NORTH AYRSHIRE COUNCIL

ECONOMIC DEVELOPMENT & REGENERATION


Cunninghame House, Irvine, KA12 8EE
Email: transportation@north-ayrshire.gov.uk

Construction Consents
Standard Construction Details
Date: 19th August 2019
Revision: 3
Revision Date: 25th February 2020

INTRODUCTION
North Ayrshire Council has produced a set of standard details that can be used in the submission
of construction consents within North Ayrshire. Our standard construction details provide useful
information for construction consent applications. These can either be duplicated for consents
within the area or referenced in any submitted consent. The developer is responsible for ensuring
that the standard details are relevant for their construction consent submission.

If the standard details are copied into construction consent submissions, please add the following
to the drawings.

“The standard details (Revision X) within this submission are obtained from North Ayrshire
Council's standard details, with their permission. North Ayrshire Council disclaim all responsibility
and accept no liability (including in negligence) for the consequences for any person using these
standard details."
NORTH AYRSHIRE COUNCIL - LIST OF STANDARD DRAWINGS  Day  19  10  25     
  Month  08  01  02     
      Year  19  20  20     
Revision on 
No  Code    Title 
date 
STANDARD FOOTWAY/CARRIAGEWAY CONSTRUCTION 
001  CD  NAC/001/CD  A         
DEPTHS 
Kerb Details 
PRECAST CONCRETE KERB TYPES 
101  HB1  NAC/101/HB1  A         
STANDARD 125x255mm HALF BATTER KERB (HB1) 
PRECAST CONCRETE KERB TYPES 
102  SP1  NAC/102/SP1  A         
STANDARD 125x255mm SPLAYED KERB (SP1) 
PRECAST CONCRETE KERB TYPES 
103  BN1 ‐ 4  NAC/103/BNK  STANDARD 125x255mm BULLNOSED KERB (Various  A         
Upstand) 
PRECAST CONCRETE KERB TYPES 
104  BN5  NAC/104/BN5  A         
STANDARD 125x150mm BULLNOSED KERB (BN5) 
PRECAST CONCRETE KERB TYPES 
105  CS  NAC/105/CS  A         
STANDARD 125x225mm SQUARE CHANNEL KERB (CS) 
PRECAST CONCRETE KERB TYPES 
106  RT  NAC/106/RT  A         
STANDARD 50x150mm ROUND TOP EDGING KERB (RT) 
Page 1 of 3
PRECAST CONCRETE KERB TYPES 
107  FT  NAC/107/FT  A         
STANDARD 50x150mm FLAT TOP EDGING KERB (FT) 
PRECAST CONCRETE KERB TYPES 
108  TR  NAC/108/TR  A         
STANDARD TRIEF KERB (TR) 
Typical Sections 
STREET TYPE 1, 2 OR 3 WITH FOOTWAY (100mm kerb 
201  FCA  NAC/201/FCA  A         
upstand) 
STREET TYPE 3 OR 4 WITH FOOTWAY (30mm kerb 
202  FCB  NAC/202/FCB  A         
upstand) 
203  DM4  NAC/203/DM4  STREET TYPE 4 WITH DEMARCATION ZONE  A         
204  SC4  NAC/204/SC4  STREET TYPE 4 WITH SERVICE STRIP (50mm kerb upstand)  A         
205  DW2  NAC/205/DW2  STREET TYPE 1, 2 OR 3 AT DRIVEWAY/ACCESS  A         
206  DW3  NAC/206/DW3  STREET TYPE 4 AT DRIVEWAY/ACCESS  A         
STREET TYPE 1, 2 OR 3 ‐ NO ADJACENT ADOPTABLE ASSET 
207  SNA1  NAC/207/SNA1  A         
(100mm kerb upstand) 
STREET TYPE 3 or 4 ‐ NO ADJACENT ADOPTABLE ASSET 
208  SNA2  NAC/208/SNA2  A         
(50mm kerb upstand) 
TYPICAL STREET WITH GULLY AND ADJACENT FILTER 
209  SFT  NAC/209/SFT  A         
TRENCH 
210  RFP  NAC/210/RFP  TYPICAL FOOTPATH WITH FILTER TRENCH  A         
211  OVR  NAC/211/OVR  BLOCK PAVED OVERRUN CONSTRUCTION DETAIL  A         
212  TRCS  NAC/212/TRCS  TRANSITION FEATURE TO A TYPE 3 OR 4 STREET  A         
STANDARD FOOTWAY/OFF STREET PARKING BAYS 
213  PAR  NAC/213/PAR  A         
CONSTRUCTION 
Utilities and Drainage 
RECOMMENDED POSITIONING OF UTILITY 
301  SER  NAC/301/SER  A         
APPARATUS IN A 2 METRE FOOTWAY 
PRECAST CONCRETE TRAPPED STREET GULLY 
302  GUL  NAC/302/GUL  A         
450 mm NOMINAL BORE 
TYPE B MANHOLE ‐ MAXIMUM DEPTH 3 METRES 
303  MH1  NAC/303/MH1  A         
(to be used within carriageway) 
TYPE A MANHOLE ‐ DEPTH 3 TO 6 METRES 
304  MH2  NAC/304/MH2  A         
(to be used within carriageway) 
CATCHPIT 
305  CTP  NAC/305/CTP  A         
(to be used outwith carriageway) 
306  ROD  NAC/306/ROD  RODDING EYE DETAIL  A         
307  CPD  NAC/307/CPD  CARRIER PIPE DETAIL ‐ PIPE BEDDING DETAIL  A         
308  FLT1  NAC/308/FLT1  FILTER TRENCH CONSTRUCTION ‐ SECTION  A         
309  FLT2  NAC/309/FLT2  FILTER TRENCH CONSTRUCTION ‐ PLAN  A         
310  HCH  NAC/310/HCH  HYDROBRAKE CHAMBER  A         
311  PS  NAC/311/PS  TYPICAL SECTION THROUGH POND MARGIN  A         
312  PB  NAC/312/PB  TYPICAL SECTION THROUGH BASIN  A         
313  PI  NAC/313/PI  DETENTION POND INLET HEADWALL DETAIL  A         
314  PO  NAC/314/PO  DETENTION POND OUTLET HEADWALL DETAIL  A         
315  PSG  NAC/315/PSG  DETENTION POND OUTFALL SAFETY GRILLE DETAIL  A         
316  PPF  NAC/316/PPF  DETENTION POND/BASIN PERIMETER FENCE DETAIL  A         
317  SWP  NAC/317/SWP  STANDARD WET SWALE/CARRIAGEWAY CONSTRUCTION  A         
318  SWS  NAC/318/SWS  STANDARD WET SWALE/CARRIAGEWAY CONSTRUCTION  A         
319  SDP  NAC/319/SDP  STANDARD DRY SWALE/CARRIAGEWAY CONSTRUCTION  A         
320  SDS  NAC/320/SDS  STANDARD DRY SWALE/CARRIAGEWAY CONSTRUCTION  A         
Page 2 of 3
Footway 
401  TPS  NAC/401/TPS  TACTILE PAVING AT SIGNALS  A         
TACTILE PAVING AT PEDESTRIAN 
402  TPC  NAC/402/TPC  A         
CROSSING POINTS 
403  BS  NAC/403/BS  STANDARD BUS STOP CONSTRUCTION  A         
404  DW1  NAC/404/DW1  STANDARD PRIVATE DRIVEWAY ACCESS (FOOTWAY)  A  A  B     
SINGLE MINOR COMMERCIAL ACCESS, HOUSING COURT 
405  SMA  NAC/405/SMA  A         
OR CAR PARK UP TO 50 SPACES 
MINOR COMMERCIAL ACCESS OR CAR PARK OVER 50 
406  MCA  NAC/406/MCA  A         
SPACES 
407  MAC  NAC/407/MAC  MAJOR COMMERCIAL ACCESS  A         
408  DWD  NAC/408/DWD  MINIMUM DRIVEWAY DIMENSIONS  A         
DROPPED KERB DETAIL AT DESIGNATED PEDESTRIAN 
409  PCR  NAC/409/PCR  A  B       
CROSSING 
410  DW4  NAC/410/DW4  STANDARD PRIVATE DRIVEWAY ACCESS (SERVICE STRIP)  ‐  ‐  A     
Miscellaneous 
CAPPING LAYER REQUIREMENTS: SUBJECT TO FROST 
501  CAP  NAC/501/CAP  A         
SUSCEPTIBILITY 
502  BOL  NAC/502/BOL  BOLLARD DETAIL  A         
503  TRE  NAC/503/TRE  TREE PIT DETAIL WITH CONTAINMENT  A         
504  SCJ  NAC/504/SCJ  STEPPED CARRIAGEWAY JOINT  A         
505  POS  NAC/505/POS  SIGNPOST FOUNDATION DETAIL  A         
506  SNP  NAC/506/SNP  STREET NAMEPLATE DETAIL  A         

Page 3 of 3
NOTES
Carriageway Construction
Road Type Sub-Base Base Course Binder Course Surface Course 1. All dimensions in millimetres.
1 Connector Streets 300mm Granular Sub-base Type 1 140mm Dense Base Course Asphalt Concrete 60mm Dense Binder Course Asphalt Concrete 40mm Hot Rolled Asphalt Surface Course
2. For construction works in Arran HRA
(cl 803) Recipe Mixture (cl 906) Recipe Mixture (cl 906) (Recipe Mixture) (cl 910)
(AC 32 Dense Base 100/150 rec) (AC 20 Dense Bin 100/150 rec) (HRA 30/14 F surf 40/60) should be substituted for the following;
Black 14/20mm Coated Chipping 40/60 PSV 60 HRA 30/14 to AC 10 close surf 100/150
(cl 915) HRA 15/10 to AC 6 close surf 100/150
2 Local Residential Streets 300mm Granular Sub-base Type 1 100mm Dense Base Course Asphalt Concrete 60mm Dense Binder Course Asphalt Concrete 40mm Hot Rolled Asphalt Surface Course
(cl 803) Recipe Mixture (cl 906) Recipe Mixture (cl 906) (Recipe Mixture) (cl 910)
(AC 32 Dense Base 100/150 rec) (AC 20 Dense Bin 100/150 rec) (HRA 30/14 F surf 40/60)
Black 14/20mm Coated Chipping 40/60 PSV 60
(cl 915)

3 Shared Space Streets 300mm Granular Sub-base Type 1 80mm Dense Base Course Asphalt Concrete 50mm Dense Binder Course Asphalt Concrete 40mm Hot Rolled Asphalt Surface Course
(cl 803) Recipe Mixture (cl 906) Recipe Mixture (cl 906) (Recipe Mixture) (cl 910)
(AC 32 Dense Base 100/150 rec) (AC 20 Dense Bin 100/150 rec) (HRA 30/14 F surf 40/60)
130mm Dense Binder Course Asphalt Concrete Red 14/20mm Uncoated Chipping 40/60 PSV 60
Recipe Mixture (cl 906) (cl 915)
(AC 20 dense bin 100/150 rec)

4 300mm Granular Sub-base Type 1 80mm Dense Base Course Asphalt Concrete 50mm Dense Binder Course Asphalt Concrete 40mm Hot Rolled Asphalt Surface Course
(cl 803) Recipe Mixture (cl 906) Recipe Mixture (cl 906) (Recipe Mixture) (cl 910)
(a) (AC 32 Dense Base 100/150 rec) (AC 20 Dense Bin 100/150 rec) (HRA 30/14 F surf 40/60)
130mm Dense Binder Course Asphalt Concrete Red 14/20mm Uncoated Chipping 40/60 PSV 60
Recipe Mixture (cl 906) (cl 915)
Level Surface Streets
(AC 20 dense bin 100/150 rec)
4 400mm Granular Sub-base Type 1 50mm Bedding Layer of Sharp Sand or Crushed 200 x 100 x 80mm Concrete Block Paving (cl 1043)
(cl 803) Rock (Appendix 7/1)
(b)

Footway/path, Cycle Track Construction


Type Sub-Base Binder Course Surface Course
Flexible Surfacing 150mm Granular Sub-base Type 1 50mm Dense Binder Course Asphalt Concrete 30mm Hot Rolled Asphalt Surface Course
(Urban) (cl 803) Recipe Mixture (cl 906) Recipe Mixture (cl 910)
(AC 20 dense bin 100/150 rec) (HRA 15/10 F surf 40/60)
Prior To Compaction 6mm Or 10mm Limestone Chippings
Shall Be Applied To The Surface At A Nominal Of 1 Kg/m²
Flexible Surfacing 200mm Granular Sub-base Type 1 40mm Close Graded Asphalt Concrete 25mm Hot Rolled Asphalt Surface Course
(Rural) (cl 803) (cl 912) Recipe Mixture (cl 910)
or recycled suitable material (eg planings) (AC 14 close surf 100/150) (HRA 15/10 F surf 40/60)
Prior To Compaction 6mm Or 10mm Limestone Chippings
Shall Be Applied To The Surface At A Nominal Of 1 Kg/m²

or subject to the agreement of NAC

25mm Close Graded Asphalt Concrete Surface Course


(cl 912)
(AC 10 close surf 100/150)
Combined 50mm Close Graded Asphalt Concrete Surface course (cl 912) (AC 10 close surf 100/150)

Block Paving or Paviors 150mm Granular Sub-base Type 1 40±10 mm Bedding Layer of Sharp Sand or Crushed Rock 200 x 100 x 65mm thick Rectangular Concrete Block Paving (cl
(cl 803) Fines (Appendix 11/1) 11 07) or Concrete Pavers (cl 1107)

DRAWING NO REV
STANDARD FOOTWAY/CARRIAGEWAY CONSTRUCTION DEPTHS
NAC/001/CD A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
NOTES
50 1. All dimensions in millimetres. (This
drawing is not to scale)

2. Kerb details to comply with BS EN 1340.

3. Standard Kerb size 125mm x 255mm

60
4. Standard Kerb upstand 100mm or

100
otherwise directed
CARRIAGEWAY LEVEL 5. Kerbs to be hydraulically pressed.

