FIRE NOTAS GENERALES

SPARE SP I V-8701C ME-8701C P-8701 A/B/C P-8703 FV General Notes


4"L6" PSV LPG STORAGE SPHERE LPG EDUCTOR LPG TRANSFER PUMPS LPG OFF-SPEC PUMP
SET AT 030-2 J
8720 6" 8703 DETAIL "A" 1. DIP LEG IN ACCORDANCE WITH LEVEL INSTRUMENT.
250 psi-g ZLO ZLC 2. SDV SHALL BE LOCATED AS CLOSE TO THE SPHERE AS IS PRACTICAL, AND ACCESSIBLE TO OPERATOR
NOTE 24 NOTE 19 4"-LG-87071-B2AL-VA FOR MAINTENANCE. VALVE IN HORIZONTAL POSITION.
NO POCKETS XXX XXX

3/4"BA-14

3/4"BA-76
8"x6" 8"BA-15A FIRE 3. DELETED.
SP I VC 4"BA-77 4"CK-04 4"x1½" 1½"-300# 4"x1½" 4"BA-77 4. ACCORDING TO CONSEQUENCES ANALYSIS REPORT LPG/F-PCF-GN-PRU-75-011, PROCESS LINES IN
A0G1 LO FP 4"L6" PSV 3/4"BA-76 FO I
6"x4" B2AL SET AT 030-2 J LPG STORAGE ZONE CAN BE EXPOSE TO DIRECT PRESSURIZED FLAME OR RADIATION HIGHER THAN

SEE DETAIL "D"


250 psi-g 8708 SEE DETAIL "D" NOTE 22 37.5 kW/m². THEREFORE IS REQUIRED TO COVER THOSE LINES WITH A LISTED/APPROVED

NOTE 26
16"-VC-07062-A0G1-N NOTE 26 FIRE-RESISTANCE RATING INTUMESCENT PAINTING.
NOTE 24
NO POCKETS 5. LIT-8715 (ALARM), MUST BE FROM DIFFERENT MANUFACTURER COMPARED TO LIT-8710/8711.

3/4"BA-14
8"BA-15A 16"x8" PI HH I I I
8"x6" PI 6. EXCESS VALVE FOR AUTOMATIC SPHERES SHUTDOWN (BASED ON HYDRAULIC CIRCUIT PRESSURE LOSE).
FIRE SP I LO FP 8709 2BZ 2BY SDY
A0G1 7. VALVE LOCATED AT SAFE PLACE IN ORDER TO BE OPERATED MANUALLY.
4"L6" PSV LL 8710
SET AT 030-2 J 6"x4" B2AL XXX 8. VENT/DRAIN AT LOWEST POINT OF PIPING.
262 psi-g 8719 9. FIRE PROOFING ON SPHERE SUPPORT STRUCTURE IN ACCORDANCE WITH API 2218.

2"-VC-07194-A0G1-N
START/STOP
NOTE 24 3JD 1A13 NOTE 21 10. NOTES 11, 12, 13, 14, 16, DELETED.
NO POCKETS H

3/4"BA-14
8"x6" 8"BA-15 HS ZSO ZSC PST 15. A VERY LOW PRESSURE DROP FLOW ELEMENT ANNUBAR TYPE. 12 DIAMETERS OF STRAIGHT PIPE LINE
PDI

2"-LG-87094-B2AL-VA
LO FP 3/4"GL-303 UPSTREAM AND 4 DIAMETERS DOWNSTREAM OF THE FLOW ELEMENT SHALL BE KEEPED.
A0G1 SEE DETAIL "H" 8701B XXX XXX XXX 17. MULTITEMPERATURE ELEMENT OF TANK GAUGING SYSTEM WITH STILLING WELL.
8715 3JD
6"x4" B2AL

4"-LG-87068-B2AL-VA
NOTE 26 2BW 2BV 2BL 3JD 18. RESTRICTIVE ELEMENT 1/8 IN HOLE.
3/4"BA-01 SEE DETAIL SDV

3/4"GL-303
3/4"GL-303 NOTE 27 MCC FIC 19. DRAINS AND VENTS ACCORDING TO DISCHARGE TYPE ARE GOING TO THE FOLLOWING P&DS:
3/4"GL-303 XXX

