GESTRA in Hospitals: Application Examples For Steam and Condensate Systems

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

GESTRA in Hospitals

Application Examples for


Steam and Condensate Systems

Application Examples
for Steam and
Condensate Systems

Specific Requirements for


Everyday Healthcare

Day after day, hospitals and their teams perform


tasks of great responsibility – making it all the
more important for each item of technical equip-
ment to function smoothly. This applies just as
much to the steam and condensate systems.

These units must be designed specifically for the


hospital environment, because they often have
to supply remote buildings with process steam
and also have to provide sterilized pure steam
wherever needed.

At the same time, hospitals have long been sub-


ject to the constantly rising demands of economic
efficiency. As a result, the reliable supply of
steam as well as the potential energy savings play
a significant role in the decisions to be taken on
the most suitable plant technology.

We have compiled various possibilities for saving


energy, with a special focus on the requirements
for steam and condensate systems in health ser-
vices. With the GESTRA products recommended
here, you can combine reliable plant functionality
with financially attractive results.
5 9
11 8

9 7

2 7
9

7
12

10

4
3
19

10
7

1 15

7
14
5 4 16
13

Schematic of a Hospital 7
17
7
14
1 Steam boilers 8 Plant control with 15 Air-conditioning
2 Feedwater deaerating plant SPECTORcontrol plant
3 Condensate recovery and 9 Self-acting pressure reduction 16 Disinfection of beds
return system 10 Steam flow measurement and mattresses 3

4 Electro-pneumatic pressure 11 Electrical temperature 17 Sterilization


reduction control 18 High-purity water
7
5 Steam regenerator 12 Flash vessel treatment
6 Economizer 13 Steam drier 19 Condensate 3 18
7 Steam trap monitoring 14 Steam header header To 2
Steam and Condensate Systems in Hospitals

Application Examples for the Boiler House

GESTRA Steam Boiler Equipment with Bus Technology Overview GESTRA Feedwater Flash steam
Deaerating Plants
For operation e.g. according to TRD 604 (72 h) or EN 12953 (24 h) Reliability, availability and economy have always
enjoyed top priority in boiler operation. To an in- For the operation of steam boilers with a high ther-
creasing extent, plant automation and visualization mal load on the heating surfaces, it is necessary
are playing a central role. to use boiler feedwater that has been treated and Condensate Softened water
conditioned according to TRD 611, EN 12952 part
To implement these efficiency parameters as 12 or EN 12953 part 10. The boiler feedwater
effectively as possible, GESTRA AG has for must be free of hardening constituents, in order to
decades now been working exclusively with prevent the formation of scale on the boiler heating
electrode systems that are low in maintenance and surfaces.
wear. In contrast to other systems, they function Dissolved oxygen and carbon dioxide are likely to
entirely without moving parts. cause serious corrosion of metal boiler parts. With
the GESTRA feedwater deaerating plant, dissolved
Over and above the boiler house equipment itself, aggressive gases are reliably removed from the
these systems have now conquered the peripheral boiler feedwater and make-up water.
units, such as feedwater and condensate tanks,
pumpless and pump-driven return installations The system consists of the feedwater tank SW
etc. Many of our customers therefore do not enter and the deaerator dome NDR. Each deaerating Heating steam
into any compromises in this area too – after all, plant for boiler feedwater is custom-designed for
an energy supply centre is only as effective as its that particular application and meets the essential
weakest element. thermodynamic requirements to achieve optimal To the feedwater tank
performance.
For more on this topic, see our separate brochure
entitled “Equipment for Energy Supply Centres”.
Sample water
inlet

GESTRA Sample Coolers

For the smooth operation of steam boilers, it line or in the sample container, which cause an
is especially important to analyse samples of increase in the density of the boiler water sample.
the boiler water. However, to obtain proper and The samples then no longer represent the true TDS
uncorrupted analysis values, you require accurate content (salinity) in the steam boiler.
sampling methods and also testing instruments
that function correctly. The perfect solution to these challenges is to use
the GESTRA sample cooler PK. The boiler water
Direct sampling of hot boiler water from pres- sample is cooled down to the reference tempera- Sample
surized lines always involves mastering a number ture of 25 °C and thus fulfils all of the requirements water outlet
of challenges. Firstly, there is the danger of scal- for precise water analysis and comprehensive work
ding; secondly, analysis results may be corrupted safety. Cooling water
as a result of flashing losses within the sampling

