Sr. No. Test Standard Description Lab Name & Country
TEST RESULTS
PARAMETERS RESULTS
SAMPLE TYPE AEROFOAM NBR/FLEXICELL NBR
SUPPORT / FACING NIL
NOM. THICKNESS (mm) : 40
NOM. DENSITY (kg/m3) : 60
SPECIFICATION LIMIT (kg/m3) NG
SPECIMEN NO 1 2 3 4 5
APPARENT DENSITY (kg/Cubic m) 70.5 72.0 72.5 72.5 74.0
Material tested: Sections of a black foamed rubber plate with a wall thickness of approx. 25mm
by proxy
The test results and statements presented in this test report refer exclusively to the indicated test material. The reproduction, duplication, translation or use of this report for advertising
purposes – no matter wether unabridged, abridged or in extracts – requires the written consent of the State Materials Testing Institute Darmstadt.
Test Report F 17 0236
Page 2 / 3
3 Results
The test conducted on the material sample labelled "AEROFOAM NBR" in the way as described in chapter 2
yielded the following levels - expressed as mas.-% - after filtration and potentiometric respectively photometric
analysis of the eluate as means of double determinations as shown in table 1.
Table No. 1
Test Report F 17 0236
Page 3 / 3
pH Value
7,03 ± 0.06
Table No. 2
4 Assessment
According to standard DIN 1988 ("Technical Rules for Drinking Water Installations, Prevention of Corrosions
Damage and Calculus Build-up"), part 200, paragraph 14.2.5 „Compatibility with pipe materials“, Version of
May 2012, the following requirements have been specified, among other things:
"Insulating materials for tubes of stainless steels must not exceed a mass content of 0.05 % of water-soluble chloride
ions."
Furthermore, it says:
„Insulations for copper materials must be free of nitride (mass percentage rate<0.01 %) and must not contain an
ammonia mass content of more than 0.2 %.”
These requirements are completely fulfilled by the tested insulation material labelled "Aerofoam NBR/Flexicell
NBR”.
Zentrum für Konstruktionswerkstoffe
Staatliche Materialprüfungsanstalt Darmstadt
Fachgebiet und Institut für Werkstoffkunde
Prof. Dr.-Ing. Matthias Oechsner
Material tested: A section of a black foamed insulation board with a wall thickness of approx. 25 mm
by proxy
The test results and statements presented in this test report refer exclusively to the indicated test material. The reproduction, duplication, translation or use of this report for advertising
purposes – no matter wether unabridged, abridged or in extracts – requires the written consent of the State Materials Testing Institute Darmstadt.
Test Report F 17 0237.1
Page 2 / 3
The determination of the chloride and fluoride anions was carried out using ion chromatography (IC) in
accordance with sections 7.2.2.2 and 7.2.3.2 of the standard.
The determination of the silicate and the sodium content of the extract were made using inductively coupled
plasma atomic emission spectrometry (ICP-AES) in accordance with sections 7.2.4.3 and/or 7.2.5.3.
The pH value was determined using a pH measurement device in accordance with section 7.2.6 of the standard.
pH value 7,74 --