Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

140 HOSTEL BUILDING KSP

E - EARTHING
TOP VIEW
G.P. - GLAND PLATE
DP - DOUBLE POLE
INCOMING
G.P. G.P. TPN - TRIPLE POLE
NEUTRAL 1. 200 A MAIN MCCB BREAKING CAPACITY 35KA AT 415V
(CURRENT RATING 200A & ADJUSTABLE 80%-100%THERMAL)

2. 200 A CHANGE OVER SWITCH ( 200A ,415 / 500 VOLTS )


BUSBAR
CHAMBER
MCCB 125 A
R Y B FOR
VTPN 1
GF OUTGOING
1.
v A MCCB 125 A
FOR 1. 125 A OUTGOING MCCB BREAKING CAPACITY 25KA AT 415V
VTPN 2
FF (CURRENT RATING 100A & 80%-100%) ADJUSTABLE )
2.
MCCB 125 A
FOR CABLE 2. 125 A OUTGOING MCCB BREAKING CAPACITY 25KA AT 415V
VTPN 3
SF CHAMBER (CURRENT RATING 100A & 80%-100%) ADJUSTABLE )
C/O SW 200A 3.
2. MCCB 125 A 3. 125 A OUTGOING MCCB BREAKING CAPACITY 25KA AT 415V
FOR (CURRENT RATING 100A & 80%-100%) ADJUSTABLE )
VTPN 3
TF

MCCB 200 A 4.
4. 125 A OUTGOING MCCB BREAKING CAPACITY 25KA AT 415V
EXTRA
(TUBE (CURRENT RATING 100A & 80%-100%) ADJUSTABLE )
WELL &
E STREET ) E

1. 200 A BUSBAR
3 NO'S 2 NO'S
5.
32A DP 63A TPN
5. 32 A (DP) OUTGOING MCB BREAKING CAPACITY 10KA AT 240V
63 A (TPN) OUTGOING MCB BREAKING CAPACITY 10KA AT 415V

FRONT VIEW SIDE VIEW

G.P. G.P.

BOTTOM VIEW