NOTE 26
SEE DETAIL "H"
HH NOTE 23 8703 DISCHARGE TYPE P&ID
LI 3/4"BA-01 SEE DETAIL "H" PDIT PIT 2CE PIT L PU-PRE-07-074-1/1

2"GL-305
3/4"BA-76
8710 3/4"BA-01 NOTE 26 PI VC COLD FLARE
FP LO 8715 8709 8710 PU-PRE-07-071-1/1
FP LC FP LO M 8718 VL LOW PRESSURE FLARE PU-PRE-06-061-1/1
6"BA-77F 6"BA-77F 6"BA-77F NOTE 23
HH FIT VH HIGH PRESSURE FLARE MP-PRE-05-002-1/1

3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1
LI
8703 6"-LG-87062-B2AL-VA DC CLOSED DRAIN PU-PRE-09-091-1/2-2/2

2"BA-77
MOV MOV

LC
8711 1500 MM LC

8"x6"
8"x6" 8"x6" SP I

A0G1
M M

B2AL
MIN. 8731 8733 8" 20. DELETED.
12"
013-2 J 21. PUMP SHUTDOWN IN CASE OF LL LEVEL IN THE SUCTION SPHERE SEE C&E FOR DETAILS.
10"-LG-87051-B2AL-VA 22. PUMP SHUTDOWN IN CASE OF ODORANT PACKAGE SHUTDOWN OR LPG TRUCK LOADING PACKAGE
LIT SHUTDOWN WHEN PUMP IS IN "TRUCK LOADING MODE" SEE C&E FOR DETAILS.
10" 10"BA-77A 6"CK-04 6"BA-77 6"

3/4"BA-76
8710 23. TRANSMITTER MUST BE SIL-2 CERTIFIED.
P-8701A

3/4"BA-76
2BE MOV SP F MOV 6"
SEE 3/4"BA-76 24. PSV INLET/OUTLET DIAMETERS CONFIRMED BASED ON FINAL VENDOR INFORMATION.

3/4
M FE
8732 M 25. DELETED.

8"-LG-87082-B2AL-VA

"B
LI DETAIL "C" 328-1 Y 8734

A-
1oo2 3/4"BA-14 NOTE 17 8703 26. FOR TYPICAL DRAIN ARRANGEMENT DETAILS SEE P&ID: LPG/F-PCF-GN-PRE-00-001-01.

7
3/4"BA-76 NOTE 31

6
8711 2BW SEE DETAIL "G" SEE DETAIL "G" 27. FOR MOTORS DETAILS SEE P&ID: LPG/F-PCF-GN-PRE-00-003-01.
LL PIT NOTE 26 FV NOTE 26 28. DELETED.

6"-LG-87065-B2AL-VA
2"-LG-87085-B2AL-VA TE 8" 8"-LG-87056-B2AL-VA 6"
8708 SEE 8704 29. EDUCTOR REQUIRES 5 STRAIGHT DIAMETERS UPSTREAM AND 10 STRAIGHT DIAMETERS
2"BA-05 8707 DETAIL "C" DOWNSTREAM.
LIT 4"-LG-87072-B2AL-VA
30"MW NOTE 18 30. DELETED.
LI 31. ADDITIONAL SCREEN TO BE PROVIDED FOR START UP PROCEDURE.

3/4"BA-76
8711
4"BA-77 4"CK-04 4"x1½" 1½"-300# 4"x1½" 4"BA-77

2"MDB2A1-6
8710 FO
LL 3/4"BA-76
SEE DETAIL "D" LAH LAL TAH TAL PAH
SEE DETAIL "C" NOTE 26 8715 8715 8707 8707 8708
LIT V-8701C NOTE 22 ATG SERVER
8715 PI HH XA LY LI TI PI
VENDOR CONTRACTOR PI
NOTE 5 SUPPLY 8711 2BZ 2BY 8715 8715 8715B 8707 8708
LL 8712 A
ATG GENERAL COMPENSATED
START/STOP ALARMA LEVEL
3JE 1A13 NOTE 21
H HS
PDI
8701B MULTIPOINT
HHL = 441" 8716 3JE
2BW 2BV 2BL 3JE