6. Kerb foundation and haunch to be


concrete class ST4, 30 slump.
Foundation slump may be reduced if
kerbs laid wet.

7. Kerbs to be laid and bedded on a layer


195

of M12 mortar not less than 10mm and


not more than 40mm thick. Alternatively,
kerbs may be laid directly on newly
placed concrete foundation.

8. All kerbs to be abutted, except kerbs laid


to a radius of less than 40m, which shall
be laid with an average gap of 6mm and
pointed with M12 mortar.

9. For curves of radius 12m or less, kerbs


25mm M12 Mortar Bed of appropriate radius shall be used as
per BS EN 1340.

(This drawing is not to scale)

ST4 Class
150

Concrete
Foundation
and Haunch

175 125 50

PRECAST CONCRETE KERB TYPES DRAWING NO REV

STANDARD 125x255mm HALF BATTER KERB (HB1)


NAC/101/HB1 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
NOTES
50 1. All dimensions in millimetres. (This
drawing is not to scale)

2. Kerb details to comply with BS EN 1340.

3. Standard Kerb size 125mm x 255mm

60
4. Standard Kerb upstand 100mm or

100
otherwise directed
CARRIAGEWAY LEVEL 5. Kerbs to be hydraulically pressed.

6. Kerb foundation and haunch to be


concrete class ST4, 30 slump.
Foundation slump may be reduced if
kerbs laid wet.

7. Kerbs to be laid and bedded on a layer


195

of M12 mortar not less than 10mm and


not more than 40mm thick. Alternatively,
kerbs may be laid directly on newly
placed concrete foundation.

8. All kerbs to be abutted, except kerbs laid


to a radius of less than 40m, which shall
be laid with an average gap of 6mm and
pointed with M12 mortar.

9. For curves of radius 12m or less, kerbs


25mm M12 Mortar Bed of appropriate radius shall be used as
per BS EN 1340.

(This drawing is not to scale)

ST4 Class
150

Concrete
Foundation
and Haunch

175 125 50

PRECAST CONCRETE KERB TYPES DRAWING NO REV

STANDARD 125x255mm SPLAYED KERB (SP1)


NAC/102/SP1 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
NOTES
50 1. All dimensions in millimetres. (This
drawing is not to scale)

2. Kerb details to comply with BS EN 1340.

3. Standard Kerb size 125mm x 255mm

60

VARIES
(SEE TABLE)
4. Kerb upstand to be noted using Type
Reference from the table shown
CARRIAGEWAY LEVEL 5. Kerbs to be hydraulically pressed.

6. Kerb foundation and haunch to be


concrete class ST4, 30 slump.
Foundation slump may be reduced if
kerbs laid wet.

7. Kerbs to be laid and bedded on a layer


195

of M12 mortar not less than 10mm and


not more than 40mm thick. Alternatively,
kerbs may be laid directly on newly
placed concrete foundation.
25mm M12 Mortar Bed
8. All kerbs to be abutted, except kerbs laid
to a radius of less than 40m, which shall
be laid with an average gap of 6mm and
pointed with M12 mortar.
ST4 Class
9. For curves of radius 12m or less, kerbs
Concrete of appropriate radius shall be used as
Foundation per BS EN 1340.

and Haunch (This drawing is not to scale)


150

Carriageway Construction
Kerb Type Upstand
BN1 100mm
BN2 50mm
175 125 50 BN3 30mm
BN4 20mm
BN5 See NAC/104/BN5

PRECAST CONCRETE KERB TYPES DRAWING NO REV

STANDARD 125x255mm BULLNOSED KERB (Various Upstand)


NAC/103/BNK A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. Kerb details to comply with BS EN 1340.

3. Standard Kerb size 125mm x 150mm

50 4. Standard Kerb upstand 0-6mm at


CARRIAGEWAY LEVEL Pedestrian Crossing

5. Kerbs to be hydraulically pressed.

0-6mm 6. Kerb foundation and haunch to be


60

concrete class ST4, 30 slump.


Foundation slump may be reduced if
kerbs laid wet.

7. Kerbs to be laid and bedded on a layer


of M12 mortar not less than 10mm and
not more than 40mm thick. Alternatively,
kerbs may be laid directly on newly
90

placed concrete foundation.

8. All kerbs to be abutted, except kerbs laid


to a radius of less than 40m, which shall
be laid with an average gap of 6mm and
25mm M12 Mortar Bed pointed with M12 mortar.

9. For curves of radius 12m or less, kerbs


of appropriate radius shall be used as
per BS EN 1340.

ST4 Class (This drawing is not to scale)


150

Concrete
Foundation
and Haunch

175 125 50

PRECAST CONCRETE KERB TYPES DRAWING NO REV

STANDARD 125x150mm BULLNOSED KERB (BN5)


NAC/104/BN5 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
NOTES

Block Paving)
accomodate
(or 85 to
1. All dimensions in millimetres. (This

60
drawing is not to scale)

50 CARRIAGEWAY LEVEL 2. Kerb details to comply with BS EN 1340.

3. Standard Kerb size 125mm x 225mm

4. Standard Kerb upstand 0mm or


otherwise directed

5. Kerbs to be hydraulically pressed.

6. Kerb foundation and haunch to be


concrete class ST4, 30 slump.
Foundation slump may be reduced if
kerbs laid wet.

7. Kerbs to be laid and bedded on a layer


of M12 mortar not less than 10mm and
not more than 40mm thick. Alternatively,
kerbs may be laid directly on newly
placed concrete foundation.

8. All kerbs to be abutted, except kerbs laid


to a radius of less than 40m, which shall
be laid with an average gap of 6mm and
pointed with M12 mortar.

9. For curves of radius 12m or less, kerbs


25mm M12 Mortar Bed of appropriate radius shall be used as
per BS EN 1340.

(This drawing is not to scale)

ST4 Class
150

Concrete
Foundation
and Haunch

150 125 150

PRECAST CONCRETE KERB TYPES DRAWING NO REV

STANDARD 125x225mm SQUARE CHANNEL KERB (CS)


NAC/105/CS A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
NOTES
1. All dimensions in millimetres. (This
drawing is not to scale)

2. Kerb details to comply with BS EN 1340.

3. Standard Edging Kerb size 50mm


x 150mm

4. Standard Kerb upstand 50mm or


otherwise directed

5. Kerbs to be hydraulically pressed.

6. Kerb foundation and haunch to be


concrete class ST4, 30 slump.
FOOTWAY LEVEL Foundation slump may be reduced if

50
kerbs laid wet.

25 7. Kerbs to be laid and bedded on a layer


of M12 mortar not less than 10mm and

30
not more than 40mm thick. Alternatively,
kerbs may be laid directly on newly
placed concrete foundation.

8. All kerbs to be abutted, except kerbs laid


to a radius of less than 40m, which shall
be laid with an average gap of 6mm and
pointed with M12 mortar.

25mm M12 Mortar Bed 9. For curves of radius 12m or less, kerbs
of appropriate radius shall be used as
ST4 Class per BS EN 1340.

Concrete
100

(This drawing is not to scale)

Foundation
and Haunch

300

PRECAST CONCRETE KERB TYPES DRAWING NO REV

STANDARD 50x150mm ROUND TOP EDGING KERB (RT)


NAC/106/RT A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
NOTES
1. All dimensions in millimetres. (This
drawing is not to scale)

2. Kerb details to comply with BS EN 1340.

3. Standard Edging Kerb size 50mm


x 150mm

4. Standard Kerb upstand 0mm or


otherwise directed
FOOTWAY LEVEL 5. Kerbs to be hydraulically pressed.

6. Kerb foundation and haunch to be


concrete class ST4, 30 slump.
Foundation slump may be reduced if
kerbs laid wet.

80
25 7. Kerbs to be laid and bedded on a layer
of M12 mortar not less than 10mm and
not more than 40mm thick. Alternatively,
kerbs may be laid directly on newly
placed concrete foundation.

8. All kerbs to be abutted, except kerbs laid


to a radius of less than 40m, which shall
be laid with an average gap of 6mm and
pointed with M12 mortar.

25mm M12 Mortar Bed 9. For curves of radius 12m or less, kerbs
of appropriate radius shall be used as
ST4 Class per BS EN 1340.

Concrete
100

(This drawing is not to scale)

Foundation
and Haunch

300

PRECAST CONCRETE KERB TYPES DRAWING NO REV

STANDARD 50x150mm FLAT TOP EDGING KERB (FT)


NAC/107/FT A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
NOTES
1. All dimensions in millimetres. (This
drawing is not to scale)

75
2. Kerb details to comply with BS EN 1340.

3. Kerbs to be hydraulically pressed.

4. Kerb foundation and haunch to be


concrete class ST4, 30 slump.
Foundation slump may be reduced if
kerbs laid wet.

5. Kerbs to be laid and bedded on a layer


of M12 mortar not less than 10mm and
not more than 40mm thick. Alternatively,
kerbs may be laid directly on newly
415

placed concrete foundation.

6. All kerbs to be abutted, except kerbs laid


to a radius of less than 40m, which shall
be laid with an average gap of 6mm and
CARRIAGEWAY LEVEL pointed with M12 mortar.

7. For curves of radius 12m or less, kerbs


of appropriate radius shall be used as
per BS EN 1340.

(This drawing is not to scale)

75
25mm M12 Mortar Bed

ST4 Class
150

Concrete
Foundation
and Haunch

235 380 75

PRECAST CONCRETE KERB TYPES DRAWING NO REV

STANDARD TRIEF KERB (TR)


NAC/108/TR A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Kerb Type RT Footway Construction
Type 2 Carriageway Type 3 Carriageway
to Table: NAC/001/CD Kerb Type HB1 Type 1 Carriageway 1. All dimensions in millimetres. (This
Construction to Construction to
Construction to Table: NAC/001/CD drawing is not to scale)
50 Table: NAC/001/CD

50
2.5% Fall Table: NAC/001/CD
25 2. New Kerbing details to comply with
30

drawing as stated

60

100
3. Full Construction Information for
2.5% Fall Carriageway to Table NAC/001/CD
M12 Mortar Bed
ST4 Class
Concrete
4. Full Construction Information for Footway
100

to Table NAC/001/CD

195
Foundation
and Haunch
(This drawing is not to scale)

300

M12 Mortar Bed

150
ST4 Class
Concrete
Foundation
and Haunch

175 125 50

Carriageway Construction
SURFACE COURSE Road Type Sub-Base Base Course Binder Course Surface Course
1 Connector 300mm Granular Sub-base Type 1 140mm Dense Base Course 60mm Dense Binder Course Asphalt 40mm Hot Rolled Asphalt Surface
Streets (cl 803) Asphalt Concrete (Recipe Mixture Concrete (Recipe Mixture) (cl 906), Course (Recipe Mixture) (cl 910),
BINDER COURSE (cl 906), (AC 32 dense base (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with
100/150 rec) Black 14/20mm Coated Chipping
40/60 PSV 60 (cl 915)

BASE COURSE 2 Local


Residential
300mm Granular Sub-base Type 1
(cl 803)
100mm Dense Base Course
Asphalt Concrete (Recipe Mixture
60mm Dense Binder Course Asphalt
Concrete (Recipe Mixture) (cl 906),
40mm Hot Rolled Asphalt Surface
Course (Recipe Mixture) (cl 910),
Streets (cl 906), (AC 32 dense base (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with
100/150 rec) Black 14/20mm Coated Chipping
SUB-BASE 40/60 PSV 60 (cl 915)

3 Shared 300mm Granular Sub-base Type 1 80mm Dense Base Course Asphalt 50mm Dense Binder Course Asphalt 40mm Hot Rolled Asphalt Surface
Space (cl 803) Concrete (Recipe Mixture (cl 906), Concrete (Recipe Mixture) (cl 906), Course (Recipe Mixture) (cl 910),
Streets (AC 32 dense base 100/150 rec) (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with Red
14/20mm Uncoated Chipping 40/60
130mm Dense Binder Course Asphalt Concrete (Recipe Mixture) (cl 906), PSV 60 (cl 915)
(AC 20 dense bin 100/150 rec)

DRAWING NO REV
STREET TYPE 1, 2 OR 3 WITH FOOTWAY (100mm kerb upstand)
NAC/201/FCA A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Type 3/4a Type 4b Carriageway
Carriageway Construction to
Kerb Type RT Footway Construction
Construction to Table: NAC/001/CD
to Table: NAC/001/CD
Kerb Type BN3 Table: NAC/001/CD
1. All dimensions in millimetres. (This
50

