KD220C3

Engine type 6068HFS86


Alternator type KH01220T
Performance class G3

GENERAL CHARACTERISTICS
Frequency (Hz) 50
Voltage (V) 400/230
Standard control panel APM303
Optional control panel APM403
Optional control panel M80
POWER
ESP PRP
Voltage Standby Amps
kWe kVA kWe kVA

415/240 176 220 160 200 306


400/230 176 220 160 200 318
DESCRIPTIVE
380/220 176 220 160 200 334
Kohler Co. Provides one-source responsibility for the
generating system and accessories 200/115 176 220 160 200 635
The generator set and its components are prototype- 240 TRI 176 220 160 200 529
tested, factory-built, and production-tested 230 TRI 176 220 160 200 552
A one-year limited warranty covers all systems and
components 220 TRI 176 220 160 200 577
Electronic governor
Mechanically welded chassis with antivibration
DIMENSIONS COMPACT VERSION
suspension Length (mm) 2398
Main line circuit breaker Width (mm) 1114
Radiator for core temperature of 48/50°C max with Height (mm) 1480
mechanical fan
Protective grille for fan and rotating parts (CE option) Dry weight (kg) 1811
9 dB(A) silencer supplied separately Tank capacity (L) 340
Charger DC starting battery with electrolyte
12 V charge alternator and starter DIMENSIONS SOUNDPROOFED VERSION
Delivered with oil and coolant -30°C
Commercial reference of the enclosure M226
Manual for use and installation
Length (mm) 3508
POWER DEFINITION Width (mm) 1200
PRP : Prime Power is available for an unlimited number of annual Height (mm) 1830
operating hours in variable load applications, in accordance with ISO
8528-1. ESP : The standby power rating is applicable for supplying Dry weight (kg) 2471
emergency power in variable load applications in accordance with ISO Tank capacity (L)
8528-1. Overload is not allowed
340
TERMS OF USE Acoustic pressure level @1m in dB(A) 77
According to the standard, the nominal power assigned by the genset is Sound power level guaranteed (Lwa) 97
given for 25°C Air Intlet Temperature, of a barometric pressure of 100
kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions Acoustic pressure level @7m in dB(A) 66
in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTY
For the generator sets used indoor, where the acoustic pressure levels
depend on the installation conditions, it is not possible to specify the
ambient noise level in the operating and maintenance instructions.
You will also find in our operating and maintenance instructions a
warning concerning the air noise dangers and the need to implement
appropriate preventive measures.

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03028 (KD220C3) 08/17
KD220C3
ENGINE CHARACTERISTICS

GENERAL ENGINE DATA EXHAUST


Engine model JOHN DEERE Exhaust gas temperature @ ESP 50Hz (°C) 548
Engine type 6068HFS86 Exhaust gas flow @ ESP 50Hz (L/s) 502
Air inlet Turbo Max. exhaust back pressure (mm H2O) 765
Cylinders arrangement L
Number of cylinders 6
FUEL
Displacement (L) 6.72
Air/Water DC Consumption @ 110% load (L/h) 48.6
Air coolant
Consumption @ 100% load (L/h) 46
Bore (mm) x Stroke (mm) 106 x 127
Consumption @ 75% load (L/h) 37.6
Compression ratio 17 : 1
1500 Consumption @ 50% load (L/h) 26.1
Speed (RPM)
Pistons speed (m/s) Maximum fuel pump flow (L/h) -
6.35
Maximum stand-by power at rated
202
RPM (kW) OIL
Frequency regulation, steady state (%) +/- 0.25% Oil capacity (L) 32
BMEP (bar) 21.9 Min. oil pressure (bar) 1.1
Governor type Electronic Max. oil pressure (bar) 3.8
Oil consumption 100% load (L/h) 0.1
COOLING SYSTEM Oil sump capacity (L) -

Radiator & Engine capacity (L) 27.6


Max water temperature (°C) - HEAT BALANCE
Outlet water temperature (°C) - Heat rejection to exhaust (kW) 112
Fan power (kW) 10 Radiated heat to ambient (kW) -
Fan air flow w/o restriction (m3/s) 4.9 Heat rejection to coolant (kW) 84
Available restriction on air flow (mm
-
H2O)
Type of coolant Glycol-Ethylene AIR INTAKE
Thermostat modulating range HT (°C) - Max. intake restriction (mm H2O) 637
Intake air flow (L/s) 215

EMISSIONS
Emission PM (g/kWh) 0.1
Emission CO (g/kWh) 1.15
Emission HC+NOx (g/kWh) 3.68
Emission HC (g/kWh) 0.13

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03028 (KD220C3) 08/17
KD220C3
ALTERNATOR CHARACTERISTICS