6 w w w . g e s t r a . d e Waste water 7
Steam and Condensate Systems in Hospitals

Challenges in the Boiler House

Flash steam
GESTRA Mixing Cooler VDM discharge / vent Steam and Condensate Systems Energy-saving tip: Energy-saving tip:
in Hospitals Reusing the condensate Undercooling on the condensate side
Mixing coolers (a type of blowdown receiver) serve
to cool hot waste water that can no longer be used In a modern hospital, the process steam needed The condensate produced at the various users is For heating cycles and the heating of service water,
for heat recovery and is therefore discharged into a for daily operation is usually generated in a cen- collected and then conveyed via steam-powered it is possible to use vertical heat exchangers with
basin, pit or drain. Cooling water tral boiler house. As a rule, two or three steam condensate return units to the central condensate undercooling on the condensate side instead of
Here it is necessary to ensure that the maximum boilers running in parallel are used to ensure that recovery and return system. The condensate horizontal heat exchangers controlled on the steam
GESTRA

temperature prescribed by law is observed. the necessary output is available. The specific obtained from heat exchangers for the heating side. With condensate undercooling, it is possible
demands of hospital operation on its steam and cycle and hot-water supply is also fed in here and to avoid the energy losses which would otherwise
Typical applications for mixing coolers: condensate systems are not related to steam then pumped back to the central boiler house. occur in the conventional horizontal heat exchang-
generation in the central boiler house, however. Thanks to the GESTRA monitoring systems, it is ers through flashing of the condensate.
◗ Process plants where hot, contaminated waste The steam generation here differs little from that also possible to return condensate endangered by
Hot waste
water is formed water
in other sectors. On the contrary, the steam gen- the ingress of foreign matter – no matter whether
◗ Steam boiler plants where the blowdown is eration in remote supply units represents a special this concerns oils, greases, acids, alkalis, raw
cooled with untreated water Cooling water challenge, e.g. clinic buildings widely distributed water or other substances.
◗ Mixing condenser for vapours and flash steam Mixed about the hospital grounds. For this reason, we
GESTRA

cooled water will focus on the possible optimization of such a


decentralized steam output and the corresponding
potentials for saving energy.
Condensate inlet Vent
In the ideal case, the process steam generated in
the boiler house will be passed to the various con-
Drain
sumption points via a process steam header.
To meet the demand while conserving resources,
the quantities required by the corresponding
Flash steam
users are continuously recorded by a steam flow
Air balance pipe measurement setup, and reliably monitored and
controlled with the aid of an energy management
Vent line system.
Condensate
GESTRA Flash Vessel Systems inlet In the healthcare sector, process steam is needed Condensate Condensate
for the following users, amongst others: outlet 2 outlet 1
Flash vessels reduce the operating costs consid- several times, depending on ◗ For generating (pressurized) hot water and
erably, because the sensible heat of the conden- the possibilities for operating for heating systems
sate is utilized economically. They can be used in the steam system at different ◗ Heating of service water
all steam systems in which condensate from steam pressure ratings. The residual ◗ Feedwater deaeration Drain
users can be flashed to a lower pressure. During condensate in the flash vessel ◗ Pure steam for automatic cleaners and
the flashing process, heat is released, which leads is passed into a condensate disinfectors
to the formation of flash steam. In the flash vessel, tank and reused as boiler ◗ Ironing, washing, calendering
Drain Condensate outlet ◗ Kettles in the kitchen
this flash steam is separated from the water and feedwater.
fed into a steam system with a lower pressure
for further use. Such a process can be repeated GESTRA condensate recovery and return systems

