STH/N/5.

10F-02
TEST REPORT
CERTIFICATE NO. STHDGG19022 PAGE 1 of 1

SERVICE REQUEST NO.


719010 SERVICE REQUEST DATE 18.07.2019
DATE OF ISSUE 20.07.2019 Sample recd on 18.07.2019
NAME & ADDRESS OF CUSTOMER SAMPLE DETAILS
M/s. Description : DG Noise
Weather condition : Clear sky
Gaur City Mall, Plot no.-C-1B/GH-01, Date of monitoring : 18.07.2019
Gaur City, Greater Noida. DG Capacity : 2000 KVA
DG Identification : Make: Cummins
Monitoring done by : Mr. Kushal Kant Sharma
Name of customer representative : Mr Justin
Instrument used : Luttron, Sound level meter, model no.
SL -4033SD, sr no. I.333999

TEST RESULTS

DG NOISE Level

Results Standard Limit


S.NO Parameter Units Method Adopted
as per *CPCB

Noise Level When dB(A) - SHR/SOP/NSE-02


1. 90.36
canopy is open
Noise level when canopy dB(A) 85 SHR/SOP/NSE-02
2. 64.60
is closed (at 1m distance)
3. Insertion Loss dB(A) 25.76 25 (minimum) SHR/SOP/NSE-02

******

*CPCB- Central Pollution Control Board

For Shreya Realty Pvt Ltd

Checked By. Authorized Signatory

Note 1. The results given above are related to the observed values at the time of monitoring. The customer asked for the
above tests only.
2. The results given above are related to the tested sample and mentioned parameters. Endorsement of product is
neither inferred nor implied.
3. Total liability of our works is limited to invoiced amount.
4. This report can not be used as evidence in a court of law without the written approval of the lab.
5. Certificate shall not be reproduced, except in full, without prior written approval of the laboratory.
6. Any sort of play by the customer with the data of this certificate shall be illegal.