A) PG11 cable gland (IP65/67)
~120
ø40 B) Test magnet
B C) G1A (cylindrical), 1 NPT (conical), R 1
41 (conical), made of corrosion resistant steel
D) Vibration fork made of heavy duty corrosion
C resistant steel
E) Green light-emitting diode "ready to operate"
19
F) Red light-emitting diode for switch indicator
"circuit cut off"
128
G) The connector housing can be mounted at a 90°
D angle.
9
20
28
E
F
G
LVL-T1-!!S-!!PG-!!
Vibracon LVL-T1
Function
Features
• Vibration limit switch for liquids
• Level limit switch for application in
storage tank, stirring container and
pipeline with liquids
• Due to its compact construction, it
can be directly connected to a Electrical connection
miniature contactor, magnet
operated valve or programmable AC connection
logic control (PLC) Maximum fail-safe mode Minimum fail-safe mode
R
min.
R N (3)
access
PE PE
• Rugged stainless steel housing,
allows use in rough ambient R = external load
DC connection
conditions
Maximum Minimum
• Function test with testing magnet
0.5 A
under built-in condition + R
0.5 A
+ R
• Function control with outside
PE PE
indication of the switching state and
external testing • AC version (WA):
Always connect the Vibracon in series with a load! Take into account the voltage drop via the Vibracon
27.03.2002
• Low-cost plug connection when switched in circuit and the residual current when isolated (see technical data, output) and, for low
supply voltages, take into account the voltage drop via the load, in order to ensure that the terminal volt-
age on the Vibracon does not fall below the permissible value.
• DC version (E5):
Date of issue
Should be used in conjunction with programmable logic controllers (PLC). Positive signal on the Vibracon
switch output (PNP).
Vibracon LVL-T1
Application
Description Level limit switch for application in storage tank, stirring container and pipeline with liquids
Output characteristics
Alarm signal Output blocked
Fail-safe mode Minimum or maximum fail-safe mode, determined by the way of connection
Switching time approx. 0.5 s when covering, approx. 1.0 s when uncovering the vibration fork
Load Alternating current (load switched across thyristor directly in power supply circuit ):
• transient (40 ms): max. 1.5 A, max. 375 VA at 250 V or max. 36 VA at 24 V (not short- circuit proof)
• continuous: max. 87 VA at 250 V, max. 8.4 VA at 24 V; min. 2.5 VA at 250 V (10 mA), min. 0.5 VA at 24 V
(20 mA)
• Voltage drop via LVL-T1 max. 12 V
• Residual current max. 4 mA with blocked thyristor
Direct current (the load is switched via a transistor and a separate connection):
• transient (1 s): max. 1 A, max. 55 V (overload and short-circuit protection)
• continuous: max. 350 mA max. 0.5 µF at 55 V, max. 1 µF at 24 V
• Residual voltage < 3 V (with closed transistor)
• Residual current < 100 µA (with open transistor)
Auxiliary energy
Electrical connection This device may be used with any sequential circuit, as long as the circuit can support the electrical circuit
values of the switching elements.
Supply voltage Alternating current (WA): 19 ... 253 V AC, 50/60 Hz, direct current (E5): 10 ... 55 V DC
Current consumption Alternating current (WA): max. 4 mA (stand by), direct current (E5): max. 15 mA
Residual ripple Direct current: max. 1.7 V, 0 ... 400 Hz
Reverse polarity protection yes
Accuracy of measurement
Hysteresis approx. 4 mm with vertical mounting
Operating conditions
Mounting conditions
Mounting position any position
A) vertical installation
B) horizontal installation
A C) Installation in 1" nozzles (A to C for the entire viscosity
range up to 10000 mm²/s)
u Switching point depending on the installation direction
25
max. 60
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany (06 21) 7 76-0 • USA (330) 4 25 35 55 • Singapore 67 79 90 91 • Internet http://www.pepperl-fuchs.com 2
Vibration limit switch Technical data
Vibracon LVL-T1
Vibracon LVL-T1
Mechanical construction
Design Compact version, installation with socket spanner or box spanner SW 41
Versions Compact version
• LVL-T1-G3S-E5PG-NA, process connection G1, 1.4571, 10 ... 55 V DC, PNP 3-wire, connector PG11
• LVL-T1-G3S-E5PG-WH, process connection G1, 1.4571, 10 ... 55 V DC, PNP 3-wire, connector PG11,
overspill protection WHG
• LVL-T1-G3S-WAPG-WH, process connection G1, 1.4571, 19 ... 253 V AC, 3-wire, connector PG11,
overspill protection WHG
All above-mentioned versions are also available with thread 1 NPT.
27
Sealing
Ø60
G1
Welding bushing
LVL-Z61
Socket spanner
LVL-Z64
27.03.2002
Date of issue
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
3 Pepperl+Fuchs Group • Tel.: Germany (06 21) 7 76-0 • USA (330) 4 25 35 55 • Singapore 67 79 90 91 • Internet http://www.pepperl-fuchs.com
Technical data Vibration limit switch
Vibracon LVL-T1
L V L – T 1 – S – –
Approvals
NA No approval
WH Overspill protection WHG
CG CSA general purpose
Electrical connection
PG PG11 connector, ISO 4400, IP65/IP67
PN Connector ½ NPT, ISO 4400, IP65
Electrical output
WA 19 ... 253 V AC, 3-wire
E5 10 ... 55 V DC, PNP 3-wire
Fork surface
S Standard surface, Ra < 3.2 mm
Process connection
G3 Thread G1 BSP, 1.4571
N3 Thread 1 NPT, 1.4571
R3 Thread R 1 BSP 1.4571, DIN 2999
27.03.2002
Date of issue