V3R14M2 db170327.

16

User SPL Cold room


7/22/2020

Internal lenght m 4.000 Internal volume m3 34.800


Internal width m 3.000 Cold room position Inside
Internal height m 2.900 Trafic Medium

Insulating Thickness Conductivity Ext. T. wall


mm W/(m*°C) °C
Wall A Polyurethane foam 24 kg/m3 200 0.023 20.0
Wall B Polyurethane foam 24 kg/m3 200 0.023 20.0
Wall C Polyurethane foam 24 kg/m3 200 0.023 20.0
Wall D Polyurethane foam 24 kg/m3 200 0.023 20.0
Ceiling Polyurethane foam 24 kg/m3 100 0.023 20.0
Floor Polyurethane foam 24 kg/m3 120 0.023 20.0

3 - MEAT Mean_value
Freezing point °C -2.2
Water content % 64
Specific heat BEFORE freezing kJ/(kg*°C) 2.99
Latent heat for freezing kJ/kg 205.30
Specific heat ABOVE freezing kJ/(kg*°C) 1.56
Respiration heat W/kg*24h 0

Cold room Frozen products preserv.


Max room capacity by load 350.00 kg/m3 kg 8526.000
Daily load kg 4000.000

Outside temp. / Rel. Hum. °C / % 20.0 / 55


Air inlet temperature °C -22.0
Load temperature °C -16.0
Cooling time h 6
Number of personnel in room 1
Hours of stay in room h 2.0
Lighting W/m2 10

Walls dispersions 24.00 h kW 11.244


Air changes 24.00 h kW 10.282
Ventilation 24.00 h kW 3.263
Product freezing 24.00 h kW 41.593
Respiration 24.00 h kW 0
Packaging 24.00 h kW 0
Personnel 24.00 h kW 0.869
Lighting 24.00 h kW 0.240
Other 24.00 h kW 1.200

TOTAL 24.00 h kW 68.690

Equipment running hours h 18.00

Hourly equipment load kW 3.816