4"-LG-87069-B2AL-VA
NOTE 1

LI LIT TE PIT
NOTE 1

SEE DETAIL
NOTE 1

HL = 430"
NOTE 27 MCC
FIC 8715 8715 NOTE 5 8707 NOTE 17 8708 NOTE 18 H H H
8704 LI TI PI
PDIT PIT 2CE PIT GROSS
L

SEE DETAILS "J", "O"


8715A 8707A 8708A

GN-PRE-00-001-5/7
LL = 36" PI LEVEL
8716 8711 8712 L L
LLL = 20" M 8719
NOTE 23 NOTE 23 FIT

3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1
6"-LG-87063-B2AL-VA DETAIL "MOVS"
MOV 8704 MOV
M M YA HS ZS XLR XA
8741 8743
NOTE 9 NOTE 9 10"-LG-87050-B2AL-VA
OPEN / CLOSE 10" 6" C2/C5
HS

3/4"BA-76
10"BA-77A 6"CK-04 6"BA-77 HS: OPEN /CLOSE COMAND
P-8701B

3/4"BA-76
MOV SP MOV

329-2 J
F

I
8729B 3/4"BA-76 ASP ZS: STATUS OPEN / CLOSE

3/4
8742 M FE M XLR: STATUS RUN / STOP

"
328-1 Y 8744

BA
6"BA-77

8704 8700 XA: FAILURE ALARM

-7

SP
3/4"BA-76 NOTE 31 M

6
30"MW V.B SEE DETAIL "G" SEE DETAIL "G" YA: STATUS LOCAL/REMOTE
4"BA-77

6"-LG-87066-B2AL-VA
OPEN / 8" NOTE 26 FV NOTE 26 INSTR.
8"-LG-87057-B2AL-VA 6" 1½"
HS
10 FT

CLOSE 8705 PIPING


VC
MIN.

3/4"BA-01 3JC 2BW 8703B


EFV 4"-LG-87073-B2AL-VA PUMPS P-8701A/B/C P-8703
DC
12"BA-77A

MIN.

3/4"BA-76
SEE DETAIL "A" 8701C 4"BA-77 4"CK-04 4"x1½" 1½"-300# 4"x1½" 4"BA-77 1-1/2" TYPE CENTRIFUGAL CENTRIFUGAL
MIN.

NOTE 2 SEE DETAIL "D" FO THROUGHPUT 616 gpm 41.16 gpm


NOTE 6 SEE DETAIL "A" PRE-87-001 3/4"BA-76
4" SEE DETAIL "D" SEE DETAIL "F" DISCH. PRESSURE 305 psig 466 psig
OPEN / CLOSE FC NOTE 2 DIFF. PRESSURE 168 psi 309 Psi
NOTE 26 GN-PRE-00-001-4/7
12" DES. PRESSURE 485 psi-g 630 psi-g
4"-LG-87111-B2AL-VA

HS SDV FC 1A13 2BE 3JL NOTE 22 HOLD


6"CK-04

DES. TEMPERATURE 170 °F / -30 °F 170 °F / -30 °F


8728B 3JI 2BE 8728 SDV SDV PI HH SEE DETAIL "F"
PI OP. TEMPERATURE 110°F 110°F
8729 8703 8713 2BZ 2BY GN-PRE-00-001-5/7 SP. GR. AT COND. 0.505 0.505
VC NOTE 19
RO LL 8714 TRIM NUMBER LG-87002-B2AL-VA PG-87003-B2AL-VA
3/4"BA-01 NOTE 2 3"-VC-07075-A0G1-N
DC 6" VC
FC SEE DETAIL "A" 8703B START/STOP
B2AL
A0G1

