PLTMG Seram Peaker 20 MW: Mobile Power Plant & Fixed Type Gas Engine Power Plant Package Iii (Fixed Power Plant)

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 4

CIVIL

MOBILE POWER PLANT & FIXED TYPE


GAS ENGINE POWER PLANT PACKAGE III R MECHANICAL
(FIXED POWER PLANT) E
V ELECTRICAL
PLTMG SERAM PEAKER 20 MW I
I&C
E
CONTRACTOR DOCUMENT REVIEW W SUPPORT

LOGI DATE
N COMM. NO.
A APPROVED
B APPROVE AS NOTED D CONTRACTOR RECORD
C NOT APPROVED I WORKING DOCUMENT
S
I INFORMATION
T
R
APPROVAL DOES NOT RELIEVE CONTRACTOR I
FROM RESPONSIBILITY FOR ERRORS AND B
DEVIATIONS FROM CONTRACT REQUIREMENTS U
T
I
BY : DATE :
O
LOG DATE N
OUT COMM.NO :
OWNER
PT. PERUSAHAAN LISTRIK NEGARA ( PERSERO )
UNIT INDUK PEMBANGUNAN MALUKU
ENGINEER

PT. PLN ( PERSERO ) PUSAT ENJINIRING KETENAGALISTRIKAN


CONTRACT NO. : 0177.PJ/DAN.02.01/DIR/2017
PLN DOC. NO.
1 1 0 2 6 B - 3 . - - - - - - -

TITLE :
DATA SHEET FOR NEUTRAL GROUNDING RESISTOR
PURPOSE :

ISSUED FOR APPROVAL


REV Description Prepared Checked Approved Date

0 DA NJ DE 14/08/2017
CONTRACTOR Doc No. :

CONSULTANT ENG-DED-SRM-EL-09-AQ-022
CONSORTIUM OF PT. WIJAYA KARYA &
PT. WIJAYA KARYA REKAYASA KONSTRUKSI

ENGINEERING DOCUMENT
PLTMG SERAM
PEAKER
ENG-DED-SRM-EL- DATA SHEET FOR NEUTRAL GROUNDING RESISTOR 2 of 4
09-AQ-022

N DESCRIPTION DATA
UNIT
O
ENGINE GENERATOR NGR
1 Manufacturer
2 General Technical Specification
- Network Voltage (Ur) kV 11
- Reted Voltage (Un=Ur/1.732) kV 6.35
- Rated Fault Current A 9.7
- Rated Fault Time 60 Sec / 760°C rise
- Resistance @ 20°C Ohms 650
- Insulation Level kV 12
- Power Frequency Withstand Voltage kVrms 28
- Impulse Withstand Voltage (BIL) kVpea 75
k
- Connection-Generator to NGR Bottom Side
- Connection-NGR to earth Bottom Side
- Current Transformer
- Voltage grade kV 15
- No. Of Core 1
- Ratio 50/1A
- Class 5P20
- Knee point voltage kV 6.35
- Burden value VA 15

3 Enclosure
- Type Free Standing
- Degree of Protection IP 55
- Material Carbon Steel
- Coating Powder Coating RAL 7035
- Plate Thickness mm Minimum 2mm
- Enclosure grounded Yes

GENERATOR TRANSFORMER NGR


CONSORTIUM OF PT. WIJAYA KARYA &
PT. WIJAYA KARYA REKAYASA KONSTRUKSI

ENGINEERING DOCUMENT
PLTMG SERAM
PEAKER
ENG-DED-SRM-EL- DATA SHEET FOR NEUTRAL GROUNDING RESISTOR 3 of 4
09-AQ-022

N DESCRIPTION DATA
UNIT
O
4 Manufacturer TBA

5 General Technical Specification


- Network Voltage (Ur) kV 20
- Reted Voltage (Un=Ur/1.732) kV 11.55
- Rated Fault Current A 23.09
- Rated Fault Time 60 Sec / 760°C rise
- Resistance @ 20°C Ohms 500
- Insulation Level kV 12
- Power Frequency Withstand Voltage kVrms 28
- Impulse Withstand Voltage (BIL) kVpea 75
k
- Connection-Generator to NGR Bottom Side
- Connection-NGR to earth Bottom Side
- Current Transformer
- Voltage grade kV 15
- No. Of Core 1
- Ratio 50/1A
- Class 5P20
- Knee point voltage kV 11.55
- Burden value VA 15

6 Enclosure
- Type Free Standing
- Degree of Protection IP 55
- Material Carbon Steel
- Coating Powder Coating RAL 7035
- Plate Thickness mm Minimum 2mm
- Enclosure grounded Yes
CONSORTIUM OF PT. WIJAYA KARYA &
PT. WIJAYA KARYA REKAYASA KONSTRUKSI

ENGINEERING DOCUMENT
PLTMG SERAM
PEAKER
ENG-DED-SRM-EL- DATA SHEET FOR NEUTRAL GROUNDING RESISTOR 4 of 4
09-AQ-022

NO DESCRIPTION GENERAL SPECIFICATION UNIT QUANTITY REMARK


Neutral Grounding 20 kV, 23.09 A, 500 Ohm, CT 50/1 A, free
1 SET 4 Seram & Langgur
Resistance standing,
    ip 55, plate tickness 2mm      
           
Neutral Grounding 20 kV, 288,4 A, 40 Ohm, CT 300/1A, free MERAUKE, BIAK,
2 SET 6
Resistance standing TANJUNG SELOR
    ip 55, plate tickness 2mm      