathing transformers if the air-drying system is poorly
are greater in FB1, FB2 and in the upper part of FB4. For maintained. Another source is during repair in the field where
FB1 and FB2 the differences can be explained by the unbal- there are no possibilities of dry storage. The last, if not
ance of the core (magnetic circuit) and remanence of the core. the most important one is moisture originating from ageing
Mismatching between phases in the upper part of FB4 can be of paper and pressboard. This means, that even a perfectly
serviced transformer will become wet with increasing age.
There are studies which show that the ageing accelerates with
higher moisture content and at the same time water is pro-
duced due to ageing (see Fig. 6) (7) . One can conclude that
lifetime estimations of cellulosic insulating systems do not
only depend on operating temperature but also on moisture
content of solid insulation. This is the reason why water
assessment in combination with other diagnostic techniques
can help finding the health condition of a transformer.
4.3 Methods of Moisture Assessment The aim is to
know the water content of the critical solid insulation which
is the thin paper. It is nearly impossible to measure this di-
rectly as the paper cannot be sampled for measurement with-
out destroying it. Here only indirect methods can help. Ba-
sically there are two groups of techniques: first are the mois-
ture equilibrium charts and second are the dielectric response
Fig. 4. Connection schemes for measurements of end-
to-end (EE) and capacitive inter-winding (CI) frequency measurements. The equilibrium diagrams use the fact that
response the moisture in the paper-oil system reaches an equilibrium
Maximilian Heindl (Non-member) received the Diploma degree in Mark Jovalekic (Non-member) received his diploma degree in elec-
electrical engineering and information technology trical engineering and information technology from
from the University of Stuttgart, Germany, in 2007 University of Stuttgart, Germany in 2008. Since then
and joined the Institute of Power Transmission and he joined the Institute of Power Transmission and
High Voltage Technology, where he currently is doc- High Voltage Technology as research assistant. His
toral research assistant. The focus of his work and field of research is the oil-paper insulation system,
research lies on frequency response analysis, trans- especially with focus on natural ester fluids. This in-
former transient interaction and transformer related cludes the fundamental characteristics and ageing be-
modeling of both high and low frequency problem haviour of these dielectric liquids as well as diagno-
types. Mr. Heindl is member of CIGRE and VDE sis of power transformers by means of dissolved gas
ETG and published several papers. analysis and moisture assessment. Mark Jovalekic is member of VDE ETG
and published several papers.