SEE DETAIL "D" 1500 MM 3JF 1A13 NOTE 21 SPHERES V-8701C


H HS
PRE-87-001 MIN. PDI DIAMETER 43 ft 11 in
3"-LG-87048-B2A1-VA 8701C
4"CK-04 OP. PRESSURE 155 psig

4"-LG-87070-B2AL-VA
8717 3JF
3/4"BA-76

3"BA-77 3"GL-305 SP 2BW 2BV 2BL 3JF OP. TEMPERATURE 110°F


12"BA-77A

3"-LG-87101-B2AL-VA

NC I SEE DETAIL

THIS DOCUMENT IS PROPERTY OF TIPIEL SA IT MAY NOT BE COPIED, REPRODUCED AND/OR CIRCULATED WITHOUT AUTHORIZATION
MCC DES. PRESSURE 250 psi-g / FV

ESTE DOCUMENTO ES PROPIEDAD DE TIPIEL SA Y NO DEBE SER COPIADO, REPRODUCIDO Y/O CIRCULADO SIN SU AUTORIZACIÓN.
NOTE 27 FIC
3/4"GL-303

314 J 2CE DES. TEMPERATURE 170 °F / -30 °F


3/4"MDB2A1-1 NOTE 15 NOTE 8 PDIT 8705 MATERIAL LT.C.S
PIT PIT L
H PI
B2AL
A2A1

8717 TRIM NUMBER LG-87120-B2AL-VA


PDI PDIT FE FIT 8713 8714
M 8720
8704 8704 8709 8709 2BW NOTE 23 NOTE 23 FIT
3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1
ME-8701C 1-1/2" SEE DETAILS "J", "O"
MIN. 3"GL-305 MOV 8705 6"-LG-87064-B2AL-VA MOV
NOTE 29 GN-PRE-00-001-5/7
M M
3"-DC-09171-A2A1-VA

DC 8751 8753 DOCUMENTOS DE REFERENCIA


2"CK-04 SEE DETAIL "F" SP I HH Reference Documents
FI
GN-PRE-00-001-4/7 C2/C5 NOTE 19 10"-LG-87049-B2AL-VA REF.
DOCUMENTO No.
REV.
DESCRIPCIÓN
329-2 J 8709 Document No. Description
HOLD ASP 10" 10"BA-77A 6"CK-04 6"BA-77 6"
P-8701C

3/4"BA-76

3/4"BA-76
SEE DETAIL "F" MOV SP F MOV
1-1/2" 8705 3/4"BA-76
3/4

GN-PRE-00-001-5/7 8752 M FE M
"

3/4"MDB2A1-1 328-1 Y 8754


PIPING

BA
INSTR.
4"BA-77

8705
-7

3/4"BA-76 NOTE 31
6

SEE DETAIL "G" SEE DETAIL "G"


OPEN / CLOSE

6"-LG-87067-B2AL-VA
8" NOTE 26 NOTE 26
MOV 8"-LG-87058-B2AL-VA 6" REVISIONES
HS FV Revisions
8723 M 0 29-JUN-2018 ISSUED FOR CONSTRUCTION E.GARCIA I.SANCHEZ O.SANGUINOD.MANRIQUE
8730B 3JQ 2BN 1A13 8710

Calle 38 No. 8-62 Bogotá - Colombia.


NOTE 25 (CONTRACT 3010893)
2"-LG-87116-B2AL-VA D3 26-APR-2018 DETAILED ENGINEERING FINAL ISSUE E.GARCIA I.SANCHEZ O.SANGUINOD.MANRIQUE
OFF SPEC MIN. FLOW

3/4"BA-76
2" (CONTRACT 3010893)
TO LPG STORAGE SPHERES 2"BA-77 2"CK-04 2"x1" 1"-300# 2"x1" 2"BA-77
FO A2 01-FEB-2018 ISSUED FOR COMMENTS M.SANTAMARIA I.SANCHEZ O.SANGUINOD.MANRIQUE
MP-PRE-87-001-1/1 3/4"BA-76 (CONTRACT 3010893)
D2 29-DEC-2016 APRROVED FOR DESIGN (REVISED AHS SHOWN) C.LOPEZ H.MONTOYA O.SANGUINO A.ARRIETA
SEE DETAIL "D"
NOTE 26 NOTE 19 D1 15-NOV-2016 APPROVED FOR DESIGN C.LOPEZ H.MONTOYA O.SANGUINO A.ARRIETA
A1 28-SEP-2016 ISSUE FOR COMMENTS C.LOPEZ H.MONTOYA O.SANGUINO A.ARRIETA
SDV PI VC
MOV FECHA DESCRIPCIÓN PREPARÓ CHEQUEÓ APROBÓ AUTORIZÓ
REV. Date Description Prepared by Checked by Approved by Authorized by
8730 8724 8726 HH
LL PI
MOV 3JX 1A13 NOTE 21 1-VC-07274-A0G1-N
12" THERMAL
8721 8728
M