50
drawing is not to scale)
25 2.5% Fall
30 2.5% Fall 2. New Kerbing details to comply with

30
drawing as stated

60
3. Full Construction Information for
Carriageway to Table NAC/001/CD
M12 Mortar Bed
ST4 Class 4. Full Construction Information for Footway
Concrete
100

to Table NAC/001/CD

195
Foundation
and Haunch (This drawing is not to scale)

300

M12 Mortar Bed

ST4 Class

150
Concrete
Foundation
SURFACE COURSE and Haunch

BINDER COURSE 175 125 50

SAND BEDDING

SUB-BASE

Carriageway Construction
Road Type Sub-Base Base Course Binder Course Surface Course
3 Shared 300mm Granular Sub-base Type 1 80mm Dense Base Course Asphalt 50mm Dense Binder Course Asphalt 40mm Hot Rolled Asphalt Surface
Space (cl 803) Concrete (Recipe Mixture (cl 906), Concrete (Recipe Mixture) (cl 906), Course (Recipe Mixture) (cl 910),
Streets (AC 32 dense base 100/150 rec) (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with Red
14/20mm Uncoated Chipping 40/60
130mm Dense Binder Course Asphalt Concrete (Recipe Mixture) (cl 906), PSV 60 (cl 915)
(AC 20 dense bin 100/150 rec)

4 300mm Granular Sub-base Type 1 80mm Dense Base Course Asphalt 50mm Dense Binder Course Asphalt 40mm Hot Rolled Asphalt Surface
(cl 803) Concrete (Recipe Mixture (cl 906), Concrete (Recipe Mixture) (cl 906), Course (Recipe Mixture) (cl 910),
(a) (AC 32 dense base 100/150 rec) (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with Red
Level 14/20mm Uncoated Chipping 40/60
130mm Dense Binder Course Asphalt Concrete (Recipe Mixture) (cl 906),
Surface PSV 60 (cl 915)
(AC 20 dense bin 100/150 rec)
Streets
4 400mm Granular Sub-base Type 1 (cl 803) 50mm Bedding Layer of Sharp Sand 200 x 100 x 80mm thick Concrete
or Crushed Rock (Appendix 7/1) Rectangular Block Paving (cl 1043)
(b)

DRAWING NO REV
STREET TYPE 3 OR 4 WITH FOOTWAY (30mm kerb upstand)
NAC/202/FCB A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Demarcation Zone
1. All dimensions in millimetres. (This
drawing is not to scale)

2. New Kerbing details to comply with


drawing as stated
Kerb Type BN2
Type 4b Carriageway 3. Full Construction Information for
Construction to Table: Carriageway to Table NAC/001/CD
Type 4b Carriageway
NAC/001/CD Kerb Type CS Type 4a Carriageway Construction to
Construction to 4. Full Construction Information for Footway
50 Table: NAC/001/CD1

accommodate
to Table NAC/001/CD

Block Paving
Table: NAC/001/CD

85 to
(This drawing is not to scale)

50
50
60

2.5% Fall 2.5% Fall


100

60
195

25mm M12 Mortar Bed

25mm M12 Mortar Bed


ST4 Class
150

Concrete
Foundation ST4 Class

150
and Haunch Concrete
Foundation
and Haunch

175 125 50

150 125 150

SURFACE COURSE
Carriageway Construction
BINDER COURSE Road Type Sub-Base Base Course Binder Course Surface Course
4 300mm Granular 80mm Dense Base Course 50mm Dense Binder Course 40mm Hot Rolled Asphalt Surface Course
Sub-base Type 1 Asphalt Concrete (Recipe Asphalt Concrete (Recipe (Recipe Mixture) (cl 910), (HRA 30/14 F
(a) (cl 803) Mixture (cl 906), (AC 32 Mixture) (cl 906), (AC 20 surf 40/60) with Red 14/20mm Uncoated
SAND BEDDING Level
dense base 100/150 rec) dense bin 100/150 rec) Chipping 40/60 PSV 60 (cl 915)
Surface 130mm Dense Binder Course Asphalt Concrete (Recipe
Streets Mixture) (cl 906), (AC 20 dense bin 100/150 rec)
SUB-BASE 4 400mm Granular Sub-base Type 1 (cl 803) 50mm Bedding Layer of
Sharp Sand or Crushed Rock
200 x 100 x 80mm thick Concrete
Rectangular Block Paving (cl 1043)
(b) (Appendix 7/1)

TOP SOIL & GRASS SEED

DRAWING NO REV
STREET TYPE 4 WITH DEMARCATION ZONE
NAC/203/DM4 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Type 4a Carriageway Type 4b Carriageway 1. All dimensions in millimetres. (This
Kerb Type BN2 Construction to drawing is not to scale)
Construction to
Table: NAC/001/CD Table: NAC/001/CD 2. New Kerbing details to comply with
Kerb Type FT drawing as stated
50
3. Full Construction Information for
Carriageway to Table NAC/001/CD

50
2.5% Fall

60
80
25 (This drawing is not to scale)

100
M12 Mortar Bed

195
ST4 Class
Concrete
100

Foundation
and Haunch

M12 Mortar Bed


300

ST4 Class

150
Concrete
Foundation
and Haunch

175 125 50

SURFACE COURSE

BINDER COURSE

SAND BEDDING
Carriageway Construction
Road Type Sub-Base Base Course Binder Course Surface Course
SUB-BASE 4 300mm Granular 80mm Dense Base Course 50mm Dense Binder Course 40mm Hot Rolled Asphalt Surface Course
Sub-base Type 1 Asphalt Concrete (Recipe Asphalt Concrete (Recipe (Recipe Mixture) (cl 910), (HRA 30/14 F
(a) (cl 803) Mixture (cl 906), (AC 32 Mixture) (cl 906), (AC 20 surf 40/60) with Red 14/20mm Uncoated
TOP SOIL & GRASS SEED Level
dense base 100/150 rec) dense bin 100/150 rec)
130mm Dense Binder Course Asphalt Concrete (Recipe
Chipping 40/60 PSV 60 (cl 915)
Surface
Streets Mixture) (cl 906), (AC 20 dense bin 100/150 rec)
4 400mm Granular Sub-base Type 1 (cl 803) 50mm Bedding Layer of 200 x 100 x 80mm thick Concrete
Sharp Sand or Crushed Rock Rectangular Block Paving (cl 1043)
(b) (Appendix 7/1)

DRAWING NO REV
STREET TYPE 4 WITH SERVICE STRIP (50mm kerb upstand)
NAC/204/SC4 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
ACO Domestic Channel Drain or similar 1. All dimensions in millimetres. (This
approved (Not required if Driveway falls drawing is not to scale)
away from footway. See Note 6)
2. This drawing should be read in
conjunction with drawing NAC/404/DW1
Type 2 Carriageway Type 3 Carriageway
Private Driveway to Architects Kerb Type FT Type 3 Carriageway Type 1 Carriageway Construction to
Design Construction to Table: Construction to Construction to 3. New Kerbing details to comply with
Table: NAC/001/CD Table: NAC/001/CD
NAC/001/CD Table: NAC/001/CD drawing as stated
2m wide Footway
Kerb Type BN4 4. Full Construction Information for
50 Carriageway to Table NAC/001/CD
2.5% Fall
2.5% Fall

20
5. Full Construction Information for Footway

80

60
25
to Table NAC/001/CD

M12 Mortar Bed 6. Where the gradient of the Private


Driveway slopes towards the Public
Footway, a Drainage Channel as

195
depicted must be installed. It is not
100

required if the Private Driveway slopes


into the private grounds.
ST4 Class
Concrete M12 Mortar Bed
300 (This drawing is not to scale)
Foundation
and Haunch
ST4 Class

150
Concrete
Foundation
and Haunch

175 125 50

SURFACE COURSE

BINDER COURSE

BASE COURSE Carriageway Construction


Road Type Sub-Base Base Course Binder Course Surface Course
SUB-BASE 1 Connector
Streets
300mm Granular Sub-base Type 1
(cl 803)
140mm Dense Base Course
Asphalt Concrete (Recipe Mixture
60mm Dense Binder Course Asphalt
Concrete (Recipe Mixture) (cl 906),
40mm Hot Rolled Asphalt Surface
Course (Recipe Mixture) (cl 910),
(cl 906), (AC 32 dense base (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with
100/150 rec) Black 14/20mm Coated Chipping
40/60 PSV 60 (cl 915)

2 Local 300mm Granular Sub-base Type 1 100mm Dense Base Course 60mm Dense Binder Course Asphalt 40mm Hot Rolled Asphalt Surface
Residential (cl 803) Asphalt Concrete (Recipe Mixture Concrete (Recipe Mixture) (cl 906), Course (Recipe Mixture) (cl 910),
Streets (cl 906), (AC 32 dense base (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with
100/150 rec) Black 14/20mm Coated Chipping
40/60 PSV 60 (cl 915)

3 Shared 300mm Granular Sub-base Type 1 80mm Dense Base Course Asphalt 50mm Dense Binder Course Asphalt 40mm Hot Rolled Asphalt Surface
Space (cl 803) Concrete (Recipe Mixture (cl 906), Concrete (Recipe Mixture) (cl 906), Course (Recipe Mixture) (cl 910),
Streets (AC 32 dense base 100/150 rec) (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with Red
14/20mm Uncoated Chipping 40/60
130mm Dense Binder Course Asphalt Concrete (Recipe Mixture) (cl 906), PSV 60 (cl 915)
(AC 20 dense bin 100/150 rec)

DRAWING NO REV
STREET TYPE 1, 2 OR 3 AT DRIVEWAY/ACCESS
NAC/205/DW2 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)
ACO Domestic Channel Drain or similar Type 4b Carriageway
approved (Not required if Driveway falls Construction to Table:
2. This drawing should be read in
away from footway. See Note 6) NAC/001/CD
conjunction with drawing NAC/404/DW1

3. New Kerbing details to comply with


Private Driveway to Architects Kerb Type FT Kerb Type BN4 Type 4a Carriageway Type 4b Carriageway drawing as stated
Design Construction to Construction to
Table: NAC/001/CD Table: NAC/001/CD 4. Full Construction Information for
2m wide Service Strip Carriageway to Table NAC/001/CD

50 5. Full Construction Information for Footway


2.5% Fall to Table NAC/001/CD
2.5% Fall

20
80

80
25 6. Where the gradient of the Private
Driveway slopes towards the Public
Footway, a Drainage Channel as
depicted must be installed. It is not
M12 Mortar Bed required if the Private Driveway slopes
ST4 Class into the private grounds.
Concrete
100

Foundation
(This drawing is not to scale)
and Haunch

M12 Mortar Bed


300

ST4 Class

150
Concrete
Foundation
and Haunch

175 125 50

SURFACE COURSE

BINDER COURSE

SAND BEDDING Carriageway Construction


Road Type Sub-Base Base Course Binder Course Surface Course
4 300mm Granular 80mm Dense Base Course 50mm Dense Binder Course 40mm Hot Rolled Asphalt Surface Course
SUB-BASE (a)
Sub-base Type 1 Asphalt Concrete (Recipe Asphalt Concrete (Recipe (Recipe Mixture) (cl 910), (HRA 30/14 F
(cl 803) Mixture (cl 906), (AC 32 Mixture) (cl 906), (AC 20 surf 40/60) with Red 14/20mm Uncoated
dense base 100/150 rec) dense bin 100/150 rec) Chipping 40/60 PSV 60 (cl 915)
Level
Surface 130mm Dense Binder Course Asphalt Concrete (Recipe
Streets Mixture) (cl 906), (AC 20 dense bin 100/150 rec)

4 400mm Granular Sub-base Type 1 (cl 803) 50mm Bedding Layer of 200 x 100 x 80mm thick Concrete
Sharp Sand or Crushed Rock Rectangular Block Paving (cl 1043)
(b) (Appendix 7/1)

DRAWING NO REV
STREET TYPE 4 AT DRIVEWAY/ACCESS
NAC/206/DW3 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
NON-ADOPTABLE ADOPTABLE

1. All dimensions in millimetres. (This


drawing is not to scale)
Landscaping or Kerb Type HB1
other to Type 2 Carriageway Type 3 Carriageway
Type 1 Carriageway Construction to 2. New Kerbing details to comply with
Architect's design Construction to Construction to drawing as stated
50 Table: NAC/001/CD Table: NAC/001/CD
Table: NAC/001/CD
3. Full Construction Information for
Carriageway to Table NAC/001/CD

60

100
(This drawing is not to scale)

2.5% Fall
195

25mm M12 Mortar Bed


150

ST4 Class
Concrete
Foundation
and Haunch

175 125 50

Carriageway Construction
Road Type Sub-Base Base Course Binder Course Surface Course
SURFACE COURSE 1 Connector 300mm Granular 140mm Dense Base Course 60mm Dense Binder Course 40mm Hot Rolled Asphalt Surface Course
Streets Sub-base Type 1 Asphalt Concrete (Recipe Asphalt Concrete (Recipe (Recipe Mixture) (cl 910), (HRA 30/14 F surf
(cl 803) Mixture (cl 906), (AC 32 dense Mixture) (cl 906), (AC 20 dense 40/60) with Black 14/20mm Coated Chipping
base 100/150 rec) bin 100/150 rec) 40/60 PSV 60 (cl 915)
BINDER COURSE 2 Local 300mm Granular 100mm Dense Base Course 60mm Dense Binder Course 40mm Hot Rolled Asphalt Surface Course
Residential Sub-base Type 1 Asphalt Concrete (Recipe Asphalt Concrete (Recipe (Recipe Mixture) (cl 910), (HRA 30/14 F surf
Streets (cl 803) Mixture (cl 906), (AC 32 dense Mixture) (cl 906), (AC 20 dense 40/60) with Black 14/20mm Coated Chipping
BASE COURSE base 100/150 rec) bin 100/150 rec) 40/60 PSV 60 (cl 915)

