Professional Documents
Culture Documents
Battery Safety and Environmental Concerns Transcript
Battery Safety and Environmental Concerns Transcript
Battery Safety and Environmental Concerns Transcript
Transcript
Slide 1
Welcome to the Data Center UniversityTM course on Battery Safety and Environmental Concerns.
Slide 2
For best viewing results, we recommend that you maximize your browser window now. The screen controls
allow you to navigate through the eLearning experience. Using your browser controls may disrupt the
normal play of the course. Click the Notes tab to read a transcript of the narration.
Slide 3
At the completion of this course, you will be able to:
Differentiate between various battery types
o Flooded (unsealed) batteries (also referred to as “wet cell” or “vented”)
o Valve Regulated Lead Acid (VRLA) batteries
o Modular Battery Cartridges (MBC)
Recognize the standards and codes that apply to battery systems and rooms
o Federal Code of Regulations
o Fire codes
o Environmental Protection Agency (EPA) considerations
o Occupational Safety and Health Agency (OSHA) considerations
Describe how safety regulations apply to different battery technologies
Slide 4: Introduction
Battery systems and battery rooms are regulated by a number of fire safety and environmental standards
and codes. Proper interpretation of these codes is essential in the design and implementation of data
centers and network rooms.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
It is important for data center designers to have a clear understanding of the fire safety and environmental
regulations as they apply to UPS battery installations. For example, in some cases, fire codes do not clearly
recognize improvements in battery safety resulting from changing battery technology. Valve Regulated Lead
Acid (VRLA) batteries are frequently deployed within data centers and network rooms without the need for
the elaborate safety systems that are required for flooded lead acid batteries. We’ll explore this further a
little later in the course.
Slide 5: Introduction
While most commercial battery back-up systems fall below government-required reporting levels, very large
UPS and DC plant batteries may have to comply. Failure to comply can result in costly penalties.
Environmental compliance focuses on the amount of sulfuric acid and lead at a particular location. Power
ratings for VRLA batteries and modular battery cartridges (MBC) are much higher than for flooded batteries
at the same reporting threshold. This course offers a high level summary of the regulations and provides
guidance for locating sources of regulatory information.
Let’s begin with an illustration of the common concern involved with batteries and compliance.
Slide 6: Introduction
The following scenario illustrates the common concern about batteries and compliance:
An IT manager will be installing (or maybe already has installed) a large, lead-acid battery system to back
up critical data center operations. He is nervous about all the batteries stored in his facility and now he is
informed that he may have a compliance issue. He’s already been down the road with the electrical
inspectors and fire marshals, and now he hears that the Federal Government may have a disturbing interest
in his facility as well.
Compliance is an important issue that all data center managers need to address. Let’s explore the issue of
compliance a little further.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Slide 7: Code of Federal Regulations
Flooded batteries are required to comply with the Occupational Safety and Health Administration (OSHA)
Regulation 29 CFR 1926.441, Battery Rooms and Battery Charging. This regulation applies to batteries of
the unsealed type installed in new construction. Unsealed in this case means flooded batteries. Under this
regulation, ventilation, worker protection, acid flushing and neutralization are required. If using flooded
batteries please see the OSHA web site www.osha.gov for specific details on how to comply. VRLA
batteries are of the “sealed” type, so OSHA regulation 29 CFR does not apply.
Smaller and distributed back-up power systems are typically located much closer to the equipment they
protect. They generally use Valve Regulated Lead Acid (VRLA) batteries. VRLA batteries are designed to
recombine hydrogen and oxygen and emit only extremely small amounts of hydrogen under normal
operating conditions. Normal room ventilation is sufficient to remove any hydrogen, so special ventilation is
not required.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
The electrolyte in a VRLA battery is not in liquid form but is immobilized. The most common technology,
termed Absorbed Glass Mat (AGM), uses a highly porous, absorbent micro fiberglass mats that immobilize
the electrolyte and prevent it from spilling. A crack or hole in the casing of a VRLA battery using AGM
technology will not result in a measurable electrolyte spill. Spill containment with VRLA batteries is therefore
not meaningful or appropriate.
Originally published by the Western Fire Chiefs Association, the UFC is now published by the National Fire
Protection Association (NFPA - 1) as of 2003.
The International Code Council (ICC) writes the IFC. The ICC was created in 1994 when the Southern
Building Code Congress International (SBCCI), the International Conference of Building Officials (ICBO),
and the Building Officials and Code Administrators International (BOCA) united to create a set of
harmonized standards.
Codes change with each rewrite and jurisdictions use differing versions of codes. This course can only
generalize about codes. Checking with local authorities is essential in order to determine which code they
enforce.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Slide 12: Application of the Codes to Battery Technologies
Before applying the codes, one must understand how the codes will apply to a specific installation. There
are four questions that must be answered:
1. What is a battery system?
2. How many gallons of electrolyte are in this battery system?
3. Is the electrolyte free-flowing liquid or is it immobilized?
4. At what electrolyte volume does the code apply?
Under the UFC definition, a battery system consists of three interconnected subsystems:
1. A lead-acid battery
2. A battery charger
3. A collection of rectifiers, inverters, converters and associated electrical equipment as required for a
particular application
From this definition each individual UPS or DC Plant constitutes one battery system. Smaller, separately
installed UPSs are independent and do not have an additive effect on the electrolyte capacity. A fault in one
system will not propagate to the others, as they are independent of each other. The threshold triggers are
defined per battery system and not by facility. The code specifically does not instruct the summation of
independent battery systems.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Gallons are a liquid measure and the fire codes seek to determine the amount of liquid electrolyte in the
battery system. In a flooded battery system 100% of the electrolyte is in liquid form. In a VRLA battery
solution, about 3% of the electrolyte is in liquid form. These values are provided by the battery manufacturer.
