Geor Et Rnce (07020)
4 in 424-7457 1 28 L 4-wheel
4 in 115-2421 1 28 L 4-wheel
5 in 115-2421 2 38 L 4-wheel
5 in 115-2421 2 38 L 4-wheel
5 in 115-2421 2 38 L 4-wheel
5 in 115-2421 2 38 L 4-wheel
6 in 115-2421 2 38 L 6-wheel
6 in 115-2421 2 38 L 6-wheel
8 in 115-2421 2 38 L 6-wheel
8 in 115-2421 2 38 L 6-wheel
10 in 115-2421 2 58 L 8-wheel
RATING, kW VOLTAGE
MODEL
(STANDBY) 230 240 380 400 415 440 460 480
200 630 630 400 400 400 400 400 400
250 800 800 500 500 500 500 400 400
C9
275 1000 1000 630 500 500 500 500 500
300 1000 1000 630 630 630 500 500 500
350 1250 1250 700 630 630 630 630 630
C13
400 1250 1250 800 800 700 700 630 630
C15 500 1600 1600 1000 1000 1000 1000 800 800
C18 600 2000 2000 1250 1250 1250 1000 1000 1000
3412C 800 2500 2500 1600 1600 1600 1600 1250 1250
C32 1000 3200 3200 2000 2000 2000 2000 1600 1600
3512 1250 2500 2500 2500 2500 2000 2000
3512B 1500 3200 3200 3200 2500 2500 2500
3516 1750 4000 3200 3200 3200 3200 3200
2000 4000 4000 4000 4000 3200 3200
3516B
2250 5000 4000 4000 4000 4000 4000
3516C 2500 5000 5000 5000 5000 4000 4000
C175-16 3000 6300 6300 6300 5000 5000 5000
Note: Breaker ratings mentioned here may or may not have an equivalent frame size,
and could require the next higher model but with adjusted trip setting.
MULTIPLIER FOR MAXIMUM CURRENT