3 Shared 300mm Granular 80mm Dense Base Course 50mm Dense Binder Course 40mm Hot Rolled Asphalt Surface Course
Space Sub-base Type 1 Asphalt Concrete (Recipe Asphalt Concrete (Recipe (Recipe Mixture) (cl 910), (HRA 30/14 F surf
Streets (cl 803) Mixture (cl 906), (AC 32 dense Mixture) (cl 906), (AC 20 dense 40/60) with Red 14/20mm Uncoated
SUB-BASE base 100/150 rec) bin 100/150 rec) Chipping 40/60 PSV 60 (cl 915)
130mm Dense Binder Course Asphalt Concrete (Recipe Mixture)
(cl 906), (AC 20 dense bin 100/150 rec)

STREET TYPE 1, 2 OR 3 - NO ADJACENT ADOPTABLE ASSET DRAWING NO REV

(100mm kerb upstand)


NAC/207/SNA1 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
NON-ADOPTABLE ADOPTABLE

1. All dimensions in millimetres. (This


Type 3/4a Type 4b Carriageway drawing is not to scale)
Landscaping or Carriageway Construction to
other to Table: NAC/001/CD 2. New Kerbing details to comply with
Construction to drawing as stated
Architect's design Kerb Type BN2 Table: NAC/001/CD
50
3. Full Construction Information for
Carriageway to Table NAC/001/CD

50
2.5% Fall

60
(This drawing is not to scale)

195

M12 Mortar Bed


150

ST4 Class
Concrete
Foundation
and Haunch

175 125 50

Carriageway Construction
Road Type Sub-Base Base Course Binder Course Surface Course
SURFACE COURSE 3 Shared 300mm Granular 80mm Dense Base Course Asphalt 50mm Dense Binder Course Asphalt 40mm Hot Rolled Asphalt Surface
Space Sub-base Type 1 Concrete (Recipe Mixture (cl 906), Concrete (Recipe Mixture) (cl 906), Course (Recipe Mixture) (cl 910),
Streets (cl 803) (AC 32 dense base 100/150 rec) (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with Red
14/20mm Uncoated Chipping 40/60
130mm Dense Binder Course Asphalt Concrete (Recipe Mixture) (cl 906), PSV 60 (cl 915)
BINDER COURSE (AC 20 dense bin 100/150 rec)
4 300mm Granular 80mm Dense Base Course Asphalt 50mm Dense Binder Course Asphalt 40mm Hot Rolled Asphalt Surface
Sub-base Type 1 Concrete (Recipe Mixture (cl 906), Concrete (Recipe Mixture) (cl 906), Course (Recipe Mixture) (cl 910),
(a) (cl 803) (AC 32 dense base 100/150 rec) (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with Red
BASE COURSE Level
130mm Dense Binder Course Asphalt Concrete (Recipe Mixture) (cl 906), 14/20mm Uncoated Chipping 40/60
Surface PSV 60 (cl 915)
(AC 20 dense bin 100/150 rec)
Streets
4 400mm Granular Sub-base Type 1 (cl 803) 50mm Bedding Layer of Sharp Sand 200 x 100 x 80mm thick Concrete
SUB-BASE (b)
or Crushed Rock (Appendix 7/1) Rectangular Block Paving (cl 1043)

STREET TYPE 3 or 4 - NO ADJACENT ADOPTABLE ASSET DRAWING NO REV

(50mm kerb upstand)


NAC/208/SNA2 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
LIMIT OF drawing is not to scale)
ADOPTABLE WORKS
2. New Kerbing details to comply with
Kerb Type HB1 Footway Construction drawing as stated
to Table: NAC/001/CD
3. Full Construction Information for
Carriageway Gully detail to
Kerb Type FT Carriageway to Table NAC/001/CD
Construction to drawing
Table: NAC/001/CD NAC/302/GUL 100mm Topsoil Cover
Kerb Type FT 4. Full Construction Information for Footway
Finished ground level to Table NAC/001/CD

80

80
25 25
5. Gully detail to drawing NAC/302/GUL

110
M12 Mortar Bed M12 Mortar Bed 6. Acceptable Backfill material to be
ST4 Class ST4 Class
Concrete Concrete material excavated from within the site or

100

100
Foundation Foundation

FORMATION and Haunch and Haunch imported on to the site which meets the
300 300 requirements of S.H.W. Table 6/1 and
contract specific Appendix 6/1 for

500
acceptability for use in the permanent
Class 1, 2 or 3 general fill
works.
material complying with
Series 600 (S.H.W. cl 505) (This drawing is not to scale)
150 min
cover

150
150
150 dia perforated
overflow pipe
Open end to have
mesh cap to prevent
stone entering pipe
Type A or C filter material

1000
to S.H.W. cl 505 or
granular material TO
S.H.W. cl 503.3(i)

1000 Guage
SURFACE COURSE SUB-BASE Visqueen
Impermeable barrier 150 dia perforated
or similar carrier pipe

BINDER COURSE TOP SOIL & GRASS SEED

BASE COURSE 1250

DRAWING NO REV
TYPICAL STREET WITH GULLY AND ADJACENT FILTER TRENCH
NAC/209/SFT A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Kerb Type FT Footway Construction Kerb Type FT
to Table: NAC/001/CD 300
2.5% Fall Finished ground level
1. All dimensions in millimetres. (This
drawing is not to scale)

80
25

80
25
2. New Kerbing details to comply with
drawing as stated

3. Full Construction Information for Footway


M12 Mortar Bed to Table NAC/001/CD
ST4 Class Concrete
Foundation and M12 4. Desirably, gradients on footways and
100

Mortar footpaths should not exceed 5%, with a

100
Haunch
Bed nominal maximum of 8%. They should be
constructed with crossfall of 3%. Steeper
gradients may occasionally be permitted,
300
300 subject to the provision of a handrail on
at least one side and rest platforms at 10
ST4 Class metre intervals.
Concrete X Type B filter material
Foundation and 5. Dimension X is the external diameter of
SURFACE COURSE Haunch
to S.H.W. cl 505 the pipe
75
6. This drawing is to be read in conjunction
BINDER COURSE Type A or C filter material with Appendix 5/1
to S.H.W. cl 505 or 7. Pipes shall comply with the requirements
granular material TO for filter drain pipes in Table 5/1 of the
SUB-BASE X + 300 min. for drains not
S.H.W. cl 503.3(i) S.H.W.
exceeding 1.5 m depth
X + 450 min. for drains 8. Pipes are to be laid with slots or
exceeding 1.5 m depth
(Depth below finished level) perforations upwards where a concrete
TOP SOIL & bed is used. For other beds the slots
GRASS SEED shall be orientated as described in
Appendix 5/1

9. Minimum drain width;

Footway/path, Cycle Track Construction X+300 for drains not exceeding 1.5 m
depth
X+450 for drains exceeding 1.5 m depth
Location Sub-Base Binder Course Surface Course (Depth below finished level)

(This drawing is not to scale)


Urban 150mm Granular 50mm Dense Binder Course 30mm Hot Rolled Asphalt Surface Course
Sub-base Type 1 Asphalt Concrete (Recipe (Recipe Mixture)(cl 910), (HRA 15/10 F surf
(cl 803) Mixture) (cl 906), (AC 20 40/60)
dense bin 100/150 rec)
Rural 200mm Type 1 or 40mm Close Graded Asphalt 25mm Hot Rolled Asphalt Surface Course (Recipie
Mixture) (cl 910), (HRA 15/10 F surf 40/60)
recycled suitable Concrete (cl 912) (AC 14 close
or
material (eg planings) surf 100/150) 25mm Close Graded Asphalt Concrete Surface course (cl
912), (AC 10 close surf 100/150)

Combined 50mm Close Graded Asphalt Concrete Surface course (cl 912)
(AC 10 close surf 100/150)

DRAWING NO REV
TYPICAL FOOTPATH WITH FILTER TRENCH
NAC/210/RFP A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. New Kerbing details to comply with


drawing as stated

3. Full Construction Information for


Carriageway to Table NAC/001/CD

4. Overrun areas should not have any


200 x 100 x 80mm thick CONCRETE PAVING BLOCKS (cl. 1107) vertical face which exceeds 6 mm in
height and sloping areas should not
Kerb Type to
exceed a slope angle of 15°, measured
match selected
30mm POLYMER MODIFIED MORTAR from the surface of the carriageway.
freeboard
(This drawing is not to scale)

150mm CLASS ST1 CONCRETE FOUNDATION

max 100
Min 25,
CARRIAGEWAY LEVEL Kerb Type BN1
15% FALL MAX
15mm MAX.

VERTICAL
UPLIFT IN

PLANE

°
60

M12 Mortar Bed

ST4 Class
150

Concrete
Foundation
and Haunch

50 125 175

DRAWING NO REV
BLOCK PAVED OVERRUN CONSTRUCTION DETAIL
NAC/211/OVR A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Shared Space/Level Surface Streets BLOCK PAVED TRANSITION Connector/Local Residential Streets
(TYPE 3 or 4) (PREFERRED 10M LONG) (TYPE 1 or 2)

1. All dimensions in millimetres. (This


Type 3 or 4a Type 4b Type 1 or 2 drawing is not to scale)
Carriageway Carriageway Carriageway
Construction to Construction to Construction to 2. New Kerbing details to comply with
Kerb Type CS Kerb Type CS
drawing as stated
Table: NAC/001/CD Table: NAC/001/CD Table: NAC/001/CD
50 50
3. Full Construction Information for
Carriageway to Table NAC/001/CD

60

60
85
4. Full Construction Information for Footway
to Table NAC/001/CD
M12 Mortar Bed
(This drawing is not to scale)
M12 Mortar Bed

ST4 Class ST4 Class


150

150
Concrete Concrete
Foundation Foundation
and Haunch and Haunch

150 125 150 150 125 150

Service Strip or Type 3 or 4a Carriageway


Landscaping or other Construction to Table: NAC/001/CD
to Architect's design Footway Construction
to Table: NAC/001/CD
BLOCK PAVING
Reflective
SURFACE COURSE Bollards

BINDER COURSE Kerb Type CS


5.5m
Shared
BASE COURSE Surface

SUB-BASE Type 1 or 2
Carriageway
Preferred 10m Construction to
SAND BEDDING Table:
NAC/001/CD
Type 4b
TOP SOIL & GRASS SEED Kerb Type FT through footpath Carriageway Kerb Type CS
to provide flush finish Construction to
Table:
NAC/001/CD

DRAWING NO REV
TRANSITION FEATURE TO A TYPE 3 OR 4 STREET
NAC/212/TRCS A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)
2.0m WIDE FOOTWAY OFF STREET PARKING BAYS BITUMINOUS ACCESS ROAD
2. New Kerbing details to comply with
drawing as stated

3. Full Construction Information for


Carriageway to Table NAC/001/CD
Kerb Type RT Type 4a Carriageway Type 4b Carriageway
Footway Construction Type 3 Carriageway
to Table: NAC/001/CD Type 4b Carriageway Construction to Construction to 4. Full Construction Information for Footway
Kerb Type HB1 Type 4a Carriageway Construction to Table: NAC/001/CD
Construction to Construction to Table: NAC/001/CD Table: NAC/001/CD to Table NAC/001/CD
50 Table: NAC/001/CD
50

Table: NAC/001/CD
25
(This drawing is not to scale)
30

60

50

100
M12 Mortar Bed

85
ST4 Class
Concrete
100

195

Foundation
and Haunch

300

M12 Mortar Bed

M12 Mortar Bed


150

ST4 Class
Concrete ST4 Class

150
Foundation Concrete
and Haunch Foundation
and Haunch

175 125 50

150 125 150

Carriageway Construction
SURFACE COURSE
Road Type Sub-Base Base Course Binder Course Surface Course
BINDER COURSE 3 Shared 300mm Granular 80mm Dense Base Course Asphalt 50mm Dense Binder Course Asphalt 40mm Hot Rolled Asphalt Surface
Space Sub-base Type 1 Concrete (Recipe Mixture (cl 906), Concrete (Recipe Mixture) (cl 906), Course (Recipe Mixture) (cl 910),
Streets (cl 803) (AC 32 dense base 100/150 rec) (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with Red
BASE COURSE 14/20mm Coated Chipping 40/60
130mm Dense Binder Course Asphalt Concrete (Recipe Mixture) (cl 906), PSV 60 (cl 915)
(AC 20 dense bin 100/150 rec)
SUB-BASE
4 300mm Granular 80mm Dense Binder Course Asphalt 40mm Hot Rolled Asphalt Surface
Sub-base Type 1 Concrete (Recipe Mixture) (cl 906), Course (Recipe Mixture) (cl 910),
SAND BEDDING (a) (cl 803) (AC 20 dense bin 100/150 rec) (HRA 30/14 F surf 40/60) with Red
Level 14/20mm Coated Chipping 40/60
Surface PSV 60 (cl 915)
FORMATION Streets
4 400mm Granular Sub-base Type 1 (cl 803) 50mm Bedding Layer of Sharp Sand 200 x 100 x 80mm thick Concrete
or Crushed Rock (Appendix 7/1) Rectangular Block Paving (cl 1043)
(b) or 200 x 100 x 65mm Concrete
Pavers (cl 1107)

DRAWING NO REV
STANDARD FOOTWAY/OFF STREET PARKING BAYS CONSTRUCTION
NAC/213/PAR A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Electricity

Cable TV/Communications

Gas

Water

Telecoms

450 295 295 270 260 430


250-350mm

250-350mm

Carriageway
450mm LV

600mm

750-900mm
450-1200mm HV

RECOMMENDED POSITIONING OF UTILITY DRAWING NO REV


APPARATUS IN A 2 METRE FOOTWAY
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF
NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY. NAC/301/SER A
ADJACENT
FOOTWAY/VERGE
Class D400 gully with min clear
opening 450 x 450, grating laid
ROAD LEVEL perpendicular to carriageway

150 dia outlet

Two course of class B


375/450
engineering brickwork
150 min
to be provided on a
minimum of 3 sides as
a seating for gully
frame or 4 sides where
150
750/900

no kerb is present

2000

450 x 900 or 375 x 750


Polypropylene Gully Pot

PRECAST CONCRETE TRAPPED STREET GULLY DRAWING NO REV


450 mm NOMINAL BORE
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF
NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY. NAC/302/GUL A
1. All dimensions in millimeters.