8 w w w . g e s t r a . d e 9
Steam and Condensate Systems in Hospitals

Specific Challenges in Hospitals

Rapid Provision of Exact Steam Besides the need for correct sizing, it is also impor- the operational and acquisition costs, the greater From Process Steam to A well-planned hygienic installation considers the A smoothly functioning hygienic installation also
Pressures tant to locate the control valve and the associated the care that should be exercised in selecting Sterilized Pure Steam diverse aspects of energy efficiency and safe- needs professional planning and workmanship for
measuring transducers at the correct position in and sizing the plant components. Our experience guarding sterility. For example, the condensate is the pure-steam and condensate lines. The pipes
The washing units as well as the automatic the piping. Only then can optimum plant function shows that valves with too large a nominal size A core element for supplying steam to hospitals is collected from the sterilizing equipment and con- and valves to be used in medical sterilization must
cleaners and disinfectors need pure steam or be ensured. are often installed. If the valve is oversized, the the steam regenerator. For the operation of steri- veyed to the feedwater deaerating plant through a be made of chrome-nickel steel to ensure sterility.
process steam with a lower steam pressure than smallest repeatable opening may be too large for lizing equipment and air humidifiers in healthcare, special recovery and return system. The energy still contained in the returned process-
that generally prevailing in steam systems. Since For effective and reliable operation of a plant, the the minimum flow that is needed. Incorrect valve the steam must be absolutely free of attendant steam condensate can be put to good use in pre-
this steam pressure need not be exact, it can be control circuit must be designed carefully with a selection can also lead to premature wear and substances that are noxious, chemically reactive What is more, the pure steam is used prudently. In heating the feedwater for the steam regenerator.
regulated with the aid of self-acting pressure re- suitable measuring transducer, process controller excessive noise development. If cavitation arises in or odorous. This is the case only with pure steam. the units for humidifying room air, it is sprayed in
ducing valves. If operation of the plant requires that and control valve as well as all the necessary a control valve due to faulty sizing, this frequently For example, to guarantee uninterrupted supply of a fine mist. In the feedwater deaerating plant, it is Frequently, energy supply centres do not have
a precise steam pressure be provided very quickly, system components. results in damage to the internals, body or piping. the operating theatres with pure steam, two steam atomized directly into the water bath by means of a enough space left over for a separate feedwater
electro-pneumatic steam control is used. regenerators are operated in redundant mode as steam injector. As a result, very little condensate is deaerating plant. A compact alternative is offered
The higher the requirements in respect of control Owing to faulty (or no) calculation of the kv-value a rule, i.e. one unit is keep on hot standby to take collected from the pipe drainage legs. To compen- by the GESTRA steam regenerators, for which a
accuracy, rangeability, manipulating speed, for control valves, often only a small part of the over the supply immediately in case of failure. sate for the difference in quantity, it is necessary deaerator dome can be mounted on top. With the
cavitation, sound pressure level and optimizing of possible control range is used, or the required to provide for a continuous feed of fully deionized correspondingly adapted controls, the deaeration
minimum or maximum flow is not achieved. In In the healthcare sector, pure steam is needed for water into the feedwater plant. function can be integrated into the steam regen-
such cases, the control circuit will not function as the following users, amongst others: erator.
GESTRA electro-pneumatic pressure reduction it should. ◗ Sterilizing equipment
◗ Room air humidifiers Depending on the plant operator’s requirements,
Even with correct design of the control valves, it ◗ Feedwater deaerating plants for we can supply either conventional or PLC control
8 11
13 may happen that the standard version with para- highly purified water equipment – the latter offering the added possi-
9 bolic plug is not able to fulfil the specific control bility of data transfer to a central control system.
7 task. Depending on the requirement, it may be
12 necessary to fit the control valve with a reduced
14
seat, hardened contours, multihole plug, Silent
1 3
1 Pack or other additional internals.
2
15
Because of the building-block concept, the control
2 3 4
10 valves of the series V725/726 offer a broad
spectrum of applications. The modular construc-
4
tion permits easy expansion up to a fully-fledged
5 control valve system offering communication 1 Pure steam outlet
functions. Thanks to the built-on positioner, this
2 Vent line
6 series offers a particularly compact structure. The
pocket-free valve stem guarantees a long service 3 Control cabinet
life; the exchangeable internals facilitate mainte- 4 Heating steam inlet
1 Steam inlet 6 Drainage 11 Shut-off valve with throttling plug nance, because the control valve can remain in the 5 Feedwater inlet 7 6
2 Shut-off valve 7 Pneumatic control valve 12 Pressure gauge piping while the trim is replaced.
6 Continuous/intermittent 5
3 Strainer 8 General-purpose controller 13 Safety valve blowdown
4 Steam drier 9 Pressure transducer 14 Vent line 7 Condensate outlet
5 Steam trap 10 Shut-off valve 15 Steam outlet GESTRA steam regenerator as a compact system