4" FC 3/4"X1"
NOTA 7 H SET AT
MOV START/
M

4" 4" DIB 6"CK-04 PDI STOP HS 2BW 2BV 2BL 630 psi-g
M

8725 6"
B2AL 8725 3JX
4"-LG-26042-B2AL-VA

8703AB PSV NOTE 24


M

6"
A1W1 MOV 8"-LG-87001-B2AL-VA
8721
M

8" ½"-LG-87157-B2AL-VA SEE DETAIL 2BG 2BJ 2BM

2"-LG-87115-B2AL-VA
MCC 3JX
4"-NT-67044-A1W1-VA

MOV 8726 NOTE 27


6"-LG-87083-B2AL-VA

6"-LG-87084-B2AL-VA

3/4"BA-900
12"-LG-87048-B2AL-VA

3/4"BA-14
FIC
8"-LG-87055-B2AL-VA

8722 SP
A0G1 1"BA-14
I
INGENIERÍA COMPRAS CONSTRUCCIÓN Y PUESTA EN

1"x3/4"
8710 B2AL LO FP
4"CK-30 PDIT PIT PIT L 328-2 J
PI 3/4"GL-303
FROM LPG REFLUX PRODUCT
PUMPS P-2603 A/B
8725 8726 M 8728 SERVICIO DE LA PLANTA DE ESTABILIZACIÓN DE
8727 3/4"BA-76
MP-PRE-87-001-1/1 FIT TO LPG TRUCK LOADING CONDENSADOS DEL CPF CUPIAGUA
3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1

3/4"MDB2A1-1
FP LO
TO LGP STORAGE SPHERES 8710 TA-PRE-87-003-1/1
6"-LG-87036-B2AL-VA 1"BA-76
MP-PRE-87-001-1/1 ½"
-6 600#
MIN. PUMP FLOW 00
# 300#
TO DEETHANIZER COLUMN
CT-2603
PIPING AND INSTRUMENTATION DIAGRAM
3"-LG-87112-B2AL-VA MP-PRE-26-004-1/1
FROM LPG STORAGE 3"BA-77 300#
2"-LG-87114-B2AL-VA
2"CK-04 2"BA-77
LPG STORAGE PRODUCT SPHERE AND PUMPS
P-8703

3/4"BA-76

3/4"BA-76
SPHERES SP F 600#
12-LG-87039-B2AL-VA 3/4"BA-76
3/4

MP-PRE-87-001-1/1 FE ESCALA CONTRATO PLANO No. HOJA


"B

328-1 Y REV.
A-

Scale Contract Drawing No. Sheet


FROM LPG STORAGE 8710 RO
76

NOTE 31
SPHERES SEE DETAIL "G" SEE DETAIL "G"
INTERNAL TRANSFER SUCTION PUMP LINE 8"-LG-87047-B2AL-VA 6"-DO-87124-A2A1-UC 8708 DE
MP-PRE-87-001-1/1 NOTE 26 NOTE 26 N/A 3010893 LPG/F-PCF-TA-PRE-87-002-1/1 01 Of 01 0
TO LPG STORAGE SPHERES DO
CÓDIGO TIPIEL:
INTERNAL TRANSFER LINE 6"-LG-87044-B2AL-VA 1348-0000-PID-0021-12-01
MP-PRE-87-001-1/1
ARCHIVO CAD: LPGFPCFTAPRE87002.1-1.0 PID - LPG SPHERES AND PUMPS.dwg FDP ISO A1_1 : ISO A1 841x 594mm