675x675mm DIA DOUBLE TRIANGULATED COVER AND


MANHOLE COVER BEDDED IN CLASS M1 TABLE 1B - TYPE `B' MANHOLE (0-3m d'p) 2. Pipelines and manholes to be
CEMENT MORTAR IN ROADS AND OTHER constructed in accordance with the
FRAME TO BS EN124 & BS7903 (Cl 4.2.33) CLASS D 400 HARD SURFACES. 150mm GRADE C25 MANHOLE DIMENSIONS (mm)
675 SQ.
IN CARRIAGEWAYS, (INCLUDING PEDESTRIAN
CLEAR OPENING CONCRETE SURROUND IN ALL OTHER AREAS. `Sewers for Scotland' 3rd edition WRC
STREETS), HARD SHOULDERS AND PARKING AREAS. Pipe Dia Rocker publication in conjunction with Scottish
Mh Dia
CLASS B 125 IN ALL OTHER AREAS. (largest diameter) pipe length
Water, office specification and
150 1200 600 requirements.
20mm THICK CEMENT MORTAR 225-300 1200 600

DIRECTION
OF FLOW
RENDERING IN TWO COATS
375-450 1350 600 3. Rocker pipes shall be used for pipes less

675mm Max
ROCKER PIPE LENGTH
225 Th'k CLASS 'B' ENGINEERING BRICKWORK PRECAST COVER SLAB TO BE (SEE TABLE 1B) than 750 nominal diameter entering and
MIN. 1 COURSE, MAX. 3 COURSES. BEDDED ON CEMENT MORTAR FIRST JOINT TO BE AS CLOSE TO leaving manholes. Maximum length not
150mm THICK TYPE `1' SEATING MANHOLE BASE AS POSSIBLE. to exceed 600mm uno refer to tables 1B.
SLAB WITH 675x675 ECCENTRIC THIS SHOULD NOT EXCEED A CLEAR
ACCESS HOLE POSITIONED TO 100mm FROM CONCRETE BASE PIPE JOINT WITH CHANNEL 4. All precast concrete units to be reinforced
ALIGN WITH DOUBLE STEP IRONS AND MUST NOT BE ENCASED IN TO BE LOCATED MIN 100mm
THE CONCRETE BASE INSIDE FACE OF MANHOLE
and conform to b.s.5911. Step irons to
PRECAST CONCRETE CHAMBER SECTIONS BS EN 13101 double rungs).
PRECAST UNITS TO BS 8911; PART 200
P.C RINGS
JOINTS/LIFTING EYES SEALED WITH (to BS 5911-3 (Cl 4.2.30) (CL:4.2.28) BEDDED WITH MORTAR,
DIA SEE TABLE 1B
APPROVED BITUMINOUS MATERIAL AND COVER SLAB TO BE BEDDED WITH 5. All joints
PROPRIETARY between
BITUMEN p.c.
OR RESIN units to be made
MASTIC
FALL FALL
MORTAR, PROPRIETARY BITUMEN OR SEALANT.watertight by the application of cement
RESIN MASTIC SEALANT. LIFTING EYES TO BE SEALED
mortar. "Tokstrip" or other similar
CHAMBER HEIGHT PLASTIC COATED DOUBLE STEP IRONS approved equal.
(NOT LESS THAN 900mm) 250 (RUNGS) TO BS EN13101(cl4.2.34)
SHOWN INDICATIVELY, EXACT FALL FALL
6. The lowest chamber ring bearing on the
POSITIONS TO BE CONFIRMED ON SITE.
foundation and the highest chamber ring
GRANOLITHIC SCREED TOPPING TO 225mm Min receiving the cover slab shall have plain
BE BROUGHT UP TO A DENSE SMOOTH BENCHING 500mm Min BENCHING MINIMUM WIDTH OF ends and be bedded in cement mortar.
Min 450mm BELOW LL
FACE NEATLY SHAPED AND FINISHED BOTTOM STEP IRON BENCHING FOR LANDING FA FA
LL
TO ALL BRANCH CONNECTIONS. AREA TO BE 225mm PLASTIC COATED DOUBLE STEP IRONS
BENCHING SLOPE 7. Manhole access hole and step iron
(MIN. 20mm THICK) (RUNGS) TO BS EN 13101 SHOWN
TO BE 1:10-1:30 positions to be located to give greatest
INDICATIVELY, EXACT POSITIONS TO
CEMENT MORTAR FILLET BE CONFIRMED ON SITE. free area of benching immediately below
THE BOTTOM PRECAST MANHOLE MINIMUM WIDTH OF BENCHING
RING TO BE BUILT INTO BASE
FIRST JOINT TO BE AS CLOSE TO 8. Manhole covers to be class D400 to BS
MANHOLE BASE AS POSSIBLE FOR LANDING AREA TO BE 500mm
CONCRETE MINIMUM 75mm EN 124 double triangular cover & frame
AS NOTED ABOVE
DISTANCE BETWEEN TOP OF PIPE JOINT WITH CHANNEL 150mm deep with 675mm sq. opening in

DIRECTION
OF FLOW
ALL INSITU CONCRETE TO BE PIPE AND UNDERSIDE OF TO BE LOCATED MIN 50mm
ROCKER PIPE LENGTH ductile iron. and bearing the registered
200

GEN3 WITH SULPHATE RESISTANT PRECAST SECTION TO BE INSIDE FACE OF MANHOLE


(SEE TABLE 1B) certification mark of the british standards
CEMENT UNLESS STATED OTHERWISE. MIN 50mm TO MAX 300mm
1 LAYER A252 MESH. 40mm COVER institution.
INVERTS TO BE FORMED
75

BLINDING CONCRETE GEN1 USING CHANNEL PIPES


9. Step irons not to protrude into 675
square access opening in shaft cover
slab.

NOTE: MANHOLE & SILT TRAP COVERS


10. Precast concrete cover slabs to be heavy
MIN. COVER TO PIPES WITHOUT CONCRETE PROTECTION: duty.
ADOPTABLE ROADS/
1.2m WITHIN ROADWAY, 0.9m WITHIN PARKING.
PRIVATE DUCTILE IRON HEAVY DUTY DOUBLE
PIPES WITH LESS THAN THE MIN. COVER SHOULD
CARRIAGEWAY/ TRIANGULAR CLASS D400 11. Top step iron to be located maximum
PARKING: BY PETER SAVAGE Ltd. OR SIMILAR.
BE PROTECTED WITH 150mm CONCRETE SURROUND 675mm from the finished manhole cover
WITH FLEXIBLE JOINTS AT EACH PIPE JOINT.
PEDESTRIAN AND DUCTILE IRON CLASS B125 MEDIUM level.
CONCRETE PROTECTION TO uPVC PIPES: LANDSCAPED AREAS: DUTY BY PETER SAVAGE Ltd OR SIMILAR.
150 th'k CONCRETE SLAB INSTALLED ABOVE CROWN 12. Concrete foundation to be scabbled
OF PIPE IN ACCORDANCE WITH Sco.W. DETAILS. MANHOLE COVERS WITHIN BUILDINGS TO BE DOUBLE
SEALED COVERS before placing granolithic finish.
ALL PIPES TO HAVE A 150mm THICK CLASS 'S' ALL MANHOLE COVERS TO HAVE BS `KITEMARK'
GRANULAR PIPE SURROUND UNLESS NOTED OTHERWISE. 13. All metalwork to be hot-dip galvanised to
BS 729 after manufacture.

14. Buried manholes - covers to be set below


ground level (600mm in fields and
300mm in gardens) and covered with a
sheet of heavy duty polthene, held in
place with waterproof protective tape.

TYPE B MANHOLE - MAXIMUM DEPTH 3 METRES DRAWING NO REV

(to be used within carriageway)


NAC/303/MH1 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimeters.

2. Pipelines and manholes to be


675x675mm DIA DOUBLE TRIANGULATED COVER AND
MANHOLE COVER BEDDED IN CLASS M1 constructed in accordance with the
CEMENT MORTAR IN ROADS AND OTHER
FRAME TO BS EN 124: 1994 (Cl 4.2.30) CLASS D 400 IN
675 SQ. HARD SURFACES. 150mm GRADE C25 `Sewers for Scotland' 3rd edition WRC
CARRIAGEWAYS, (INCLUDING PEDESTRIAN STREETS),
HARD SHOULDERS AND PARKING AREAS.
CLEAR OPENING CONCRETE SURROUND IN ALL OTHER AREAS. publication in conjunction with Scottish
CLASS B 125 IN ALL OTHER AREAS. TABLE 1A - TYPE 'A' MANHOLE (3-6m d'p) Water, office specification and
MANHOLE DIMENSIONS (mm) requirements.
20mm THICK CEMENT MORTAR Pipe Dia Rocker
PRECAST CONCRETE CHAMBER SECTIONS
RENDERING IN TWO COATS Mh Dia (to BS 5911: PART 200 (Cl 4.2.28)
(largest diameter) pipe length
AND COVER SLAB TO BE BEDDED WITH
3. Rocker pipes shall be used for pipes less
225 Th'k CLASS 'B' ENGINEERING BRICKWORK 150-300 1200 600 MORTAR, PROPRIETARY BITUMEN OR than 750 nominal diameter entering and

DIRECTION
RESIN MASTIC SEALANT. LIFTING EYES TO BE SEALED leaving manholes. Maximum length not

OF FLOW
MIN. 1 COURSE, MAX. 3 COURSES. PRECAST COVER SLAB TO BE
BEDDED ON CEMENT MORTAR ROCKER PIPE LENGTH
(SEE TABLE 1B)
to exceed 600mm uno refer to tables 1B.
150mm THICK TYPE `1' SEATING PIPE JOINT WITH CHANNEL
SLAB WITH 675x675 ECCENTRIC TO BE LOCATED MIN 50mm
ACCESS HOLE POSITIONED TO INSIDE FACE OF MANHOLE FIRST JOINT TO BE AS CLOSE TO 4. All precast concrete units to be reinforced
ALIGN WITH DOUBLE STEP IRONS MANHOLE BASE AS POSSIBLE.
THIS SHOULD NOT EXCEED A CLEAR and conform to b.s.5911. Step irons to
100mm FROM CONCRETE BASE BS EN 13101 double rungs).
1050Ø u.n.o BY LOCAL AUTHORITY PRECAST CONCRETE CHAMBER SECTIONS AND MUST NOT BE ENCASED IN
(to BS 5911: PART 200 (Cl 4.2.28) THE CONCRETE BASE
AND COVER SLAB TO BE BEDDED WITH 5. All joints between p.c. units to be made
MORTAR, PROPRIETARY BITUMEN OR L
RESIN MASTIC SEALANT. LIFTING EYES TO BE SEALED
FA
L
watertight by the application of cement
mortar. "Tokstrip" or other similar
PLASTIC COATED DOUBLE STEP IRONS
approved equal.
250

FALL
(RUNGS) TO BS EN 13101 SHOWN PRECAST CONCRETE REDUCING SLAB. FALL
MANHOLES LESS THAN 1.5m Dia REDUCING
INDICATIVELY, EXACT POSITIONS TO
SLAB NOT TO BE USED AND PC RINGS TO
6. The lowest chamber ring bearing on the
BE CONFIRMED ON SITE.
CONTINUE UP TO COVER SLAB foundation and the highest chamber ring
receiving the cover slab shall have plain
FALL FALL
ends and be bedded in cement mortar.