10 w w w . g e s t r a . d e 11
Steam and Condensate Systems in Hospitals

Process Reliability and Energy Efficiency Process Data Visualization

Safety tip: Energy-saving tip: GESTRA condensate Where Worlds Connect – for an Process control level Office PC, laptop
Electronic monitoring Steam trap monitoring monitoring system Optimized Flow of Information

Automatic steam traps intrinsically offer a high A leaky steam trap can lose as much as 5 to 20 If you wish to integrate your boiler data within
2
degree of functional reliability. This can be in- kilograms of steam every hour. If we assume a higher-ranking control system, you need
creased further for particularly sensitive and cost- 8,000 operating hours for the steam trap per year SPECTORcom or SPECTORcontrol by GESTRA. All
intensive steam delivery processes with the aid of and the smallest loss of live steam of 5 kg per hour, measurement data are sensed by electronic signal
electronic monitoring: over 40 tonnes of unused steam will escape per transducers and passed on to the control centre, OPC Profibus Ethernet
• Blocked and/or leaky steam traps are detected year. Assuming the steam costs to be 50 euros per where they are combined to form high-level state- DP (optional)
reliably and in realtime. tonne, this means that just one leaky steam trap ments. The SPECTORcontrol system has a Touch
• The operating conditions of all monitored steam can cost you the unnecessary expense of 2,000 PLC unit; this is used for automatic control of e.g. Land lines via modem

traps can be read off quickly and conveniently. euros per annum. the pressure, temperature and conductivity, and
• The system can be configured in a versatile man- also for the local visualization functions.
ner, and automatically suppresses error messages With the steam trap monitoring system VKE by 1
on startup and shutdown of the steam system. GESTRA, these costs can be ruled out perma-
• With the aid of a fault history function, it supports nently. The Benefits for You
the possibilities for continuous system optimization.
1 Level electrode for installation Better process overview:
Your benefit: Process reliability is enhanced; cost- in GESTRA steam trap ◗ Enhanced overview of the process, through Service partner
Supplier
intensive plant malfunctions are prevented. 2 Test unit centralized process display
◗ Actual values indicated as bar chart Modbus RTU CANopen
◗ Trend plot of the measurement values CAN
◗ Prioritized display of faults
◗ List of maintenance intervals
GESTRA Service ◗ Designations of the measurement quantities,
input/output signals, and logging of alarm and
As an international leader in the manufacture of You can also count on us for superior maintenance: status messages – configurable by the operator
valves, traps and control technology for the steam as a plant operator, you have to rely on the smooth ◗ Logical combination of all signals, limit and
and energy industry, GESTRA offers its customers operation of your installation. All systems must warning values possible
many decades of experience and the technical ser- be checked and serviced regularly. However, your ◗ The results are provided as a report I/O module
vice to match – giving you a decisive competitive maintenance staff increasingly need to concentrate
advantage. on the specific demands of the medical equipment, Greater efficiency:
giving them less time to look at the basic steam ◗ Better utilization of fuel
To make our technical service even more focused and condensate system. ◗ Totalizing of consumption
and effective, we have separated the service ◗ Improved environmental protection through
departments for GESTRA valves and steam traps Our highly trained specialists can take on this task monitoring of waste water and exhaust gases
and GESTRA electronic equipment for steam for you within the scope of a GESTRA maintenance ◗ Modular, expandable architecture for all
boilers, and also expanded them considerably. agreement. We will be happy to advise you. plant sizes
This gives our customers a direct line to the right ◗ Separate electronic control units no longer
experts, ensuring that assistance can be given needed, thanks to the integrated control
speedily. circuitry
◗ Input and output signals are easy to integrate

12 w w w . g e s t r a . d e 13