GENERAL DATA OTHER DATA


Alternator type KH01220T Continuous Nominal Rating 40°C (kVA) 200
Number of Phase Three phase Standby Rating 27°C (kVA) 220
Power factor (Cos Phi) 0.8 Efficiencies 100% of load (%) 92.5
Altitude (m) 0 to 1000 Air flow (m3/s) 0.48
Overspeed (rpm) 2250 Short circuit ratio (Kcc) 0.4010
Number of pole 4 Direct axis synchro reactance unsaturated (Xd) (%) 339
Capacity for maintaining short circuit at Quadrature-axis synchro reactance unsaturated (Xq)
No 173
3 ln for 10 s (%)
Insulation class H Open circuit time constant (T'do) (ms) 2351
T° class (H/125°), continuous 40°C H / 125°K Direct axis transient reactance saturated (X'd) (%) 14.4
T° class, standby 27°C H / 163°K Short circuit transient time constant (T'd) (ms) 100
AVR Regulation Yes Direct axis subtransient reactance saturated (X''d)(%) 11.5
Total Harmonic Distortion in no-load Subtransient time constant (T"d) (ms) 10
<2.5
DHT (%) Quadrature-axis subtransient reactance saturated
Total Harmonic Distortion, on load DHT (X"q) (%) 15.1
<2.5
(%) Subtransient time constant (T"q) (ms) 10
Wave form : NEMA=TIF <50
Zero sequence reactance unsaturated (Xo) (%) 0.6
Wave form : CEI=FHT <2 13.35
Negative sequence reactance saturated (X2) (%)
Number of bearing 1
Armature time constant (Ta) (ms) 15
Coupling Direct 0.79
No load excitation current (io) (A)
Voltage regulation at established rating 0.5
(+/- %) Full load excitation current (ic) (A) 3.03
Recovery time (Delta U = 20% 500 Full load excitation voltage (uc) (V) 41.3
transient) (ms) Engine start (Delta U = 20% perm. or 50% trans.)
Protection class IP 23 496.14
(kVA)
Technology Without collar or Transient dip (4/4 load) - PF : 0,8 AR (%) 13
brush No load losses (W) 3401.83
Heat rejection (W) 12894.02
Unbalanced load acceptance ratio (%) 100

DIMENSIONS
Dimensions soundproofed version Dimensions DW compact version
Commercial reference of the enclosure M226 Commercial reference of the enclosure -
Length (mm) 3508 Length (mm) 3560
Width (mm) 1200 Width (mm) 1180
Height (mm) 1830 Height (mm) 1874
Dry weight (kg) 2471 Dry weight (kg) 2231
Tank capacity (L) 340 Tank capacity (L) 868
Acoustic pressure level @1m in dB(A) 77 Acoustic pressure level @1m in dB(A) -
Sound power level guaranteed (Lwa) 97 Sound power level guaranteed (Lwa) -
Acoustic pressure level @7m in dB(A) 66 Acoustic pressure level @7m in dB(A) -

Dimensions DW soundproofed version Dimensions DW 48h soundproofed version


Commercial reference of the enclosure M226 DW Commercial reference of the enclosure M226 DW48
Length (mm) 3560 Length (mm) 3560
Width (mm) 1200 Width (mm) 1200
Height (mm) 2182 Height (mm) 2364
Dry weight (kg) 2811 Dry weight (kg) 3069
Tank capacity (L) 868 Tank capacity (L) 1630
Acoustic pressure level @1m in dB(A) 77 Acoustic pressure level @1m in dB(A) 77
Sound power level guaranteed (Lwa) 97 Sound power level guaranteed (Lwa) 97
Acoustic pressure level @7m in dB(A) 66 Acoustic pressure level @7m in dB(A) 66

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03028 (KD220C3) 08/17
KD220C3
CONTROL PANEL

APM303, comprehensive and simple APM403, basic generating set and power plant
control

The APM303 is a versatile unit which can be operated in


manual or automatic mode. Equipped with an LCD screen,
the user-friendly APM303 offers high-quality basic functions The APM403 is a versatile control unit which allows
to guarantee simple, reliable operation and supervision of operation in manual or automatic mode
your generating set. It offers the following features: Measurements : voltage and current
Measurements: kW/kWh/kVA power meters
phase-to-neutral and phase-to-phase voltages, active power Standard specifications: Voltmeter, Frequency meter.
currents, effective power, power factors, Kw/h energy meter Optional : Battery ammeter.
Fuel, oil pressure and coolant temperature levels J1939 CAN ECU engine control
Supervision: Alarms and faults: Oil pressure, Coolant temperature,
Modbus RTU communication on RS485 Overspeed, Start-up failure, alternator min/max, Emergency
Reports: stop button.
2 configurable reports Engine parameters: Fuel level, hour counter, battery
Safety features: voltage.
Overspeed, oil pressure Optional (standard at 24V): Oil pressure, water temperature.
Coolant temperatures Event log/ Management of the last 300 genset events.
Minimum and maximum voltage Mains and genset protection
Minimum and maximum frequency Clock management
Maximum current USB connections, USB Host and PC,
Maximum active power Communications : RS485 INTERFACE
Phase sequence ModBUS protocol /SNMP
Traceability: Optional : Ethernet, GPRS, remote control, 3G, 4G,
Stack of 12 stored events Websupervisor, SMS, E-mails
For further information, please refer to the data sheet for the
APM303.

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03028 (KD220C3) 08/17
KD220C3
CONTROL PANEL

M80, transfer of information Basic terminal block

The M80 is a dual-function control unit. It can be used as a


basic terminal block for connecting a control box and as an
instrument panel with a direct read facility, with displays The control unit can be used as a basic terminal block for
giving a global view of your generating set's basic connecting a control box.
parameters.
Offers the following functions:
Offers the following functions:
emergency stop button, customer connection terminal
Engine parameters: tachometer, working hours counter, block, CE.
coolant temperature indicator, oil pressure indicator,
emergency stop button, customer connection terminal
block, CE.

This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03028 (KD220C3) 08/17