7. Manhole access hole and step iron


positions to be located to give greatest
PRECAST CONCRETE CHAMBER SECTIONS SEE TABLE 1A LL free area of benching immediately below
LL FA
(to BS 5911: PART 200 (Cl 4.2.28) PLASTIC COATED DOUBLE STEP IRONS FA
AND COVER SLAB TO BE BEDDED WITH (RUNGS) TO BS EN 13101 SHOWN
MORTAR, PROPRIETARY BITUMEN OR INDICATIVELY, EXACT POSITIONS TO 8. Manhole covers to be class D400 to BS
RESIN MASTIC SEALANT. LIFTING EYES TO BE SEALED BE CONFIRMED ON SITE. (a) EN 124 double triangular cover & frame
LL
REDUCING SLAB
Min 2000 FROM
UNDERSIDE OF

FA MINIMUM WIDTH OF 150mm deep with 675mm sq. opening in


250

BENCHING FOR LANDING ductile iron. and bearing the registered


AREA TO BE 225mm
(z) certification mark of the british standards
Min 450mm BELOW MINIMUM WIDTH OF BENCHING FIRST JOINT TO BE AS CLOSE TO institution.
BOTTOM STEP IRON FOR LANDING AREA TO BE 500mm MANHOLE BASE AS POSSIBLE
225mm Min AS NOTED ABOVE
500mm Min BENCHING BENCHING 9. Step irons not to protrude into 675
PIPE JOINT WITH CHANNEL

DIRECTION
ROCKER PIPE LENGTH square access opening in shaft cover

OF FLOW
CEMENT MORTAR FILLET TO BE LOCATED MIN 50mm (SEE TABLE 1B)
INSIDE FACE OF MANHOLE slab.
100

ALL INSITU CONCRETE TO BE 10. Precast concrete cover slabs to be heavy


GEN3 WITH SULPHATE RESISTANT duty.
CEMENT UNLESS STATED OTHERWISE.
1 LAYER A252 MESH. 40mm COVER
75 200

11. Top step iron to be located maximum


675mm from the finished manhole cover
INVERTS TO BE FORMED
USING CHANNEL PIPES BLINDING CONCRETE GEN1
level.
NOTE: MANHOLE & SILT TRAP COVERS
MIN. COVER TO PIPES WITHOUT CONCRETE PROTECTION:
ADOPTABLE ROADS/ 12. Concrete foundation to be scabbled
1.2m WITHIN ROADWAY, 0.9m WITHIN PARKING.
PRIVATE DUCTILE IRON HEAVY DUTY DOUBLE before placing granolithic finish.
CARRIAGEWAY/ TRIANGULAR CLASS D400
PIPES WITH LESS THAN THE MIN. COVER SHOULD
BE PROTECTED WITH 150mm CONCRETE SURROUND
PARKING: BY PETER SAVAGE Ltd. OR SIMILAR.
WITH FLEXIBLE JOINTS AT EACH PIPE JOINT. 13. All metalwork to be hot-dip galvanised to
PEDESTRIAN AND DUCTILE IRON CLASS B125 MEDIUM
LANDSCAPED AREAS: DUTY BY PETER SAVAGE Ltd OR SIMILAR.
BS 729 after manufacture.
CONCRETE PROTECTION TO uPVC PIPES:
150 th'k CONCRETE SLAB INSTALLED ABOVE CROWN
OF PIPE IN ACCORDANCE WITH Sco.W. DETAILS. MANHOLE COVERS WITHIN BUILDINGS TO BE DOUBLE 14. Buried manholes - covers to be set below
SEALED COVERS
ALL PIPES TO HAVE A 150mm THICK CLASS 'S' ALL MANHOLE COVERS TO HAVE BS `KITEMARK' ground level (600mm in fields and
GRANULAR PIPE SURROUND UNLESS NOTED OTHERWISE. 300mm in gardens) and covered with a
sheet of heavy duty polthene, held in
place with waterproof protective tape.

TYPE A MANHOLE - DEPTH 3 TO 6 METRES DRAWING NO REV

(to be used within carriageway)


NAC/304/MH2 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimeters.

2. Pipelines and manholes to be


constructed in accordance with the
`Sewers for Scotland' 3rd edition WRC
publication in conjunction with Scottish
Water, office specification and
requirements.

CLASS 1 CEMENT MORTAR 600X600 COVER AND FRAME TO BE 3. Rocker pipes shall be used for pipes less
HUNCHING TO MANHOLE 600 BEDDED ON MORTAR TO BS EN124:2015
CL:4.2.30 (REFER TO MANHOLE
than 750 nominal diameter entering and
COVER AND FRAME
SCHEDULE FOR COVER TYPE) leaving manholes. Maximum length not
C.L. to exceed 600mm uno refer to tables 1B.

4. All precast concrete units to be reinforced


and conform to b.s.5911. Step irons to
NOTE BS EN 13101 double rungs).
STEP IRONS TO BE PLASTIC
PIPES ENTERING MANHOLES SHALL
ENCAPSULATED DOUBLE STEPS
PRECAST UNITS TO BS 8911; PART 200 HAVE A FLEXIBLE JOINT WITHIN 5. All joints between p.c. units to be made
TO BS 1247 (CL:4.3.31).
(CL:4.2.28) BEDDED WITH MORTAR, 750 1-3 COURSES CLASS B ENGINEERING BRICKS TO 600mm OF THE INSIDE FACE OF watertight by the application of cement
PROPRIETARY BITUMEN OR RESIN MASTIC BS 3921 AND BUILT WITH CLASS 1 MORTAR. MANHOLE IN-SITU THE MANHOLE JOINTING WITH A
mortar. "Tokstrip" or other similar
SEALANT. ALTERNATIVELY CONCRETE BLOCK OR PRECAST CONCRETE BASE SHORT 'ROCKER PIPE'.
CONCRETE COVER SEATING RINGS. approved equal.
300

6. The lowest chamber ring bearing on the


foundation and the highest chamber ring
STEP IRONS TO BE PLASTIC receiving the cover slab shall have plain
300

SEALANT TO JOINTS
ENCAPSULATED DOUBLE STEPS ends and be bedded in cement mortar.
REFER TO MANHOLE
TO BS 1247 (CL:4.3.31). DOWNTURN IN
GENERAL NOTE 7.
OUTLET PIPE
INFLOW 7. Manhole access hole and step iron
I.L.
OUTFLOW INFLOW OUTFLOW positions to be located to give greatest
free area of benching immediately below
150mm CONCRETE
450

400

SURROUND TO EXTEND Ø VARIES 8. Manhole covers to be class D400 to BS


90° LONG RADIUS REST 100
2.0m BELOW GROUND EN 124 double triangular cover & frame
BEND OUTLET PIPE
LEVEL.
DOWNTURN WARDS 150mm deep with 675mm sq. opening in
ductile iron. and bearing the registered
250

certification mark of the british standards


institution.

ALL IN-SITU CONCRETE TO BE 9. Step irons not to protrude into 675


GRADE C20 WITH SULPHATE square access opening in shaft cover
RESISTANT CEMENT UNLESS slab.
OTHERWISE STATED. TYPICAL CATCH PIT TYPICAL CATCH PIT
PRECAST CONCRETE MANHOLE DETAIL PRECAST CONCRETE MANHOLE DETAIL 10. Precast concrete cover slabs to be heavy
duty.
SECTION C-C PLAN SECTION D-D
DEPTH FROM GROUND LEVEL TO SOFFIT 1.5m - 3.0m DEPTH FROM GROUND LEVEL TO SOFFIT 1.5m - 3.0m 11. Top step iron to be located maximum
(Scale 1:20) (Scale 1:20) 675mm from the finished manhole cover
level.

12. Concrete foundation to be scabbled


before placing granolithic finish.

13. All metalwork to be hot-dip galvanised to


BS 729 after manufacture.

14. Buried manholes - covers to be set below


ground level (600mm in fields and
300mm in gardens) and covered with a
sheet of heavy duty polthene, held in
place with waterproof protective tape.

CATCHPIT DRAWING NO REV

(to be used outwith carriageway)


NAC/305/CTP A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
600 400
300

B 225 B

150

45

150

invert level

SECTIONAL ELEVATION AA

1000

150

A A

900

150

SECTIONAL PLAN BB

DRAWING NO REV
RODDING EYE DETAIL
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF
NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY. NAC/306/ROD A
1. All dimensions in millimeters.

2. This drawing is to be read in conjunction


with Appendix 5/1.

3. Dimension X is the external diameter of


the pipe.

4. The minimum or maximum width of the


trench applies on and below a line
X+600 max X+600 max X+600 max 300mm above the outside top of the pipe.
Above the 300mm line, the trunch backfill
X+300 min material shall be as described in Clause
505 of SHW.

5. The concrete bed or surround may


extend to the sides of the trench or be of
minimum width. Class 8 material is to be
300

300
used to fill any voids so formed.

X 150
6. For Type Z trench the concrete cover

X/25
may be formed to a radius batter or
X/4
X

X
horizontal surface. Minimum cover of
concrete shall be 150mm.

100 min
75 min

X+X/4

100 min
X/6

X/4
X/6
X+200 min

TYPE A TYPE F TYPE Z

DRAWING NO REV
CARRIER PIPE DETAIL - PIPE BEDDING DETAIL
NAC/307/CPD A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. New Kerbing details to comply with


drawing as stated
Cover And Frame B125 Refer To NAC/302/GUL Cover And Frame B125
Loading (12.5t) For Gully Details Loading (12.5t) 3. Full Construction Information for
Restriction Access Cap Restriction Access Cap
Rodding Eye Carriageway to Table NAC/001/CD

4. Full Construction Information for Footway


to Table NAC/001/CD
150mm Deep Concrete 150mm Deep
Collar Grade ST4
150mmØ Outlet Concrete Collar 5. This drawing to be read in junction with
Grade ST4 drawing NAC/309/FLT2
SHAFT SHAFT 450mm Diameter
Shuttered Shuttered
450mm Diameter
External Ribs External Ribs
6. Gully detail to drawing NAC/302/GUL
150mm Concrete
Surround
100mm min
7. Acceptable Backfill material to be
Top 150Ø Porous Top 150Ø Porous
Covering Layer Pipe Pipe
material excavated from within the site or
imported on to the site which meets the
Type B Filter Material requirements of S.H.W. Table 6/1 and
Inlet / Outlet Pipes To Be Cut
Into Shaft
To SHW Clause 505 contract specific Appendix 6/1 for
acceptability for use in the permanent
works.
300

(This drawing is not to scale)


150mm Concrete
Surround

Depth To Be Determined
150

1000
Concrete Grade C20 (SHW)

Note Base Level Of


Catchpit To Be 300mm
Below Outlet Filter Drain
Carrier
Area Disturbed Under Catchpit
For Rodding Eye Pipe To Be 150mm Concrete Surround
Filled With Concrete Grade ST1 To 150mm Above Incoming /
Outgoing Pipes

Inlet / Outlet Pipes To Be


Cut Into Shaft

300
Bottom 150Ø Porous Type A Or C Filter Material Bottom 150Ø
Pipe To SHW Clause 505 Porous Pipe

150
INLET FILTER TRENCH CATCHPIT DETAIL OUTLET FILTER TRENCH CATCHPIT DETAIL
1000
Concrete Grade C20 (SHW)

Note Base Level Of Catchpit


To Be 300mm Below Outlet
Filter Drain Carrier

DRAWING NO REV
FILTER TRENCH CONSTRUCTION - SECTION
NAC/308/FLT1 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. New Kerbing details to comply with


drawing as stated

3. Full Construction Information for


Carriageway to Table NAC/001/CD
2m Service Strip

Inspection Chamber
1.25m trench

4. Full Construction Information for Footway


to Table NAC/001/CD

5. This drawing to be read in junction with


Carrier Pipe
drawing NAC/308/FLT1

6. Gully detail to drawing NAC/302/GUL


Rodding Eye
7. Acceptable Backfill material to be
material excavated from within the site or
imported on to the site which meets the
requirements of S.H.W. Table 6/1 and
contract specific Appendix 6/1 for
acceptability for use in the permanent
Footpath

works.

(This drawing is not to scale)


Carriageway

Gully

DRAWING NO REV
FILTER TRENCH CONSTRUCTION - PLAN
NAC/309/FLT2 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
PULL HANDLE
EYE BRACKET FOR
OPERATING ROPE

1. All dimensions in millimeters.

TABLE 2. All Hydrobrakes should provide the flow


capacities indicated on drainage layout
INTERNAL INTERNAL
DIAMETER DIAMETER `A' mm
drawings.
`X' mm `Z' mm `H' mm `D' mm `W' mm
OF LOWER OF UPPER
PIPE (mm) PIPE (mm)
3. The minimum orifice size for all
150 150 150 150 375 300 652 1156 hydrobrake to be 75mm diameter and
PIVOTING BY-PASS DOOR OPERATING calculations provided by supplier to
150 225 150 150 375 300 704 1239
STEEL ROPE engineer for approval.
150 300 150 150 375 300 748 1328

150 375 250 150 375 400 880 1610

150 450 250 150 375 400 921 1693


HYDRO-BRAKE FLOW
525 375
CONTROL FITTED WITH 150 250 150 400 962 1775

PIVOTING BYPASS DOOR 150 600 275 150 375 425 1028 1908

225 225 150 375 300 736 1322


SEE TABLE 150

225 300 150 150 375 300 781 1411

SEE TABLE 225 375 150 375 400 922 1693


250

IN FLOW 225 450 250 150 375 400 963 1776

OUT FLOW 225 525 250 150 375 400 1004 1858

225 600 275 150 375 425 1071 1991

300 300 150 150 375 300 825 1500


OUTLET SPIGOT
300 375 250 150 375 400 966 1782

300 450 250 150 375 400 1007 1865

300 525 250 150 375 400 1048 1947

300 600 275 150 375 425 1115 2080

INTAKE
SUMP
PIVOTING
PRECAST CONCRETE HYDRO-BRAKE MANHOLE BYPASS DOOR

JOINT TO BE AS CLOSE AS POSSIBLE FIXING LUGS WITH MASONRY STUD


TO FACE OF MANHOLE TO PERMIT ANCHOR FIXING BOLTS
SATISFACTORY JOINT &
SUBSEQUENT MOVEMENT NEOPRENE RUBBER GASKET

IN FLOW OUT FLOW INTAKE


FLOW

CONCRETE GRADE C20 MOUNTING


BLOCK
HYDRO-BRAKE FLOW CONTROL FITTED
WITH PIVOTING BY-PASS DOOR.