The liquid electrolyte values in each battery within the battery system are added together to arrive at the
total for a system.
The 2003 Uniform Fire Code has also changed. Certain requirements, such as spill containment, apply only
to battery systems having free-flowing electrolyte in excess of 1000 gallons. The intent was to exempt
batteries with immobilized electrolyte, like VRLA batteries, from such rules.
For a flooded battery system the IFC (Section 608 and 609) and UFC (Article 64 in the old code and Article
52 in the updated code) use 50 gallons of electrolyte capacity criteria for when compliance is required.
Below 50 gallons the code is not applied. For a room with sprinklers the UFC threshold increases to 100
gallons. In data centers or network rooms using an alternative method of fire protection (for example, Halon
or FM200), the 50-gallon level applies.
One should assume that any UPS application using a flooded battery must comply with the fire codes. Both
codes specify requirements for occupancy separation, spill control, neutralization, and ventilation. In the
2000 and earlier editions of the UFC, Article 64 required VRLA battery systems exceeding the liquid
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
electrolyte volume threshold values to meet special protection requirements. In 2003 the code was revised
to apply spill containment requirement only to flooded battery systems (ie., batteries with free-flowing
electrolyte) with a minimum of 1,000 gallons. The purpose of the change was to hold batteries to no higher
standard than applies for hazardous material covered elsewhere in the code. Requirements other than spill
control still apply at the 50 and 100 gallon limits.
Both the UFC and the IFC require an approved method to prevent thermal runaway in VRLA battery
systems.
Note: This distinction should not be confused with EPCRA reporting requirements. EPCRA requires a
building owner to declare when the aggregate amount of sulfuric acid in batteries throughout the facility
exceeds 500 pounds. Because electrolyte is approximately 2/3 water and 1/3 acid, some inspectors have
recently taken a broader, and incorrect, interpretation by requiring owners to report when the total amount of
electrolyte exceeds 500 pounds.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
What do I have to declare?
When do I have to declare it?
To whom do I have to declare it?
What forms do I have to use?
What if I don’t do it?
Most commercial battery back-up systems fall below government-required reporting levels, but large UPS
and DC plant batteries may have to comply. Failure to comply can result in costly penalties. Wading through
the Code of Federal Regulations can be a frustrating and arduous task.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Slide 22: Hazardous Substances-MSDS
Hazardous substances commonly listed on a lead-acid battery material safety data sheet (MSDS) are:
• Electrolyte
Electrolyte in a lead-acid battery is about 1/3 sulfuric acid (CASRN # 7664-93-9) and 2/3
water. Sulfuric acid is considered an “Extremely Hazardous Substance” (EHS).
It is also important to know if the electrolyte is in a liquid state (used in vented or flooded
batteries), or if it is immobilized (as in a Valve Regulated Lead Acid battery).
The laws that affect data centers got their start in 1980 with the EPA “Superfund.” The law was called the
“Comprehensive Environmental Response, Compensation, and Liability Act,” or CERCLA. In 1986,
CERCLA was amended by yet another Act of Congress called the “Superfund Amendments and
Reauthorization Act,” (SARA). Embedded in Title III of SARA was the creation of the “Emergency Planning
and Community Right-to-Know Act” (EPCRA).
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Laws say what must be done, and can be found in the U.S. Code.
• SARA is codified in 42 U.S.C 9601 et seq.
• EPCRA is codified in 42 U.S.C. 1101 et seq.
Both the US Code and the CFRs are generally referenced, so it is important to understand both. Take care
when reviewing these; they both have similar requirements, and they both have a similar numbering system.
The same chemical will have different reporting requirements and quantities from one section to the next.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
The Code of Federal Regulations is divided into 50 titles. OSHA is covered under Title 29, whereas EPA
rules fall under Title 40, Chapter I. Subchapter J covers Superfund, Emergency Planning, and Community.
Now that we have discussed where the rules can be found, let’s move on our next topic: planning for an
emergency.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
reach the 500 pound reporting threshold, whereas it took 746 cells of VRLA batteries to reach the same
threshold.
The older codes are not clear in making the distinction between flooded and VRLA batteries, and an
inspector might take a very narrow interpretation. Most practical installations of VRLA batteries do not
trigger the spill containment and occupancy separation requirements due to their low liquid electrolyte
volume. Battery systems based on VRLA batteries can be deployed, and are routinely deployed, within data
centers, network rooms and work environments in compliance with fire codes.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Slide 30: Conclusions
Most commercial applications of stationary lead-acid batteries will fall well below the reporting quantities
required by the EPA. Flooded batteries are more likely than VRLA batteries to require reporting, whether for
reporting inventory or for the release of hazardous materials. Large battery systems can add significantly to
a company’s compliance work. Although spills or releases of hazardous material (hazmat) for batteries at
the reporting threshold are quite rare, one must nevertheless report the presence of battery inventories in
the building to local and state authorities, and one must have an emergency preparedness plan in place.
© 2013 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.