PLAN ON HYDRO-BRAKE MANHOLE SECTION ON HYDRO-BRAKE

DRAWING NO REV
HYDROBRAKE CHAMBER
NAC/310/HCH A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

(This drawing is not to scale)

3.5m wide reinforced earth


maintenance strip/safety bench
using erosa web GW100/30 or
similar pinned in place using ab
pin 300/4 (4) per square meter
(or similar) voids to be filled with
Submerged planting to landscape Above permanent water level bentomat class 4 material in accordance
architects specifications to be covered with 200mm of topsoil. with SHW Series 600 Clause
20 620 and grass seeded.
0.5% AEP Plus climate
change water level 1

500
1
Permanent Water Level Liner to be buried in anchor
500 trench and brought flush to
surface.
4
1 Exposed margins and banks to be sown
with a fescue-based seed mix specification
Pond base Emergant planting to landscape to be confirmed by landscape architect.
architacts specifications.

Pond to be lined with macafferi bentomat


ss100 or similar approved.
Bentomat to be covered with 200mm of
subsoil below permanent water level.

DRAWING NO REV
TYPICAL SECTION THROUGH POND MARGIN
NAC/311/PS A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. For Inlet detail refer to drawing


NAC/313/PI

3. For Outlet detail refer to drawing


3.5m wide NAC/314/PO
Grasscrete maintenance track
(This drawing is not to scale)
76mm thick Grasscrete type GC3
On 20mm thick sand blinding layer
On 150mm thick Type 1 to cl.803

1:4 max slope to Max 1:2 slope to


SUDS Basin proposed Ground
level
all
utf
0 0O
1:1 Non-woven Geotextile Formation to maintenance

300
0 Ø (Terram 1000 or equal approved) access to be well compacted
30

Ø 1:2
00 In
let
rete
3.5m wide Grassc
Hydro-brake chamber maintenance trac
k TYPICAL SECTION - GRASSCRETE MAINTENANCE TRACK
Flow restricted to 21.2 l/s

For Outlet detail


refer to drawing
NAC/314/PO For Inlet detail
refer to drawing
NAC/313/PI

TYPICAL PLAN - SUDS BASIN

3.5m wide 3.5m wide


Grasscrete maintenence track 1.2m 1:4 side slope Bottom of Basin 1:4 side slope 1.2m Grasscrete maintenence track

Post/Wire
Fence
Min 300mm Freeboard
1:40 FALL
1:20 FALL
Max 1:2 slope
Maximum Storage Level
to proposed
500

500
Ground Level
1m Approx Max 1:2 slope
Datum to proposed
500 500 Ground Level
Compacted general FALL Level FALL
backfill material

Anchor trench for membrane 300 mm thick layer of Topsoil Anchor trench for membrane
to be constructed around full to be constructed around full
150

perimeter of basin at 150mm perimeter of basin at 150mm


above High Water level Impermeable Liner to be laid on sand above High Water level
Low Flow Channel
bedding with no sharp objects which
could cause damage to liner.
Alternatively, a protective geotextile
fleece could be laid below the liner
(min 300g/sp.m)

TYPICAL SECTION A-A THROUGH


SUDS BASIN

DRAWING NO REV
TYPICAL SECTION THROUGH BASIN
NAC/312/PB A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. This drawing should be read in


conjunction with drawings NAC/312/PB,
3m x 2m x 0.3m deep Reno NAC/314/PO and NAC/315/PSG
mattress erosion protection
(This drawing is not to scale)

10°
A A
Rocker

2585
2130

3190
1625
825mm Ø Inlet pipe
pipe

300
Plan
300

3.5m Wide reinforced Ground level to be raised


earth maintenance strip locally around pond inlet.

B Safety grille, refer to


detail NAC/315/PSG

600
3m x 2m x 0.3m deep Reno
mattress erosion protection

1625
Rocker
825mm Ø Inlet pipe
pipe
200

600
Permanent water level

300
300
500

150mm Concrete
protection where cover is
less than 900mm 2585
B 50mm Sand Macafferi bentomat ss100
3190
300 300 2500
bedding layer. or similar approved. Line
75mm Blinding to be brought up rear of
Section through A-A concrete. headwall above 1:200 Section through B-B
year water level.

DRAWING NO REV
DETENTION POND INLET HEADWALL DETAIL
NAC/313/PI A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. This drawing should be read in


conjunction with drawings NAC/312/PB,
NAC/313/PI and NAC/315/PSG

(This drawing is not to scale)

300

275
A A
Rocker

1600

1000
450mm Ø Outlet pipe
pipe

300
Plan

3.5m Wide reinforced


earth maintenance strip
Ground level to be raised
B locally around pond outlet.

Safety grille, refer to


Safety grille, refer
detail NAC/315/PSG

600
to detail.

1350
Permanent water level Rocker
450mm Ø Outlet pipe
pipe
525

300
300

500
150mm Concrete
75mm Blinding protection where cover is
Macafferi bentomat ss100
300 300
or similar approved. Line concrete. B less than 900mm
1600
to be brought up rear of 1575 300 300
headwall above 1:200 Section through A-A
Section through B-B year water level.

DRAWING NO REV
DETENTION POND OUTLET HEADWALL DETAIL
NAC/314/PO A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. This drawing should be read in


conjunction with drawings NAC/312/PB,

100
NAC/313/PI and NAC/314/PO

(This drawing is not to scale)


Steel plate 80mm x 12mm x W
long bolted to the headwall at
maximum 300mm centres.

Intermediate bracket hinges to A A Screen to be secured to wall


suit pipe diameter not greater plate connectors by heavy-duty
than 500mm centres. padlock on one side

50mm x 12mm Flat bars at


Two steel connectors 60mm x 40mm 100mm spacing.
x 20mm drilled 22mm and joined Additional support
together by M20 bolt to form gate M20 bolt through C/W
connectors if required. Wall plate.
hinge on one side. washers under bolt head and
nut nylon washer between
70mm x 70mm x 10mm Steel faces.
angle screen frame. 40
Elevation Fillet weld.

60
40
Ø22mm drilled.

825mm Ø Pipe external diameter taken as 985mm Screen frame.


450mm Ø Pipe external diameter taken as 575mm
Detail of connector
External diameter based on available pipe dimensions to be confirmed on site

Pipe wall.
100 minimum

Two steel connectors 60mm x 40mm x 20mm


drilled 22mm and joined together by M20 80mm x 12mm Wall plate.
bolt to form gate hinge on one side.
70mm x 70mm x 10mm Steel
Width = Pipe outside diameter + 270mm
angle screen frame.

Note: mild steel fabrication 50mm x 12mm Flat bars at


to be hot dip galvanised to 100mm spacing.
Section through A-A
BS EN 1461

DRAWING NO REV
DETENTION POND OUTFALL SAFETY GRILLE DETAIL
NAC/315/PSG A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Minimum 3500 clear opening

3.6m Universal hanging field gate 1. All dimensions in millimetres. (This


by Jacksons Fencing or similar drawing is not to scale)
approved.
(This drawing is not to scale)

Round timber 125 dia. at top x


2320 long straining post to be
provided at all ends.

Typical access gate detail Signage to be attached to fence

Not to exceed 150m


Round timber straining post 125 dia.
at top x 2320 long at all changes of
3500 maximum
direction or acute changes in level.
Maximum spacing of 150m in
Six line zinc coated straight runs.
wires 4 dia.
75
230 250 250

1275
40 x 4 dia. Straining device
Round timber 125 dia. staples on each wire
150

150

at top x 2320 long


straining post to be
170

provided at all ends.


450

450
595

1045
600mm x 600mm Round timber strut 80 dia. x
Concrete Foundation 2320 long (on level ground).
Grade ST2
Round intermediate timber
posts 80 dia. at top x 1870
long girth 190-220 at 3500
max intervals.

Typical perimeter fence detail

DRAWING NO REV
DETENTION POND/BASIN PERIMETER FENCE DETAIL
NAC/316/PPF A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

(This drawing is not to scale)

150mmØ perforated
pipe between chambers.

Polypropylene silt trap with open


grill cover to allow surface water
150mmØ outlet to
from embankment to enter prior proposed mainline
to discharging to proposed surface system

surface water network.


SILT TRAP
B

450mm x 450mm
CONCRETE SLABS TO
PREVENT EROSION
DRAWING NO REV
STANDARD WET SWALE/CARRIAGEWAY CONSTRUCTION
NAC/317/SWP A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Kerb Type FT Kerb Type HB1

100 600 250 600 450 Carriageway


Construction to Table:
CD1
100mm Turf/Topsoil 1. All dimensions in millimetres. (This
80
25
drawing is not to scale)

200
2. New Kerbing details to comply with
drawing as stated
100

3. Full Construction Information for


300
Carriageway to Table NAC/001/CD

(This drawing is not to scale)

300
FORMATION

IMPERMEABLE MEMBRANE
100mm SAND & GRAVEL

150mm CARRIER Section A-A


PIPE BETWEEN SILT
TRAPS

450mm x 450mm
Kerb Type FT CONCRETE SLABS TO Kerb Type CS
PREVENT EROSION
M12 Mortar Bed Carriageway
100 600 250 600 450
Construction to Table:
CD1
100mm Turf/Topsoil
80

25
200
100

300

SURFACE COURSE
300

FORMATION
BINDER COURSE
IMPERMEABLE MEMBRANE
100mm
BASE COURSE SAND &
GRAVEL
SUB-BASE
150mm CARRIER Section B-B
PIPE BETWEEN SILT
TRAPS

DRAWING NO REV
STANDARD WET SWALE/CARRIAGEWAY CONSTRUCTION
NAC/318/SWS A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

(This drawing is not to scale)

450mm x 450mm
CONCRETE SLABS TO
PREVENT EROSION

DRAWING NO REV
STANDARD DRY SWALE/CARRIAGEWAY CONSTRUCTION
NAC/319/SDP A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Kerb Type FT Kerb Type HB1

100 600 250 600 450 Carriageway


Construction to Table: 1. All dimensions in millimetres. (This
CD1 drawing is not to scale)
100mm Turf/Topsoil
2. New Kerbing details to comply with
80

25

drawing as stated

200
3. Full Construction Information for
Carriageway to Table NAC/001/CD
100

(This drawing is not to scale)


300

TERRAM FILTER MEMBRANE

900
SAND FILTER LAYER
Section A-A

450mm x 450mm
CONCRETE SLABS TO Kerb Type CS
PREVENT EROSION
M12 Mortar Bed Carriageway
Construction to Table:
TERRAM FILTER MEMBRANE
CD1

PEA GRAVEL LAYER


300

150mm PERFORATED PIPE

SURFACE COURSE
IMPERMEABLE
BINDER COURSE MEMBRANE

BASE COURSE

SUB-BASE Section B-B

DRAWING NO REV
STANDARD DRY SWALE/CARRIAGEWAY CONSTRUCTION
NAC/320/SDS A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
Flag
50mm
Dry mix compacted
mortar bedding 25mm
thickness

Subbase 150mm

Formation level

Building or fence line

Pole position

Width
of crossing

TYPICAL LAYOUT AT CONTROLLED PEDESTRIAN CROSSING

DRAWING NO REV
TACTILE PAVING AT SIGNALS
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF
NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY. NAC/401/TPS A
Flag 50mm
compacted
Dry mix mortar bedding 25mm
thickness

Subbase 150mm

Formation level

Building or fence line

Width
of crossing

TYPICAL LAYOUT AT DROP KERB CROSSING

TACTILE PAVING AT PEDESTRIAN DRAWING NO REV


CROSSING POINTS
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF
NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY. NAC/402/TPC A
1. All dimensions in millimetres. (This
drawing is not to scale)

Footway Construction 50 400 400 400 300 135 2. New Kerbing details to comply with
to Table: CD1 drawing as stated

3. Full Construction Information for


Carriageway to Table NAC/001/CD

80
25

180
4. Full Construction Information for Footway
to Table NAC/001/CD

100
(This drawing is not to scale)

150
300

200
Cross Section 225 435

Plan View

TK 180 KK 180 KK 180 KK 180 KK 180 TK 180

DRAWING NO REV
STANDARD BUS STOP CONSTRUCTION
NAC/403/BS A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

Kerb Type RT 2. This drawing should be read in


conjunction with drawing NAC/205/DW2

3. This access is for vehicular use only.


Should provision be required for
Kerb Type FT pedestrians see drawing NAC/409/PCR.

4. Dimension "A" is the width of the access.


2000 5. Dimension "W" is the width of the drop
crossing.
+150
6. New Kerbing details to comply with
Drainage Channel drawing as stated

+100 "A" (see Note 8)


7. Full Construction Information for Footway
to Table NAC/001/CD

8. Where the gradient of the Private


Driveway slopes towards the Public
Footway, a Drainage Channel as
depicted must be installed. It is not
required if the Private Driveway slopes
into the private grounds.
+20
(This drawing is not to scale)

40
1 in sfall
cros
W=A, 3
"W"
.0 m min
Kerb Type BN2
DATUM
LEVEL
As Per Street Type

TYPICAL DETAILS FOR 2.0m FOOTWAY

DRAWING NO REV
STANDARD PRIVATE DRIVEWAY ACCESS (FOOTWAY)
NAC/404/DW1 B
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. This access is for vehicular use only.


Should provision be required for
pedestrians see drawing NAC/409/PCR.

3. Dimension "A" is the width of the access.


Kerb Type FT
4. Dimension "W" is the width of the drop
crossing.

5. New Kerbing details to comply with


drawing as stated
2000 6. Footway Crossing to match Full
Construction Information for Carriageway
+150 to Table NAC/001/CD

+ 100
"A" Drainage Channel
7. Full Construction Information for Footway
to Table NAC/001/CD
(see Note 4)
(This drawing is not to scale)

+20 Footway to match Carriageway


construction to Table NAC/001/CD

40
W=A+1
"W"
.8m, 4.5
1 in sfall
cr o s
m min

Kerb Type BN2


DATUM
LEVEL
As Per Street Type

TYPICAL DETAILS FOR 2.0m FOOTWAY

SINGLE MINOR COMMERCIAL ACCESS, HOUSING COURT DRAWING NO REV

OR CAR PARK UP TO 50 SPACES NAC/405/SMA A


COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. This access is for vehicular use only.


Should provision be required for
pedestrians see drawing NAC/409/PCR.

3. Dimension "A" is the width of the access


road.
MINIMUM - 5.5m Car Park
- 6.0m Commercial

4. Dimension "R" is the corner radius.


MINIMUM - 4.5m Car Park
- 6.0m Commercial

5. New Kerbing details to comply with


Kerb Type FT drawing as stated
2000
6. Footway Crossing to match Full
+150
Construction Information for Carriageway
to Table NAC/001/CD
+100
"A" 7. Full Construction Information for Footway
to Table NAC/001/CD

Kerb Type CS (This drawing is not to scale)

+20 Footway to match Carriageway


construction to Table NAC/001/CD "R"
Bullnose Radius
Kerb laid flush

Kerb Type BN2


DATUM
LEVEL

As Per Street
Type

DRAWING NO REV
MINOR COMMERCIAL ACCESS OR CAR PARK OVER 50 SPACES
NAC/406/MCA A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. This access is for vehicular use only.


Should provision be required for
pedestrians see drawing NAC/409/PCR.

3. Dimension "A" is the width of the access


road.
MINIMUM - 6.0m Non-Industrial
- 7.3m Industrial

4. Dimension "R" is the corner radius.


MINIMUM - 6.0m Non-Industrial
- 9.0m Industrial

5. New Kerbing details to comply with


drawing as stated

6. Footway Crossing to match Full


Kerb Type FT Construction Information for Carriageway
Kerb Type HB1 to Table NAC/001/CD

7. Full Construction Information for Footway


to Table NAC/001/CD
"A" (This drawing is not to scale)

Kerb Type CS

Carriageway
construction to
Table
Bullnose Radius Kerb NAC/001/CD

"R"

Kerb Type CS

DRAWING NO REV
MAJOR COMMERCIAL ACCESS
NAC/407/MAC A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in metres. (This drawing is
not to scale)

Min Garage dimensions 2. This drawing should be read in conjunction


6m x 3m to be accepted with drawings NAC/404/DW1,
NAC/205/DW2 and NAC/206/DW3
as allocated parking space
(see Note 6) 3. This access is for vehicular use only.
Should provision be required for
pedestrians seedrawing NAC/409/PCR.

4. Private driveways should normally meet


1B the road at right angles at dropped kerb
E
DW DROO
access
Driveway
ELL M dimensions
in ING 2
5. Unless giving direct access to a garage,
m apply to double
6m
BE OR 3 driveways should be at least 12 metres
D garage option long. This will facilitate the future
DW ROO construction of garages.
ELL M
ING
6. In order to be accepted as a dwellings
allocated parking space, a garage must
meet a minimum internal dimension of 6m
x 3m.
4O
R 7. The minimum width of driveways should
BE MOR be 2.75 metres with widening required on
D
DW ROO E narrow carriageways;
ELL M CW over 5m = 2.75m min
2.7 ING CW 5m to 3.5m = 3.0m min
(se 5m m CW 3.5m or less= 3.2m min
en
ote in
7) h 8. A width of 4.5 metres will accommodate a
w idt parked car with sufficient space to allow
y )
wa 7 access.

iage note
rr e 9. Double width parking can be
Ca (se 4 accommodated on a 4.8 metres wide
4.8 .5m driveway; however, wheelchair or
m p min
re f perambulator access may not be possible
err in these circumstance and therefore
ed
consideration should also be given to
providing a segregated pedestrian access
or local widening of the driveway.
in
m 10. The length of double driveways required in
m
.5 front of a garage to accommodate a
10 parked vehicle and access to the garage
should be a minimum of 10.5 metres.
4
5.0 .8m
m p min 11.Full Construction Information for
refe Carriageway to Table NAC/001/CD
rre
d
12.Full Construction Information for Footway
to Table NAC/001/CD

(This drawing is not to scale)

DRAWING NO REV
MINIMUM DRIVEWAY DIMENSIONS
NAC/408/DWD A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. New Kerbing details to comply with


drawing as stated
2000 3. Full Construction Information for
Carriageway to Table NAC/001/CD

4. Full Construction Information for Footway


to Table NAC/001/CD

(This drawing is not to scale)

+150
+100
dished
are
footwa a to minimise
+6 (max. 7 y gradients
.5% gra
dient)
40
1 in sfall
cros
1.8m m
in

DATUM
LEVEL

TYPICAL DETAILS FOR 2.0m FOOTWAY

DRAWING NO REV
DROPPED KERB DETAIL AT DESIGNATED PEDESTRIAN CROSSING
NAC/409/PCR B
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

Kerb Type FT Type 4b Carriageway Construction 2. This drawing should be read in


conjunction with drawing NAC/206/DW3
to Table: NAC/001/CD
3. This access is for vehicular use only.
Should provision be required for
pedestrians see drawing NAC/409/PCR.
Kerb Type BN2
(See NAC/103/BNK) Kerb Type FT
4. Dimension "A" is the width of the access.
2000 5. Dimension "W" is the width of the drop
crossing.

+100 Drainage Channel


6. New Kerbing details to comply with
drawing as stated

+50
Transition Kerb
"A" (see Note 8)
7. Full Construction Information for Footway
to Table NAC/001/CD

8. Where the gradient of the Private


Driveway slopes towards the Public
Footway, a Drainage Channel as
depicted must be installed. It is not
required if the Private Driveway slopes
into the private grounds.
+20
(This drawing is not to scale)

40
1 in sfall

W=A, 3
"W"
.0m
cros
min
Kerb Type BN2
DATUM
LEVEL
As Per Street Type

TYPICAL DETAILS FOR 2.0m SERVICE STRIP

DRAWING NO REV
STANDARD PRIVATE DRIVEWAY ACCESS (SERVICE STRIP)
NAC/410/DW4 A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres.
Varies
(see Table BITUMINOUS SUB-BASE (clause 906) For a 2% < CBR <= 5% where the total bituminous thickness
NAC/001/CD)
and sub-base thickness together are less than 450mm, the
sub-base is increased to achieve 450mm of non frost
GRANULAR SUB-BASE (clause 803) susceptible material and the capping layer can be
correspondingly reduced. This need not be done if the
capping layer is non frost-susceptible.
300

Although the table gives various thicknesses of capping layer


350

dependent upon CBR, where CBR is significantly below 2%,


these thicknesses may require to be increased dependent
upon site and weather conditions prevailing at the time of
construction. Additional material may require to be removed
and replaced by more suitable material. Although the new
600

CAPPING 5% < CBR material may be of good quality, the subgrade shall be
50

(clause 613) 50 mm assumed to be equivalent to one of a CBR just under 2% and


2% < CBR <= 5% requiring 300 mm of capping layer. The developer should
consult the Network Manager for advice in these
circumstances.
300

Where suitable technical facilities exist, it is recommended


that the specific circumstances of each site are catered for by
designing the road in accordance with the criteria stipulated
above, Subject to a minimum construction as required to
300 mm carry 0.5 Million Standard Axles (MSA), for all roads. In this
CBR <= 2% circumstance it will be necessary to complete and return form
FORMATION CCS "Carriageway Design Certificate".

DRAWING NO REV
CAPPING LAYER REQUIREMENTS: SUBJECT TO FROST SUSCEPTIBILITY
NAC/501/CAP A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. Ensure reflective banding is in the


correct orientation - RED towards
oncoming traffic.

3. The reinforcing tube or anchor bar is to


be orientated so that the coupling bolt is
inserted at 90° to the carriageway (see
Plan view).

4. The reinforcing tube should be filled with


concrete where required for additional
strength.

(This drawing is not to scale)

150

BAND RECESS
160

BAND RECESS

80
150

BODY
SLEEVE

REMOVABLE BOLLARD

1000 (height above ground)


BOLLARD
919 (height above ground)
760 (Tube height above ground)
480

BAND RECESS
20

COUPLING BOLTS

200
500 (Depth Below Ground)

CLASS E
CONCRETE CLASS E
SURROUND CONCRETE
SURROUND
745 (Depth Below Ground)

ANCHOR
BAR

REINFORCING
TUBE

345

400

115

250

400

DRAWING NO REV
BOLLARD DETAIL
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF
NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY. NAC/502/BOL A
1. All dimensions in millimetres.

SECTION
PLAN

UNDERGROUND
GUYING CABLES

PROPRIETORY PVC
ROOT CONTAINMENT
ON VERTICAL FACES OF
TREE PIT
1.2m

1.5m

300mm

FILTER MATERIAL
1.5m

NOTE: FILTER MATERIAL REQUIRED ABOVE IMPERVIOUS GROUND CONDITIONS


FLEXIBLE ROOT LINER ALTERNATIVE TO CONCRETE RING

DRAWING NO REV
TREE PIT DETAIL WITH CONTAINMENT
NAC/503/TRE A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.
1. All dimensions in millimetres. (This
drawing is not to scale)

2. Full Construction Information for


Carriageway to Table NAC/001/CD

3. All bituminous joints to be treated to


SHW cl 903, Sections 21-25

4. Bond Coat/Tack Coat to SHW cl 920

(This drawing is not to scale)


New carriageway Existing carriageway

New surface course

New binder course

New base

Proposed Existing
road level 300 300 road level

Tack coat applied


bituminous seal
to full joint
450
min

Existing surface course

Existing binder course

Existing base

New subbase Existing subbase

DRAWING NO REV
STEPPED CARRIAGEWAY JOINT
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF
NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY. NAC/504/SCJ A
Sign Face

Ground Level
(d)

(a)

(b)

(z)

(x)
(y)

Pole Base Base Base Cover to Planting


Diameter Length Width Depth Base Depth
(d) (x) (y) (z) (a) (b)
76 600 600 450 150 600
89 600 600 600 150 750
114 900 600 600 150 750
140 1200 750 750 150 900
(All dimensions in millimetres)

DRAWING NO REV
SIGNPOST FOUNDATION DETAIL
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF
NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY. NAC/505/POS A
1. All dimensions in millimetres. (This
180 min drawing is not to scale)
300 max
2. Street nameplate to be non-reflective,
helvetica medium lettering, black on
white background on 3mm aluminium
plate, rounded corners and 8mm black
border. Sealed with appropriate

EXAMPLE STREET 165 min


275 max
weatherproof clear protective material.
Lettering to be 75mm, uppercase, and on
two or more lines if appropriate.

3. Street nameplate to be mounted using


rivited channel rails and 4x76mm
stainless steel anti-rotational clips, plus
2x76mm diameter grey PVC material
coated poles, bitumen coated internal
surfaces, galvanised base plates, platic
pole caps to allow mounting heignt of
1.0m and foundation depth of 500mm.

4. Poles to be fitted in 300mm x 300mm x


500mm deep hole, ancillary concrete mix
ST2 or similar approved mix, concrete
foundations to be float finished flush with
existing hard surfaces, and painted with
bitumen paint to match. Soft soil, verge,
turf etc. to be reinstated to original
surface, where appropriate on top of
concrete foundation.
500

300

DRAWING NO REV
STREET NAMEPLATE DETAIL
NAC/506/SNP A
COPYRIGHT NORTH AYRSHIRE COUNCIL 2019. USED WITH THE PERMISSION OF NORTH AYRSHIRE COUNCIL FOR DEVELOPMENTS WITHIN NORTH AYRSHIRE ONLY.